background image

 

[

11

]

 

 

 6 – Diagrams

 (continued)

 

 

 

 6-2 Battery Cabinet Diagram (3 Shelves) 

 

 

Note

: All dimensions are inches. 

 

 
 

 

58 

Front of Cabinet 

Front of Cabinet 

Breaker 

Mounting 

Plate 

Conduit 

Knockouts 

Conduit 

Knockouts 

15.75 

2.25 

Side View 

Side View 

Side View 

Side View 

Bottom View 

Top View 

Front View 

3.25 

4.5 

4.5 

30 

32 

29 

14.5 

10.25 

24 

14 

16 

16 11 

8.25 

Содержание 3-Phase Battery Cabinet Extended-Run

Страница 1: ...Check 4 Operation and Charging 4 1 Determine Charging Voltages 4 2 Initial Charge 4 3 Operational Check 4 4 Acceptance Test Optional 5 Maintenance 5 1 Maintenance Schedule 5 2 Fuse Replacement 6 Diag...

Страница 2: ...ropriate ventilation and convection cooling of the individual batteries is provided via inch spacing between batteries Front and rear vents allow the free flow of warmer air out of the battery cabinet...

Страница 3: ...e support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recom...

Страница 4: ...h any object Do not lay tools or metal parts on top of batteries Replace batteries with equivalent batteries same number and type available from Tripp Lite The batteries are recyclable Refer to local...

Страница 5: ...Fully extend forks under load Spread forks to maximum possible width under load Lift cabinet from bottom only Wear safety shoes Confirm that load limits for freight elevators handling equipment and f...

Страница 6: ...the output load connection points Measure voltage with a digital voltmeter 2 The measured voltage should approximately match the voltage listed on the battery cabinet nameplate The battery cabinet out...

Страница 7: ...4 The top and sides of the battery cabinet include knockouts for load connection cable entry Punch out the appropriate knockout and connect the conduit or cable bushing 5 The output terminal blocks f...

Страница 8: ...attery terminals 2 Measure and record the system float current using a clamp on ammeter 3 Measure and record the float voltage of individual battery units 4 Measure and record the temperature of sever...

Страница 9: ...annual check 2 Use insulated tools to tighten all connections to the recommended torque See Section 7 2 for recommended torque values 3 Optional Measure inter battery connection resistance 5 2 Fuse Re...

Страница 10: ...s are in inches Conduit Knockouts Conduit Knockouts Breaker Mounting Plate 79 4 5 4 38 15 75 6 4 5 2 25 22 8 25 24 75 16 16 16 4 11 75 5 5 40 25 30 25 6 6 34 5 17 25 Side View Side View Front View Sid...

Страница 11: ...e All dimensions are inches 58 Front of Cabinet Front of Cabinet Breaker Mounting Plate Conduit Knockouts Conduit Knockouts 15 75 2 25 Side View Side View Side View Side View Bottom View Top View Fron...

Страница 12: ...0 VDC Breaker is UL listed and rated for 150 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary dependin...

Страница 13: ...250 A 600 VDC 25 KAIC Cabinets with breakers are shipped with the breaker in the off open position Battery arrangements shown are typical but may vary depending on cabinet and battery type Shelf 1 Bo...

Страница 14: ...suitable for 120 VAC input Temperature compensation with remote battery temperature sensor Auxiliary output circuit for Charger OK indicator 6 25 MAX 0 5 12 5 13 5 Terminal Block Detail Input Voltage...

Страница 15: ...cm 2284 lb 1038 kg 271 lb ft 2 1322 kg m 2 BP348V78 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 200 7 cm 2545 lb 1157 kg 301 lb ft 2 1474 kg m 2 BP348V103 4 40 25 x 30 25 x 79 inches 102 2 x 76 8 x 20...

Страница 16: ...rs should contact Tripp Lite support at intlservice tripplite com THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRA...