background image

Comfort

BREEZE 

TM

 Model CB707

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

11

www.trioniaq.com

6.3 Troubleshooting Chart

Problem/Symtom

Probable Cause

Corrective Action

Power is applied and the LED does not 

illuminate.

No issue.

The LED does not illuminate unless the 

H1 & H2 terminals are closed on the 

circuit board or the humidistat contacts 

are closed.

Humidistat contacts are closed but the 

unit will not produce mist

No water pressure or water supply valve 

is closed.

Ensure that the supply water is on.

Solenoid Valve is not operating

Ensure that there is power supplied to 

the valve.  Check control board output.

Motor is not operating

Ensure that there is power supplied to 

the motor.  Check control board output.

Circuit Board has failed/fuse is blown

Replace circuit board.

Duct Static pressure is too high

Ensure unit is connected to the return 

duct and not the supply duct.  Relocate if 

necessary.

Impeller pump broken or missing

Ensure pump has not fallen out of the 

impeller tube.

Motor will not operate/turn

Motor internal thermal protective device 

is open.

Remove power and allow motor to cool.  

Restart unit and ensure proper operation.  

If motor will not turn, replace motor.

Motor has failed

Replace motor.

Impeller is stuck

Remove obstruction or replace motor as 

necessary.

LED is glowing solid RED

Service Timer has expired

Follow the Cleaning instructions and 

reset the service interval.  See page 8.

Unit will not operate and LED is blinking 

rapidly. (1/4 second interval)

Damaged or stuck float switch

Clean float switch and ensure proper 

operation.  Replace switch is necessary.

Restricted input water flow; clogged 

solenoid valve

Inspect orifice located in solenoid valve 

discharge tube.

Leaking reservoir

Inspect the unit for cracks in the reser

-

voir.  Replace reservoir if necessary.

Control Board has failed.

Replace control board.

Unit will not operate & LED is blinking 

slowly (1 second interval)

Damaged or stuck float switch

Clean float switch and ensure proper 

operation.  Replace switch is necessary.

Clogged pump or damaged pump/imprel

-

ler

Ensure pump has not fallen out of the 

impeller tube.

Bad control board

Replace control board.

Solenoid Valve stuck open

Replace solenoid valve.

Содержание ComfortBREEZE CB707

Страница 1: ...T r i o n w w w t r i o n i a q c o m ComfortBREEZE TM CB707 Centrifugal Atomizing Humidifier READ AND SAVE THESE INSTRUCTIONS...

Страница 2: ...4 3 3 What s in the Box 4 3 4 Hardware Details 4 4 Installation 5 4 1 Clearances 5 4 2 Selecting a location 5 4 2 1 Wall Mounting 5 4 2 2 Duct Mounting 6 4 2 3 Ceiling Mouning 6 4 2 4 Shelf Mounting...

Страница 3: ...is limited to replacement of defective parts or components and does not include the pay ment of the cost of labor charges to remove or replace such defec tive components or parts 7 Trion will not be r...

Страница 4: ...f the air If applicable set the humidistat in the recommended range of 30 40 relative humidity for automatic humidity control during the heating season A lower setting may be necessary to pre vent con...

Страница 5: ...ic dispersion it may be hung from a ceiling mounting hardware not included for this type of installation or it may be simply mounted to a shelf An indicating LED is located on the oposite side of the...

Страница 6: ...ounting holes as shown on the template for mounting the bracket to the duct 5 Cut out the discharge hole while taking care not to injure yourself Once the hole is cut out ensure that the edges will no...

Страница 7: ...ge the water into a bucket or pan This will allow the water to flush any debris that may have accumulated in the line during the in stallation process Once this is complete close the saddle valve 3 At...

Страница 8: ...up for continu ous operation by installing a jumper between the H terminals on the control board you must remove the jumper wire placed between terminals H1 H2 on the control board 5 3 End of Season...

Страница 9: ...at care is taken not to damage bend or break the atomizing posts 7 Remove the cover from the electrical box and unwire the line cord and humidistat wires from the terminals It is not necessary to remo...

Страница 10: ...logged solenoid valve or flow restrictor c Leaking reservoir d Bad control board 2 Red LED blinking repeatedly 1 second On 1 second OFF Unit will not function B Float switch not closing in 30 minutes...

Страница 11: ...ler tube Motor will not operate turn Motor internal thermal protective device is open Remove power and allow motor to cool Restart unit and ensure proper operation If motor will not turn replace motor...

Страница 12: ...1 19 G 109 G 109 SOLENOID VALVE ASSEMBLY 1 20 165001 001 PUSH TO LOCK MALE ELBOW 1 4 X 1 8 NPT 1 21 265305 001 FILL FITTING 1 8 NPT 2 22 166129 001 SCREW 8 X 3 8 PH PH THRD CUT SST 7 23 265378 220 SC...

Страница 13: ...SHOWN 2 54 266793 001 FEMALE THREADED STANDOFF 1 55 266455 001 CONTROL BOARD BRACKET RH 1 56 266455 002 CONTROL BOARD BRACKET LH 2 57 266792 001 LOCKNUT PG9 1 58 266826 001 INLET RING 1 59 265442 001...

Страница 14: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 14 www trioniaq com See Note 2 on page 13...

Страница 15: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 15 www trioniaq com...

Страница 16: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 16 www trioniaq com...

Страница 17: ...ComfortBREEZE TM Model CB707 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 17 www trioniaq com...

Страница 18: ...Form No 265631 001 rev 01 15 2013 Trion 2013 All Rights Reserved Trion 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com...

Отзывы: