background image

www.trioniaq.com

ATS Series

12

I n s t a l l a t i o n ,   O p e r a t i o n ,   a n d   S e r v i c e   M a n u a l

of elimination. A flickering light with an arcing noise is 

an indication of a high resistance short circuit. If the 

light is OFF it is an possible indication of a dead short 

or no 120vac power to the power supply. To isolate the 

short to any one of these three components, proceed 

as follows:

•  Disconnect both high voltage leads from their 

respective terminals on the power supply and 

support them away from any point of contact

•  Energize the power supply:

• 

If  the  light  still  flickers  or  does  not  glow;  the 

trouble is indicated to be in the power supply. 

First, replace the power supply in its entirety.

•  If the light glows steady with the leads 

disconnected, the power supply is indicated to 

be normal.

•  Next reconnect both high voltage leads to their 

respective terminals on the power supply and 

disconnect them at the ionizing-collecting cells. 

Support them away from any point of contact and 

energize the power supply.

•  If either high voltage lead is defective, the light 

will indicate the trouble. Each lead may then be 

checked separately by disconnecting them, one at 

a time, from their respective terminals at the power 

supply. When a lead is found to be defective, 

replace it in its entirety. Do not repair or splice.

•  If the light glows steady with the leads disconnected 

at the cells the trouble is then indicated to be in 

the ionizing-collecting cells. The trouble can then 

be isolated to a single cell or ionizing or collector 

section of a given cell as follows:

•  First determine if the short is in the ionizing 

section or the collecting section by connecting 

each high voltage lead to its respective section, 

one at a time, and energizing the power pack. 

(The  lead  not  connected  must  be  supported 

away from any point of contact.) The short 

symptoms will still exist for the section in which 

the short is located. If the trouble causing the 

short is bridging both sections, then the short 

Note: In order to complete the primary circuit to 

the power supply, it will be necessary to close 

both the access door electrical interlock switch.

will be indicated in both sections when they 

are individually connected.

•  When the short is isolated to a cell tier, remove 

all the cells within the tier and visually check 

the sections indicated to contain the short.

•  If the short is in the ionizer section look for 

a broken or defective insulator.

•  If the short is in the collector section look 

for a large piece of foreign material bridging 

the collector plates or a defective insulator.

•  If the short is indicated to be in both 

sections, it will probably be a foreign object 

bridging the air gap between the ionizer 

and the collector.

Primary Voltage (120V)

Although open circuits can occur in the secondary they 

usually take place in the primary. If the unit contains 

only one power supply and the indicating light does 

not glow the outage is probably one of the following:

•  Supply line power to the control disconnected.

•  Access door interlock in impinger or ionizer/

collector section of electronic air cleaner.

•  Faulty power supply. Look for charred or burned 

components or a loose wiring connection.

Содержание Air Boss ATS Series

Страница 1: ...T R I O N w w w t r i o n i a q c o m Air Boss ATS Series Electrostatic Precipitators Commercial Industrial Applications READ AND SAVE THESE INSTRUCTIONS ...

Страница 2: ...tion 2 Operation 5 Initial Startup 8 Routine Maintenance 10 Preventative Maintenance 10 Troubleshooting 11 Troubleshooting Chart 13 Spare Parts 14 SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of operating personnel Any additional access that may be provided in the system where there is access to high voltage mu...

Страница 3: ...ments Condensation freezing and elevated temperatures must be considered CAUTION In addition to the previous space requirements installation of the Model ATS in NFPA applications shall have a clearance of at least 18 inches to a combustible material 3 inches to limited combustible material and 0 inches to noncombustible material Any reduction in clearance or exceptions must be in compliance with N...

Страница 4: ...TE LOCAL CODES High Voltage Wiring The high voltage wiring requires connecting the power supplies to the ionizing collecting cells located in the electronic air cleaner section cabinet On multicell units the wiring between the cells within a tier is automatically made with intercell spring contacts Two high voltage wires must be connected to each tier of cells in the ATS one for the ionizers and o...

Страница 5: ...eriodicalmanualfillingofthedetergenttank and to gain access to the pump and motor assembly After positioning the unit must be secured in place The Detergent System should not be installed more than 30ft below the ATS System Local disconnect is recommended for detergent tank motor Note TRION Tridex Detergent is specially formulated for use with TRION electronic air cleaners Use of other cleaners an...

Страница 6: ...matter from the air The modular sections can be built in several widths and heights to accommodate different air flow requirements Refer to the System Outline drawing for information on the specific system design for this project The first section the prefilter is primarily designed for capturing relatively large liquid particulate The second section houses an electronic air cleaner technically kn...

Страница 7: ...panels have become saturated or fully loaded they may be replaced with new or reactivated carbon The fifth section the Exhaust Fan Motor has been sized to handle the air flow requirements for the systems and the adjoining ducting Fire Suppression System OPTIONAL When the fire suppression system has been specified to be factory furnished it consists of strategically located chemical spray nozzles D...

Страница 8: ...ve fire suppression capabilities Some contaminate is harder to remove and may require a stronger detergent solution Average settings have been factory set Best possible settings for any given installation however are determined through experience Visually examine the collecting elements after the first few washings Control System The control system is custom configured to support the ATS System de...

Страница 9: ...ieces of foreign material are lodged between the plates Also verify that the cells are properly installed in the cabinet with the spiked ionizing blades located on the air entering side Follow the air flow directional arrows Check that the high voltage wiring is connected to the proper terminals both at the ionizing collecting cells and on the power supplies Be sure that the drain lines from the d...

Страница 10: ...n In 24 hour format LCD screen shall indicate 0 00 23 59 Programming the Timer 1 Press TIMER key LCD screen shall show 1ON 2 Press DAY key to select any of the 15 combinations of daily programs to your application demand Continuing to press DAY key will cause the LCD screen to alternate among 15 combinations 3 Press HOUR and MIN respectively to set desired hour and minute for 1ON 4 After finished ...

Страница 11: ...ervoir level should be checked on a routine basis a minimum tank level established Never let the tank run dry which will damage the pump The inside of the tank should be kept clean free from dirt and foreign objects The detergent as supplied by TRION is formulated specifically for electronic air cleaners and should not be diluted when using a pre mix solution For a concentrated mix dilution will b...

Страница 12: ...ell Alvania 2 Texaco Multifac 2 or Mobilux 2 At this time examine the exhaust fan for any accumulated dirt and clean as required Troubleshooting WARNING EXERCISE THE USUAL PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE THE MAXIMUM OPERATING OUTPUT FROM THE POWER SUPPLY IS 5 5MA 11 0MA WHEN CONNECTED IN PARALLEL AND 15 000VDC IF DOOR INTERLOCK SWITCHES ARE CLOSED AND CIRCUIT IS ENERGIZED DO NOT TOUCH H...

Страница 13: ...to a single cell or ionizing or collector section of a given cell as follows First determine if the short is in the ionizing section or the collecting section by connecting each high voltage lead to its respective section one at a time and energizing the power pack The lead not connected must be supported away from any point of contact The short symptoms will still exist for the section in which t...

Страница 14: ...switch Extremely dirty insulators Clean Cracked insulators Replace Foreign object between plates Remove Bent or warped plates Repair or replace cell Leads grounded short circuit Replace Indicating light flickering Reversed high voltage leads Reconnect leads Poor filtration Loose or defective intercell connection on multicell units Tighten or replace Foreign object adrift in ionizer or plate sectio...

Страница 15: ...llation For specific recommendations consult the TRION factory or nearest Sales Office Consideration however should be given to stocking the following components Description Quantity Complete Power Supply 1ea Power Supply Indicating Light 1ea Ionizing Collect Cell Insulator 6ea TRION Detergent 55gal Part numbers are not listed as they are subject to change Always state Unit Model and Serial Number...

Страница 16: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2017 All Rights Reserved Form No 147207 001 Rev 09 17 ...

Отзывы: