Contaminants to be collected – such as oils in vaporous
state – must be condensed into particulate form prior to
entering the ionizing-collecting cells in order to maintain
the anticipated efficiency. Gases, vapors or any non-
particulate cannot be precipitated and will therefore
pass through the air cleaner. Any condensing that takes
place downstream from the air cleaner defeats the
purpose. Similarly, heavy concentrations of water vapor,
or other matter that becomes highly conductive when
condensed, must be prevented from entering and/or
condensing in the collecting elements to prevent
electrical arc over and shorting.
ELECTRICAL INSTALLATION
All units must be wired directly in the junction box on the
access door side of the unit. Use NEC Class I wiring
methods. Size branch circuit protection in accordance
with the NEC. Refer to the appropriate enclosed wiring
diagram in the attached figures.
WARNING:
EXERCISE ALL THE NORMAL PRECAUTIONS
WHEN WORKING WITH HIGH VOLTAGE AND
COMPLY WITH NEC AND ALL APPROPRIATE
LOCAL CODES.
Check Out for System Start-up
When the installation has been completed, assure that
the equipment is ready for start-up by checking the
following:
A. All construction debris is removed from the ionizing-
collecting cells, drain connections and ductwork.
B. The drain line from the Trion drain basin is clear and
completely connected to its point of termination.
C. Supply line power is available and electrical wiring
is completed to the junction box.
IV. MAINTENANCE
The following instructions are for use by qualified
personnel.
WARNING
RISK OF ELECTRIC SHOCK
These serving instructions are for use by qualified
personnel only. To reduce the risk of electric shock,
do not perform any servicing other than that
contained in the operating instructions unless you
are qualified to do so.
SAFETY NOTE:
Factory designed access to all electrically charged
high voltage components contain electrical
interlocks for the safety of operating personnel. Any
additional access that may be provided in the
system, where there is access to high voltage, must
be equipped with such interlocks. Interlocks are
readily available from the factory.
Cleaning
To maintain optimum collection efficiency, the pre-filters
and ionizer/collector cells should be removed
periodically and soaked in a solution of hot water and
Trion Tridex detergent for 2 to 4 hours, rinsed
thoroughly and then air dried completely before
reinstalling in the unit.
The frequency of cleaning is dependent on the type of
contaminant being collected. Liquid aerosol requires
less cleaning while welding smoke may require more
frequent cleaning.
Note: Trion Tridex Detergent is specially formulated
for use with Trion electronic air cleaners. Use of
other cleaners and detergents, not specifically
approved by Trion, can cause possible failures in
the unit and will void any and all warranties on our
equipment.
Wash Ionizing/ Collecting Cells
WARNING:
DO NOT USE HIGH PRESSURE STEAM CLEANING
EQUIPMENT TO CLEAN CELLS. THE EXCESSIVE
HEAT AND PRESSURE WILL CAUSE THE PLATES
TO WARP AND IN TURN POSSIBLY CAUSE
EXCESSIVE ARCING.
1. Turn the control switch “OFF” and disconnect power
to the unit.
2. Open the cell access door.
3. Remove ionizer/collector cells and wash in HOT
detergent water. If the collected contaminant is of
6
Содержание Air Boss T1001 Module
Страница 8: ...9 ...
Страница 9: ...10 ...
Страница 10: ...11 ...
Страница 11: ...12 ...
Страница 12: ...13 ...
Страница 13: ...14 ...
Страница 14: ...Blower Motor Assembly FIG 6 15 ...
Страница 15: ...16 ...
Страница 16: ...17 ...
Страница 17: ...18 ...
Страница 18: ...19 ...
Страница 19: ...20 ...
Страница 20: ...21 ...
Страница 21: ...22 ...