extremely dry nature, it can be blown off the cells 
with a pressure hose or by gently tapping the end 
plate of the cell. 

 
4. Remove the mechanical pre-filter. Remove 

collected dust or lint by vacuuming or brushing. 
Wash with warm, soapy water. 

 
5.  Rinse all components thoroughly in warm, clear 

water and allow to drip dry completely. 

 
6. Replace pre-filters and ionizer/collector cells. 

ENSURE the airflow arrows point in the direction of 
airflow (towards the blower). 

 
7.  Close the access door; reconnect power to the unit. 
 
8.  Turn control switch to “ON”. If arcing occurs or the 

indicating light flickers, the components may still be 
damp. Turn the unit OFF and allow the cells to dry 
completely. 

 

Inspections

 
The motors and blowers on Trion T1300 and T2600 air 
cleaners have sealed ball bearings and never need 
lubricating. 
 
Belt tension should be checked periodically. When a 
moderate force is applied to the belt midway between 
the pulleys, the belt should deflect approximately ½ “ 
(13 mm). 
 

CAUTION 

Having too much tension on the belts will shorten 
the belt life and place undue stress on the motor 
and blower bearings. 

 

V. REPLACEMENT PARTS ORDERING 
INFORMATION 

 

The following pages contain exploded views and Bills of 
Material for the Trion T Series Air Cleaners. Use these 
pages to determine the part numbers of the items 
needed. To order parts contact your local Trion 
representative and provide the following information: 
 
a.  Unit Model number – located on the data label near 

the junction box. 

b.  Part Number and description – from exploded 

views.  

 
 

VI. WARRANTY 

All Trion Electronic Air Cleaners are warranted for 3 
Year Limited Warranty on units and 1 Year Limited 

Warranty on replacement parts. Labor is NOT included. 
Do not return defective parts without permission from 
the factory and receiving a material return acceptance 
number. 
 
 

VII. TROUBLESHOOTING GUIDE 

 

T1001 / T2002 
Problems and Possible Causes:

 

 
1.  Indicating Light Out 

a.  Unit not plugged in 
b.  Control switch “Off” 
c.  Cell access panel not fully closed 
d.  Broken cell insulator 
e.  Extremely dirty cells 
f. 

Service panel not secured in place 

 
2.  Excessive arcing noise after washing 

a.  Collector elements still wet – Allow more drying 

time 

b.  See “Continuous arcing noise” below 

 
3.  Continuous arcing noise and flickering indicating 

light 
a.  Extremely dirty collector plates 
b.  Bent collector plates 
c.  Large piece of material lodged between cell 

plates 

 
4. Contaminant 

Bypass 

a.  Velocity of airflow is too high through unit 
b.  Collector plates not grounded 
c.  Collector cell not making solid connection to 

access door and high voltage contact. 

 

IF PROBLEM CANNOT BE DETERMINED OR 
CORRECTED  - CONTACT YOUR LOCAL TRION 
REPRESENTATIVE OR CALL TRION CUSTOMER 
SERVICE AT 1-800-884-0002 FOR ASSISTANCE. 
 

 

T1300 / T2600 Troubleshooting Guide 

The troubleshooting chart, shown on the next page, will 
enable the user to pinpoint the cause of most problems. 
Refer to the Ordering Information for replacement parts. 
Before performing any troubleshooting, ensure the 
correct input line voltage is present. 
 

WARNING 

Factory designed access to all electrically charged 
high voltage components contain electrical 
interlocks for the safety of operating personnel.  
Always unplug the unit while performing service 
within the cabinet. 

 

 

7

Содержание Air Boss T1001 Module

Страница 1: ... Module T2002 Module T1300 T2600 INSTALLATION OPERATION SERVICE Electrostatic Precipitators for Commercial Industrial Applications 101 McNeill Road Sanford NC 27330 919 775 2201 Fax 919 777 6399 800 884 0002 www trioninc com T NO 149869 001 MANUAL PAR June 2004 4 ...

Страница 2: ...s 4 Unit Operation 4 Ducting Application 5 Liquid Aerosol Installation 5 Electrical Installation 6 Cleaning 6 Inspections 7 VI W T1001 T2002 7 T1300 T2600 7 Troubleshooting Diagram 8 Figure 1 T1300 Unit 9 Figure 2 T2600 Unit 10 Figure 3 T1001 Unit 11 Figure 4 T2002 Unit 12 Figure 5 Enclosure Assembly 13 Figure 6 Blower Assembly 14 Figure 7 Blower Assembly Bill of Material 15 Figure 8 Ionizer Colle...

Страница 3: ...1300A 230V 60 HZ 1 PH 3 4 5 6 T1300B 230V 60 HZ 3 PH 1 3 6 T1300C 460V 60 HZ 3 PH 1 1 8 T1300D 575V 60 HZ 3 PH 1 1 6 T1300E 230V 50 HZ 1 PH 3 4 5 9 T1300N 208V 60 HZ 3 PH 1 3 6 T2600 120V 60 HZ 1 PH 3 4 11 3 T2600A 230V 60 HZ 1 PH 3 4 5 7 T2600B 230V 60 HZ 3 PH 1 3 7 T2600B 230V 60 HZ 3 PH 2 6 5 T2600C 460V 60 HZ 3 PH 1 1 9 T2600C 460V 60 HZ 3 PH 2 3 3 T2600D 575V 60 HZ 3 PH 1 1 7 T2600E 230V 50 H...

Страница 4: ...ollector designed to remove up to 95 of the dust smoke liquid aerosol and other pollutants from the air passing through it HOW IT OPERATES Polluted air is drawn into the unit by the belt driven blower on a T1300 or T2600 unit The T1001 and T2002 units require an external air handler to move the air After passing through a pre filter the particles in the air are given an electrical charge supplied ...

Страница 5: ...READ THOROUGHLY 1 Carefully unpack unit from shipping crate or carton and examine for damage in shipment 2 Remove ionizer collector cell s pre filters and after filters 3 Attach 500 pound 227 kg test chain to the ceiling joist using a Wood joist 3 8 m10 eye bolts b Metal joist wrap chain around joist at least twice and secure with 500 pound 227 kg test connecting link 4 Chain should be cut to allo...

Страница 6: ...personnel WARNING RISK OF ELECTRIC SHOCK These serving instructions are for use by qualified personnel only To reduce the risk of electric shock do not perform any servicing other than that contained in the operating instructions unless you are qualified to do so SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of ...

Страница 7: ...xploded views VI WARRANTY All Trion Electronic Air Cleaners are warranted for 3 Year Limited Warranty on units and 1 Year Limited Warranty on replacement parts Labor is NOT included Do not return defective parts without permission from the factory and receiving a material return acceptance number VII TROUBLESHOOTING GUIDE T1001 T2002 Problems and Possible Causes 1 Indicating Light Out a Unit not p...

Страница 8: ...9 ...

Страница 9: ...10 ...

Страница 10: ...11 ...

Страница 11: ...12 ...

Страница 12: ...13 ...

Страница 13: ...14 ...

Страница 14: ...Blower Motor Assembly FIG 6 15 ...

Страница 15: ...16 ...

Страница 16: ...17 ...

Страница 17: ...18 ...

Страница 18: ...19 ...

Страница 19: ...20 ...

Страница 20: ...21 ...

Страница 21: ...22 ...

Страница 22: ... Boscstr 60 No 728 Fuzhou Road D 50171 Kerpen Rm 3002 3005 Germany Raffles City Office Tower Tel 49 0 2237 922 103 Shanghai P R China 200001 Fax 49 0 2237 922 104 Tel 86 21 63403232 Email info trion deutschland de Fax 86 21 63403867 Fedders International Fedders International Inc Air Conditioning 128 Joo Seng Road A 30 Chintels House 05 01 Kalish Colony DP Computers Building New Delhi Singapore 36...

Отзывы: