Troubleshooting

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output

Unit is not properly connected to utility power

Connect unit to utility power.

(All Indicator Lights are OFF)

Operating Mode Switch is set to “OFF” and AC input

Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY”.

is present.

This is normal when the Operating Mode Switch is set to

No correction is required. AC output will return when AC input 

“CHARGE ONLY” and AC input is absent.

returns. Set Operating Mode Switch to “AUTO/REMOTE” if you
require AC output.

Circuit breaker is tripped.

Reset circuit breaker.

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

battery damage). The problem may be with connected

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE” or

auxiliary chargers, if any, or with the unit’s charger.

“CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Unit has shut down due to excessive battery discharge.

Use an auxiliary charger* to raise battery voltage. Check external
battery connections and fuse. Unit automatically resets when
condition is cleared.

Unit has shut down due to overload.

Reduce load. Reset by moving Operating Mode Switch to “OFF”.
Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY”.

Battery Not Recharging

Connected batteries are dead.

Check and replace old batteries.

(AC Input Present)

Battery fuse* is blown.

Check and replace fuse.*

Battery cabling* is loose.

Check and tighten or replace cabling.*

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

battery damage). The problem may be with connected

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE” or

auxiliary chargers, if any, or with the unit’s charger.

or “CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Input circuit breaker is tripped.

Reset circuit breaker.

All Three “BATT VOLT/CHRG CURR”

Battery is excessively discharged. Unit will shut down to

Use an auxiliary charger* to raise battery voltage. Check external

LEDs are slowly flashing (½ second 

prevent battery damage.

battery connections and fuse. Unit automatically resets when

flashes) with Operating Mode Switch in 

condition is cleared.

the “AUTO/REMOTE” position.

All Three “BATT VOLT/CHRG CURR”

Battery is overcharged. Unit will shut down to prevent

Disconnect any auxiliary chargers. Reset by moving Operating Mode

LEDs are rapidly flashing (¼ second 

battery damage. The problem may be with connected auxiliary

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE.”

flashes) with Operating Mode Switch in 

chargers, if any, or with the unit’s charger.

If unit remains in shutdown mode after several attempts to reset,

the “AUTO/REMOTE” position.

contact Tripp Lite Customer Service for assistance.

Red “LOW” Battery Indicator Light is

Battery voltage is low. Unit has shut down

If AC power (utility- or generator-supplied) is present, the unit will

flashing with Operating Mode Switch in the 

to protect battery from damage.

automatically reset itself and start recharging connected batteries.

”AUTO/REMOTE” position.

However, if an external charger is used to recharge the batteries,
you will need to manually reset the unit by moving the Operating
Mode Switch to “OFF” for two seconds then returning it to
“AUTO/REMOTE”.

False reading due to undersized or

Use sufficient size DC cable sufficiently connected to 

insufficiently connected DC cabling.

Inverter/Charger.

Red “LOAD” Operation

Inverter is overloaded. Unit will automatically shut down

Reduce load. Reset by moving Operating Mode Switch to “OFF”.

Indicator Light flashing

after 5 seconds.

Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY”.

* User-supplied.

Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service at (773) 869-1234
before returning your unit for service.

Limited Warranty

Tripp Lite warrants its Inverter/Chargers to be free from defects in materials and workmanship for a 30 month period from the date of retail purchase by end user.

Tripp Lite’s obligation under this warranty is limited to repairing or replacing (at its sole option) any such defective products. To obtain service under this warranty you must obtain a Returned Material Authorization
(RMA) number from Tripp Lite or an authorized Tripp Lite service center. Products must be returned to Tripp Lite or an authorized Tripp Lite service center with transportation charges prepaid and must be
accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has been damaged by accident, negligence or
misapplication or has been altered or modified in any way, including opening of the unit’s casing for any reason. This warranty applies only to the original purchaser who must have properly registered the product
within 10 days of retail purchase.

EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS
PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Tripp Lite is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of
software, loss of data, costs of substitutes, claims by third parties, or otherwise.

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label,
along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking
name or model number of the product.

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.

Note on Labeling  

Two symbols are used on the labels.

V~

: AC Voltage    

V

: DC Voltage

WARRANTY REGISTRATION

Visit www.tripplite.com/warranty to register the warranty of your new Tripp Lite product. You'll be automatically
entered into a drawing for a chance to win a FREE Tripp Lite product!*

* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.

Содержание PowerVerter 93-2642

Страница 1: ...lt In ISOBAR Surge Protection Automatic Overload Protection Ideal Output for All Loads Frequency Controlled Output Automatic Load Switching Balanced Load Sharing Better for Your Batteries Faster Batte...

Страница 2: ...e hydrogen gas can accumulate near batteries if they are not kept well ventilated your batteries should not be installed whether for a mobile or stationary application in a dead air compartment Ideall...

Страница 3: ...e Circuit Breaker protect your Inverter Charger against damage due to charger failure See Operation section for resetting instructions Remote Control Module Connector allows remote monitoring and cont...

Страница 4: ...details LINE Green LED If the operating mode switch is set to AUTO REMOTE this light will ILLUMINATE CONTINUOUSLY when your connected equipment is receiving continuous AC power supplied from a utility...

Страница 5: ...d of the unit Wait one minute then switch operating mode switch back to either AUTO REMOTE or CHARGE ONLY Select Low AC Input Voltage Point for Switching to Battery OPTIONAL Switch Voltage Position 10...

Страница 6: ...it The figures show how to set your DIP Switches for charger limiting B1 B2 Set Battery Charging Amps OPTIONAL Check specifications for your unit s high and low charging amp options By setting on high...

Страница 7: ...module Connect Battery Temperature Sensing Cable OPTIONAL The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature Conne...

Страница 8: ...ttery voltage 12 to determine the DC amps required STEP 3 Estimate Battery Amp Hours Required for operation unsupported by the alternator Multiply the DC amps required from step 2 above by the number...

Страница 9: ...ide weather conditions Using the measurements from the diagram install two user supplied 6 mm fasteners into a rigid horizontal surface leaving the heads slightly raised Slide the Inverter Charger for...

Страница 10: ...listed fuse s and fuse block s within 18 inches of the battery The fuse s rating must equal or exceed the Minimum DC Fuse Rating listed in your Inverter Charger s specifications See Specifications fo...

Страница 11: ...ug on the unit In any case the incoming conduit must be bonded to earth or vehicle ground and the incoming conduit must be bonded to the outgoing conduit 1 2 3 4 5 AC Input Output Connection HOT IN NE...

Страница 12: ...you will need to manually reset the unit by moving the Operating Mode Switch to OFF for two seconds then returning it to AUTO REMOTE False reading due to undersized or Use sufficient size DC cable suf...

Страница 13: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...

Отзывы: