6A

Configuration 

(continued)

Set Battery Charging Amps—OPTIONAL

Check specifications for your unit’s high-
and low-charging amp options. By setting
on high charging, your batteries will
charge at maximum speed. When setting
on low charging, you lengthen the life of
your batteries (especially smaller ones).

Battery Charger

Switch Position

Low Charge Amps

Up (factory setting)

High Charge Amps

Down

CAUTION: When switching to the High Charge Amp setting, the user must ensure that the amp
hour capacity of their battery system exceeds the amperage of the High Charge Amp setting or
the batteries may be damaged or degraded.

Select Equalize Battery Charge—OPTIONAL

This DIP Switch is momentarily
engaged to begin the process of equal-
izing the charge state of your battery’s
cells by time-limited overcharge of all
cells. This can extend the useful life of
certain types of batteries; consult with your battery’s manufac-
turer to determine if your batteries could benefit from this
process. The charge equalization process is automatic; once
started, it can only be stopped by removing the input power.

Setting Procedure

• Move to “Equalize” (DOWN) position for three seconds.
• Move to “Reset” (UP) position and leave it there. This is the 

factory default setting.

CAUTION: Do not leave DIP switch #3 in the down position after beginning process. Battery
charge equalization should only be performed in strict accordance with the battery manufacturer’s
instructions and specifications.

Battery Charge

Switch Position

Reset

Up (factory setting)

Equalize

Down—momentarily

Select Battery Charger-Limiting
Points—OPTIONAL

Most Limiting

(#B1 & #B2 Up, factory

setting): Charger-limiting takes effect the
moment any 230V AC load is applied;
charger output falls gradually from full output at no 230V load
passing through to no output at full load.

Less Limiting

(#B1 Down & #B2 Up):

Charger-limiting begins when the
Inverter/Charger’s load reaches 33% of the
Inverter/Charger’s load rating. Charger
output falls gradually from full output at
33% of the Inverter/Charger’s load rating to about 33% of full output
at full load.

Least Limiting

(#B1 Up & #B2 Down):

Charger-limiting begins at when the
Inverter/Charger’s load reaches 66% of the
Inverter/Charger’s load rating. Charger
output falls gradually from full output at
66% of the Inverter/Charger’s load rating to about 66% of full output
at full load.

No Limiting

(#B1 & #B2 Down): No

charger-limiting occurs at any load size.

B1

B2

B3

B4

B1

B2

B3

B4

B1

B2

B3

B4

B1

B2

B3

B4

B1

B2

B3

B4

Set Battery Charge Conserver (Load Sense) Control—OPTIONAL (Not on 750 or 1250 models)

In order to save battery power, the unit's inverter automatically shuts off in the absence of any power demand from
connected equipment or appliances (the electrical load). When the Inverter/Charger detects a load, it automatical-
ly turns its inverter function on. Users may choose the minimum load the Inverter/Charger will detect by adjusting
the Battery Charge Conserver Control (see diagram). Using a small tool, turn the control clockwise to lower the
minimum load that will be detected, causing the inverter to turn on for smaller loads. When the control is turned
fully clockwise, the inverter will operate even when there is no load. Turn the control counterclockwise to increase the minimum load that
will be detected, causing the inverter to stay off until the new minimum load is reached. 

NOTE: The factory setting for the control is fully clockwise. However, based on the threshold load to which you’d like the inverter to respond, you should adjust the control counterclockwise to reduce
its sensitivity until the inverter is active only when connected equipment or appliances are actually in use.

Connect Remote Control—Optional

All models feature an 8-conductor telephone style receptacle on the front panel for use with an optional remote control module (Tripp Lite
model APSRM4, sold separately). The remote module allows the Inverter/Charger to be mounted in a compartment or cabinet out of sight, while
operated conveniently from a remote location. See instructions packed with the remote control module.

"Reset"

"Equalize"

B1

B2

B3

B4

OFF 

(LESSER

LOAD 

ON)

MAX 

(GREATER 

LOAD

ON)

B4

B3

200608120 93-260

8

 230V APS OM.qxd  10/16/2006  10:46 AM  Page 6

Содержание APSINT Series

Страница 1: ...ection Automatic Overload Protection Ideal Output for All Loads including computers Frequency Controlled Output Fast Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recha...

Страница 2: ...r will cause it to short circuit and could cause personal injury due to electric shock Never immerse the unit and avoid any area where standing water might accumulate Mounting should be in the driest...

Страница 3: ...tility or generator supplied AC power when used with a user supplied cable with country specific plug Hardwire AC Input Output Terminal Strip not on corded models securely connects the Inverter Charge...

Страница 4: ...CHARGE ONLY this light will FLASH to alert you that the unit s inverter is OFF and will NOT supply AC power in the absence of a utility generator source or in over under voltage situations INV Invert...

Страница 5: ...tage Point and or decreasing the Low AC Voltage Point you will reduce the number of times your unit switches to battery due to voltage swings Group B DIP Switches Select Load Sharing OPTIONAL Your Inv...

Страница 6: ...ly from full output at 33 of the Inverter Charger s load rating to about 33 of full output at full load Least Limiting B1 Up B2 Down Charger limiting begins at when the Inverter Charger s load reaches...

Страница 7: ...ur batteries with utility or genera tor supplied AC power Compensate for inefficiency by multiplying this number by 1 2 This will give you a rough estimate of how many amp hours of battery power from...

Страница 8: ...over the fasteners to engage the mounting feet molded on the front of the Inverter Charger cabinet Install and tighten two user supplied 6 mm fasteners into the mounting feet molded on the rear of th...

Страница 9: ...iring Though your Inverter Charger is a high efficiency con verter of electricity its rated output capacity is limited by the length and gauge of the cabling run ning from the battery to the unit Use...

Страница 10: ...e over the hardwire terminal box Remove the knockout covers closest to the desired electrical source and to your equipment Attach 1 28 cm diameter conduits user supplied to the knockouts and thread wi...

Страница 11: ...e fuse Battery cabling is loose Check and tighten or replace cabling Unit has shut down due to battery overcharge preventing Disconnect any auxiliary chargers Reset by moving Operating Mode battery da...

Страница 12: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...

Отзывы: