Select Battery Type—REQUIRED

CAUTION:

The Battery Type DIP Switch setting must

match the type of batteries you connect, or your batteries
may be degraded or damaged over an extended period of
time. See “Battery Selection,” p. 8 for more information.

Battery Type

Switch Position

Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down (factory setting)

A1

A2

A3

A4

INPUT C/B 10A

OUTPUT C/B 12A

B4

B3

B2

B1

A4

A3

A2

A1

Group B Dip Switches 

Group A Dip Switches 

Group A DIP Switches 

Using a small tool, configure your Inverter/Charger by setting the four Group A DIP Switches (located on the front panel of your unit; see
diagram) as follows:

A1

Operation 

(continued)

Resetting Your Inverter/Charger to Restore AC Power

Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your
electrical system. To restore normal functioning:

Overload Reset:

Switch operating mode switch to “OFF” or “DC OFF” and remove some of the connected electrical load (ie: turn off some

of the AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch
back to either “AUTO/REMOTE” or “CHARGE ONLY.” 

Select Low AC Input Voltage
Point for Switching to Battery—
OPTIONAL*

Switch 

Voltage

Position

105V

#A4 Up & #A3 Up

95V

#A4 Up & #A3 Down

85V

#A4 Down & #A3 Up

75V

#A4 Down & #A3 Down 
(factory setting)

A1

A2

A3

A4

A1

A2

A3

A4

A1

A2

A3

A4

A1

A2

A3

A4

A3

A4

* Most of your connected appliances and equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage
Point (DIP Switch #2 of Group A) is set to 135V and its Low AC Voltage Input Point (DIP Switches #3 and #4 of Group A are set to
95V. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that would have little
effect on equipment operation, you may wish to adjust these settings. By increasing the High AC Voltage Point and/or decreasing the
Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.

Configuration

Set Configuration DIP Switches

Using a small tool, set the Configuration DIP Switches (located on the front panel, see diagram) to optimize Inverter/Charger operation
depending on your application.

Charger Inhibit

Function

Switch Position

Charger Inhibited

Up

Charger Enabled

Down (factory setting)

A2

A1

A2

A3

A4

Содержание PowerVerter 93-2642

Страница 1: ...lt In ISOBAR Surge Protection Automatic Overload Protection Ideal Output for All Loads Frequency Controlled Output Automatic Load Switching Balanced Load Sharing Better for Your Batteries Faster Batte...

Страница 2: ...e hydrogen gas can accumulate near batteries if they are not kept well ventilated your batteries should not be installed whether for a mobile or stationary application in a dead air compartment Ideall...

Страница 3: ...e Circuit Breaker protect your Inverter Charger against damage due to charger failure See Operation section for resetting instructions Remote Control Module Connector allows remote monitoring and cont...

Страница 4: ...details LINE Green LED If the operating mode switch is set to AUTO REMOTE this light will ILLUMINATE CONTINUOUSLY when your connected equipment is receiving continuous AC power supplied from a utility...

Страница 5: ...d of the unit Wait one minute then switch operating mode switch back to either AUTO REMOTE or CHARGE ONLY Select Low AC Input Voltage Point for Switching to Battery OPTIONAL Switch Voltage Position 10...

Страница 6: ...it The figures show how to set your DIP Switches for charger limiting B1 B2 Set Battery Charging Amps OPTIONAL Check specifications for your unit s high and low charging amp options By setting on high...

Страница 7: ...module Connect Battery Temperature Sensing Cable OPTIONAL The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature Conne...

Страница 8: ...ttery voltage 12 to determine the DC amps required STEP 3 Estimate Battery Amp Hours Required for operation unsupported by the alternator Multiply the DC amps required from step 2 above by the number...

Страница 9: ...ide weather conditions Using the measurements from the diagram install two user supplied 6 mm fasteners into a rigid horizontal surface leaving the heads slightly raised Slide the Inverter Charger for...

Страница 10: ...listed fuse s and fuse block s within 18 inches of the battery The fuse s rating must equal or exceed the Minimum DC Fuse Rating listed in your Inverter Charger s specifications See Specifications fo...

Страница 11: ...ug on the unit In any case the incoming conduit must be bonded to earth or vehicle ground and the incoming conduit must be bonded to the outgoing conduit 1 2 3 4 5 AC Input Output Connection HOT IN NE...

Страница 12: ...you will need to manually reset the unit by moving the Operating Mode Switch to OFF for two seconds then returning it to AUTO REMOTE False reading due to undersized or Use sufficient size DC cable suf...

Страница 13: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...

Отзывы: