background image

 

[

9

]

 

 

 5 – Maintenance 

 

 

The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries, which are maintenance-free relative to the 
electrolyte. You cannot add water to these batteries or sample the electrolyte specific gravity. It is necessary, however, to periodically 
check the charging voltage, temperature and connections of the individual battery units. 

 

 5-1 Maintenance Schedule 

 

Quarterly Check 

 

1.

 

Measure individual battery unit temperature. (Measure with a digital thermometer by placing the surface thermocouple on the 
flat surface of the negative terminal—not the “L” connection surface. An infrared temperature monitor can also be used. 
Temperatures below 77° F reduce battery performance and temperatures above 77° F reduce battery lifespan. Battery lifespan 
is reduced by 50% for each 15° above 77° F. For example, battery lifespan will be reduced by half at 92° F.) 

2.

 

Measure individual battery unit float charging voltages. (Measure voltage with a digital voltmeter. Measured voltage should 
be between 13.2 VDC and 14.2 VDC. Battery units outside this range should be replaced.) 

3.

 

Measure total battery cabinet float charging voltage. 

 

Semiannual Check 

 

1.

 

Repeat quarterly check. 

2.

 

(Optional) Measure impedance or conductance of individual battery units. 

3.

 

(Optional) Perform a high-rate, 100 A, 10 second performance capacity test of individual battery units. (The performance 
capacity test is identical to the acceptance test in 

Section 4-4

, and the same procedure should be followed.) 

 

Annual Check 

 

1.

 

Repeat semiannual check. 

2.

 

Use insulated tools to tighten all connections to the recommended torque. (See 

Section 7-2

 for recommended torque values.) 

3.

 

(Optional) Measure inter-battery connection resistance. 

 

 5-2 Fuse Replacement 

 

Warning: Fuses should be replaced by qualified service personnel only. Blown fuses must be replaced with the same number 
and type of fuses. 

 

1.

 

The battery cabinet may contain a UL-listed, branch-rated fuse in the positive output (upper front of cabinet). 

2.

 

Before attempting to replace the fuse, open the disconnect between the battery cabinet and the load/charger. 

3.

 

Remove the front panel from the battery cabinet. Before attempting to replace the fuse, confirm that the battery is not shorted 
to the cabinet. Use a digital voltmeter to measure the voltage between the cabinet and both sides of the fuse holder. This 
voltage should measure 0 (zero) VDC. If the measured voltage is not zero, determine the cause and correct before 
proceeding. 

4.

 

Wearing rubber gloves and using insulated tools, remove any cables and/or terminal plates from the output side of the fuse 
holder. Using the appropriate hex socket, remove the fuse from the holder. 

5.

 

The replacement fuse must have the same voltage and current rating as the fuse being replaced (check the label on the fuse 
being replaced). 

6.

 

For nominal battery cabinet voltages less than or equal to 384 VDC, use fuses rated at 500 VDC. For nominal battery cabinet 
voltages greater than 384 VDC, use fuses rated at 700 VDC. 

7.

 

Install the replacement fuse and reconnect the output cables and/or terminal plates to the output side of the fuse holder. 

8.

 

Reinstall the battery cabinet front panel and close the disconnect between the battery cabinet and the load/charger. 

Содержание 3-Phase Battery Cabinet Extended-Run

Страница 1: ...Check 4 Operation and Charging 4 1 Determine Charging Voltages 4 2 Initial Charge 4 3 Operational Check 4 4 Acceptance Test Optional 5 Maintenance 5 1 Maintenance Schedule 5 2 Fuse Replacement 6 Diag...

Страница 2: ...ropriate ventilation and convection cooling of the individual batteries is provided via inch spacing between batteries Front and rear vents allow the free flow of warmer air out of the battery cabinet...

Страница 3: ...e support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recom...

Страница 4: ...h any object Do not lay tools or metal parts on top of batteries Replace batteries with equivalent batteries same number and type available from Tripp Lite The batteries are recyclable Refer to local...

Страница 5: ...Fully extend forks under load Spread forks to maximum possible width under load Lift cabinet from bottom only Wear safety shoes Confirm that load limits for freight elevators handling equipment and f...

Страница 6: ...the output load connection points Measure voltage with a digital voltmeter 2 The measured voltage should approximately match the voltage listed on the battery cabinet nameplate The battery cabinet out...

Страница 7: ...4 The top and sides of the battery cabinet include knockouts for load connection cable entry Punch out the appropriate knockout and connect the conduit or cable bushing 5 The output terminal blocks f...

Страница 8: ...attery terminals 2 Measure and record the system float current using a clamp on ammeter 3 Measure and record the float voltage of individual battery units 4 Measure and record the temperature of sever...

Страница 9: ...annual check 2 Use insulated tools to tighten all connections to the recommended torque See Section 7 2 for recommended torque values 3 Optional Measure inter battery connection resistance 5 2 Fuse Re...

Страница 10: ...s are in inches Conduit Knockouts Conduit Knockouts Breaker Mounting Plate 79 4 5 4 38 15 75 6 4 5 2 25 22 8 25 24 75 16 16 16 4 11 75 5 5 40 25 30 25 6 6 34 5 17 25 Side View Side View Front View Sid...

Страница 11: ...e All dimensions are inches 58 Front of Cabinet Front of Cabinet Breaker Mounting Plate Conduit Knockouts Conduit Knockouts 15 75 2 25 Side View Side View Side View Side View Bottom View Top View Fron...

Страница 12: ...0 VDC Breaker is UL listed and rated for 150 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary dependin...

Страница 13: ...250 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary depending on cabinet and battery type Shelf 1 Bo...

Страница 14: ...suitable for 120 VAC input Temperature compensation with remote battery temperature sensor Auxiliary output circuit for Charger OK indicator 6 25 MAX 0 5 12 5 13 5 Terminal Block Detail Input Voltage...

Страница 15: ...cm 2284 lb 1038 kg 271 lb ft 2 1322 kg m 2 BP348V78 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 200 7 cm 2545 lb 1157 kg 301 lb ft 2 1474 kg m 2 BP348V103 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 20...

Страница 16: ...rs should contact Tripp Lite support at intlservice tripplite com THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRA...

Отзывы: