background image

 

[

8

]

 

 

 4 – Operation and Charging 

 

 

 4-1 Determine Charging Voltages 

 

To determine the appropriate equalization (freshening) charge voltage and float charge voltage, multiply the number of batteries 
connected in series in the battery cabinet by the recommended charging voltage per unit. 

 

For example: 

 

A +/- 240 VDC cabinet containing 40 each of the UPS12-400MR batteries in series would use the following charging voltages: 

 

Freshening/Equalization Charge Voltage = 20 x 14.4 VDC/unit average= +/- 288 VDC 
Float Charge Voltage = 20 x (13.5 to 13.8 VDC/unit average) = +/- 270 to 276 VDC 

 

Note: Some battery cabinets may contain more than one series string connected in parallel within the cabinet. The calculation for 
properly charging the battery cabinet should follow the procedure above, considering the number of batteries in a single series string. 

 

 4-2 Initial Charge 

 

After the correct charging voltages have been calculated, follow these steps: 

 

1.

 

Adjust the charger/rectifier equalization and float voltage outputs to the appropriate level. 

2.

 

Place the charger/rectifier in equalization mode, 

3.

 

Close the disconnect switch/circuit breaker connection from the charger/rectifier to the battery cabinet(s) and start a 24-hour 
freshening charge at the equalization charge. 

4.

 

After a few minutes on charge, monitor the voltage across several of the individual batteries to assure they are charging at the 
proper value. 

5.

 

Following completion of the freshening charge, place the charger/rectifier in float charge mode. 

6.

 

After the battery cabinet has been on float for 1 to 24 hours, complete the operational check (

Section 4-3

). 

 

 4-3 Operational Check 

 

1.

 

Measure and record the total system float voltage. Measure at the battery terminals. 

2.

 

Measure and record the system float current using a clamp-on ammeter. 

3.

 

Measure and record the float voltage of individual battery units. 

4.

 

Measure and record the temperature of several of the batteries. (Measure battery temperature with a digital thermometer by 
placing the surface thermocouple on the flat surface of the negative terminal—not the “L” connection surface. An infrared 
temperature monitor can also be used.) 

5.

 

Optional: Perform impedance and conductance tests on individual battery units. These tests require special equipment, but the 
data can be useful in trending the system over time or identifying suspect units during later periodic checks. It may be 
necessary to disconnect the battery system from the charger/load during these checks. 

6.

 

If the acceptance test is being performed, proceed to 

Section 4-4

. If the acceptance test is not being performed, reinstall the 

cabinet’s access panels. The battery cabinet is now in operation. 

 

 4-4 Acceptance Test (Optional) 

 

1.

 

Remove the battery cabinet’s access panels to access internal components. Use a digital voltmeter when voltage 
measurements are required. 

2.

 

Determine the discharge rate (e.g. 15 seconds, 5 minutes, 15 minutes) at which the battery is to be tested. 

3.

 

Select a battery from the center of the battery cabinet and measure the temperature at the flat surface of the negative terminal. 
If the temperature is below 74° F or above 80° F, the test load should be temperature compensated accordingly. 

4.

 

Review the final check data and assure that all unit float voltages are acceptable. 

5.

 

During the acceptance discharge test, monitor the cabinet system output voltage at the cabinet, the output current and 
discharge time as a back-up to monitoring at the critical load. 

6.

 

Run the test in accordance with the IEEE standard. 

7.

 

Reinstall the cabinet’s access panels. The battery cabinet is now in operation. 

 

Содержание 3-Phase Battery Cabinet Extended-Run

Страница 1: ...Check 4 Operation and Charging 4 1 Determine Charging Voltages 4 2 Initial Charge 4 3 Operational Check 4 4 Acceptance Test Optional 5 Maintenance 5 1 Maintenance Schedule 5 2 Fuse Replacement 6 Diag...

Страница 2: ...ropriate ventilation and convection cooling of the individual batteries is provided via inch spacing between batteries Front and rear vents allow the free flow of warmer air out of the battery cabinet...

Страница 3: ...e support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recom...

Страница 4: ...h any object Do not lay tools or metal parts on top of batteries Replace batteries with equivalent batteries same number and type available from Tripp Lite The batteries are recyclable Refer to local...

Страница 5: ...Fully extend forks under load Spread forks to maximum possible width under load Lift cabinet from bottom only Wear safety shoes Confirm that load limits for freight elevators handling equipment and f...

Страница 6: ...the output load connection points Measure voltage with a digital voltmeter 2 The measured voltage should approximately match the voltage listed on the battery cabinet nameplate The battery cabinet out...

Страница 7: ...4 The top and sides of the battery cabinet include knockouts for load connection cable entry Punch out the appropriate knockout and connect the conduit or cable bushing 5 The output terminal blocks f...

Страница 8: ...attery terminals 2 Measure and record the system float current using a clamp on ammeter 3 Measure and record the float voltage of individual battery units 4 Measure and record the temperature of sever...

Страница 9: ...annual check 2 Use insulated tools to tighten all connections to the recommended torque See Section 7 2 for recommended torque values 3 Optional Measure inter battery connection resistance 5 2 Fuse Re...

Страница 10: ...s are in inches Conduit Knockouts Conduit Knockouts Breaker Mounting Plate 79 4 5 4 38 15 75 6 4 5 2 25 22 8 25 24 75 16 16 16 4 11 75 5 5 40 25 30 25 6 6 34 5 17 25 Side View Side View Front View Sid...

Страница 11: ...e All dimensions are inches 58 Front of Cabinet Front of Cabinet Breaker Mounting Plate Conduit Knockouts Conduit Knockouts 15 75 2 25 Side View Side View Side View Side View Bottom View Top View Fron...

Страница 12: ...0 VDC Breaker is UL listed and rated for 150 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary dependin...

Страница 13: ...250 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary depending on cabinet and battery type Shelf 1 Bo...

Страница 14: ...suitable for 120 VAC input Temperature compensation with remote battery temperature sensor Auxiliary output circuit for Charger OK indicator 6 25 MAX 0 5 12 5 13 5 Terminal Block Detail Input Voltage...

Страница 15: ...cm 2284 lb 1038 kg 271 lb ft 2 1322 kg m 2 BP348V78 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 200 7 cm 2545 lb 1157 kg 301 lb ft 2 1474 kg m 2 BP348V103 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 20...

Страница 16: ...rs should contact Tripp Lite support at intlservice tripplite com THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRA...

Отзывы: