5A

Configuration

Select Battery Type—All Models
(REQUIRED)

CAUTION:

The Battery Type DIP Switch setting must

match the type of batteries you connect, or your batteries
may be degraded or damaged over an extended period of
time. See “Battery Selection,” for more information.

Battery Type

Switch Position

Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down (factory setting)

Set Configuration DIP Switches

Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger
operation depending on your application. 

A1

A2

A3

A4

INPUT C/B 10A

OUTPUT C/B 12A

B4

B3

B2

B1

A4

A3

A2

A1

Group B Dip Switches

Group A Dip Switches

Group A DIP Switches

Select Low AC Input Voltage Point for Switching to
Battery—All Models* (OPTIONAL)

Voltage

Switch Position

201V

#A4 Up & #A3 Up

182V

#A4 Up & #A3 Down

163V

#A4 Down & #A3 Up

144V

#A4 Down & #A3 Down 
(factory setting)

* Most of your connected appliances and equipment will perform adequately when your Inverter/Charger’s High AC Input Voltage Point is left in the factory setting and its Low AC Voltage Input
Point is set to 182V. However, if the unit frequently switches to battery power due to momentary high/low line voltage swings that would have little effect on equipment operation, you may wish to
adjust these settings. By increasing the High AC Voltage Point and/or decreasing the Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.

Group B DIP Switches

Select Load Sharing—OPTIONAL

Your Inverter/Charger features a high-output battery charger that can draw a significant amount of AC power from your utility source or
generator when charging at its maximum rate. If your unit is supplying its full AC power rating to its connected heavy electrical loads at the
same time as this high charging occurs, the AC input circuit breaker could trip, resulting in the complete shut off of pass-through utility power.

To reduce the chance of tripping this breaker, Inverter/Chargers may be set to automatically limit the charger output. This keeps the sum of
the unit’s AC load and charge power within the circuit breaker rating. This charger-limiting function has four settings, allowing you to
reduce the charger’s draw lower and lower, as needed, if the AC input circuit breaker keeps tripping under the normal AC loads of devices
you have connected downline from the unit. The figures on the next page show how to set your DIP Switches to determine how heavy the
connected load can be on your Inverter/Charger before charger-limiting begins.

A1

A2

A3

A4

B2

B1

Select High AC Input Voltage Point 
for Switching to Battery—APSINT2424,
APSINT3636 only* (OPTIONAL)

Voltage

Switch Position

278V

Up

259V

Down (factory setting) 

.

Charger Inhibit—APSX750, APSX1250, 
APSINT2012 only (OPTIONAL)

Charger

Switch Position

Inhibit

Up

Enable

Down (factory setting) 

A2

200608120 93-260

8

 230V APS OM.qxd  10/16/2006  10:46 AM  Page 5

Содержание APSINT Series

Страница 1: ...ection Automatic Overload Protection Ideal Output for All Loads including computers Frequency Controlled Output Fast Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recha...

Страница 2: ...r will cause it to short circuit and could cause personal injury due to electric shock Never immerse the unit and avoid any area where standing water might accumulate Mounting should be in the driest...

Страница 3: ...tility or generator supplied AC power when used with a user supplied cable with country specific plug Hardwire AC Input Output Terminal Strip not on corded models securely connects the Inverter Charge...

Страница 4: ...CHARGE ONLY this light will FLASH to alert you that the unit s inverter is OFF and will NOT supply AC power in the absence of a utility generator source or in over under voltage situations INV Invert...

Страница 5: ...tage Point and or decreasing the Low AC Voltage Point you will reduce the number of times your unit switches to battery due to voltage swings Group B DIP Switches Select Load Sharing OPTIONAL Your Inv...

Страница 6: ...ly from full output at 33 of the Inverter Charger s load rating to about 33 of full output at full load Least Limiting B1 Up B2 Down Charger limiting begins at when the Inverter Charger s load reaches...

Страница 7: ...ur batteries with utility or genera tor supplied AC power Compensate for inefficiency by multiplying this number by 1 2 This will give you a rough estimate of how many amp hours of battery power from...

Страница 8: ...over the fasteners to engage the mounting feet molded on the front of the Inverter Charger cabinet Install and tighten two user supplied 6 mm fasteners into the mounting feet molded on the rear of th...

Страница 9: ...iring Though your Inverter Charger is a high efficiency con verter of electricity its rated output capacity is limited by the length and gauge of the cabling run ning from the battery to the unit Use...

Страница 10: ...e over the hardwire terminal box Remove the knockout covers closest to the desired electrical source and to your equipment Attach 1 28 cm diameter conduits user supplied to the knockouts and thread wi...

Страница 11: ...e fuse Battery cabling is loose Check and tighten or replace cabling Unit has shut down due to battery overcharge preventing Disconnect any auxiliary chargers Reset by moving Operating Mode battery da...

Страница 12: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com...

Отзывы: