background image

www.trioniaq.com

ATS Series

6

I n s t a l l a t i o n ,   O p e r a t i o n ,   a n d   S e r v i c e   M a n u a l

The  ionizing-collecting  cells  (contaminate  collecting 

elements) are housed in the cabinet on slide rails. They 

can be removed from the cabinet as required, through 

the end access door, by sliding them out like drawers. 

On multicell units, all of the electrical connections 

between cells in a given tier are automatically made 

through spring loaded contacts. When installing the 

cells into the cabinet, observe the directional arrows 

on the cell end plates. The side of the cell containing 

the spiked ionizer blades must always be located on 

the air entering side.

The 

Media Module

 is the third section of the ATS 

System. In most cases, the media is a bag filter which 

is made up of a series of long deep pockets arranged 

side-by-side. Ultra-fine fibers are used in the media to 

that trap up To 95% of the remaining particulates.

In the event of an electrical outage in the electronic 

air cleaner, the bag filter acts as a backup collector. 

Also,  in  some  applications,  the  bag  filter  will  collect 

any  contaminant  that  may  “blow-off”  the  electronic 

air cleaner. When the bags become saturated with 

contaminant they must be removed and replaced.

The fourth section of the ATS is a 

Carbon Odor 

Control Module

. Panels, filled with activated carbon 

granules, are arranged in a V-shaped bank providing 

a large surface area for the air. The surface of each 

granule is extremely porous and absorbs materials 

that are in a gaseous or vaporized state that cannot 

be  removed  by  the  previous  filter  sections.  Using 

the  carbon  filters  without  the  pre-filtration  (by  the 

bag  filters)  is  not  recommended.  When  the  panels 

have become saturated or fully loaded they may be 

replaced with new or reactivated carbon.

The  fifth  section,  the  Exhaust  Fan/Motor,  has  been 

sized  to  handle  the  air  flow  requirements  for  the 

systems and the adjoining ducting.

Fire Suppression System (OPTIONAL)

When the fire suppression system has been specified 

to be factory furnished it consists of strategically 

located chemical spray nozzles.

Depending on the installation and any local, or other 

governing requirements, the ATS unit fire suppression 

system  may  be  linked  with  other  fire  suppression 

devices. When the fire suppression system is activated, 

everything except the exhaust fan is turned off. 

After 

the fire suppression system has been activated, 

an  authorized  fire  suppression  contractor  must 

put it back into service.

When a fire control system is specified, the electronic 

air cleaner sections contain chemical spray nozzles.

Wash System

The automatic Wash System periodically cleans the 

accumulated contaminant from the cells. The wash 

system consists of a series of nozzles mounted on 

long manifolds on both sides of the cells. Gear motors 

rotate the manifolds, spraying water and detergent 

on the contaminated surfaces. Pans in the bottom 

of  each  washed  section  collect  effluent  and  drain  it 

to waste. A Detergent Feeder System adds specially 

formulated soap into the wash system. The amount 

of detergent needed for each wash is adjustable and 

depends on water pressure and temperature and the 

type and amount of contaminant collected.

The events in a wash cycle are:

1.  Power supplies and exhaust fan are turned OFF 

(1min allows the exhaust fan to coast to a stop)

2. 

Water spray wets the cells (30sec)**

3. 

Water spray and detergent (1min)**

4. 

Soak (2min)**

5.  Water Spray rinses the cells with clear water 

(2min)**

6.  Drip dry allows most of the water to drain from the 

cell (4min)

7.  Forced dry uses the exhaust fan to air dry the cells 

(60min)

Содержание Air Boss ATS Series

Страница 1: ...T R I O N w w w t r i o n i a q c o m Air Boss ATS Series Electrostatic Precipitators Commercial Industrial Applications READ AND SAVE THESE INSTRUCTIONS ...

Страница 2: ...tion 2 Operation 5 Initial Startup 8 Routine Maintenance 10 Preventative Maintenance 10 Troubleshooting 11 Troubleshooting Chart 13 Spare Parts 14 SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of operating personnel Any additional access that may be provided in the system where there is access to high voltage mu...

Страница 3: ...ments Condensation freezing and elevated temperatures must be considered CAUTION In addition to the previous space requirements installation of the Model ATS in NFPA applications shall have a clearance of at least 18 inches to a combustible material 3 inches to limited combustible material and 0 inches to noncombustible material Any reduction in clearance or exceptions must be in compliance with N...

Страница 4: ...TE LOCAL CODES High Voltage Wiring The high voltage wiring requires connecting the power supplies to the ionizing collecting cells located in the electronic air cleaner section cabinet On multicell units the wiring between the cells within a tier is automatically made with intercell spring contacts Two high voltage wires must be connected to each tier of cells in the ATS one for the ionizers and o...

Страница 5: ...eriodicalmanualfillingofthedetergenttank and to gain access to the pump and motor assembly After positioning the unit must be secured in place The Detergent System should not be installed more than 30ft below the ATS System Local disconnect is recommended for detergent tank motor Note TRION Tridex Detergent is specially formulated for use with TRION electronic air cleaners Use of other cleaners an...

Страница 6: ...matter from the air The modular sections can be built in several widths and heights to accommodate different air flow requirements Refer to the System Outline drawing for information on the specific system design for this project The first section the prefilter is primarily designed for capturing relatively large liquid particulate The second section houses an electronic air cleaner technically kn...

Страница 7: ...panels have become saturated or fully loaded they may be replaced with new or reactivated carbon The fifth section the Exhaust Fan Motor has been sized to handle the air flow requirements for the systems and the adjoining ducting Fire Suppression System OPTIONAL When the fire suppression system has been specified to be factory furnished it consists of strategically located chemical spray nozzles D...

Страница 8: ...ve fire suppression capabilities Some contaminate is harder to remove and may require a stronger detergent solution Average settings have been factory set Best possible settings for any given installation however are determined through experience Visually examine the collecting elements after the first few washings Control System The control system is custom configured to support the ATS System de...

Страница 9: ...ieces of foreign material are lodged between the plates Also verify that the cells are properly installed in the cabinet with the spiked ionizing blades located on the air entering side Follow the air flow directional arrows Check that the high voltage wiring is connected to the proper terminals both at the ionizing collecting cells and on the power supplies Be sure that the drain lines from the d...

Страница 10: ...n In 24 hour format LCD screen shall indicate 0 00 23 59 Programming the Timer 1 Press TIMER key LCD screen shall show 1ON 2 Press DAY key to select any of the 15 combinations of daily programs to your application demand Continuing to press DAY key will cause the LCD screen to alternate among 15 combinations 3 Press HOUR and MIN respectively to set desired hour and minute for 1ON 4 After finished ...

Страница 11: ...ervoir level should be checked on a routine basis a minimum tank level established Never let the tank run dry which will damage the pump The inside of the tank should be kept clean free from dirt and foreign objects The detergent as supplied by TRION is formulated specifically for electronic air cleaners and should not be diluted when using a pre mix solution For a concentrated mix dilution will b...

Страница 12: ...ell Alvania 2 Texaco Multifac 2 or Mobilux 2 At this time examine the exhaust fan for any accumulated dirt and clean as required Troubleshooting WARNING EXERCISE THE USUAL PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE THE MAXIMUM OPERATING OUTPUT FROM THE POWER SUPPLY IS 5 5MA 11 0MA WHEN CONNECTED IN PARALLEL AND 15 000VDC IF DOOR INTERLOCK SWITCHES ARE CLOSED AND CIRCUIT IS ENERGIZED DO NOT TOUCH H...

Страница 13: ...to a single cell or ionizing or collector section of a given cell as follows First determine if the short is in the ionizing section or the collecting section by connecting each high voltage lead to its respective section one at a time and energizing the power pack The lead not connected must be supported away from any point of contact The short symptoms will still exist for the section in which t...

Страница 14: ...switch Extremely dirty insulators Clean Cracked insulators Replace Foreign object between plates Remove Bent or warped plates Repair or replace cell Leads grounded short circuit Replace Indicating light flickering Reversed high voltage leads Reconnect leads Poor filtration Loose or defective intercell connection on multicell units Tighten or replace Foreign object adrift in ionizer or plate sectio...

Страница 15: ...llation For specific recommendations consult the TRION factory or nearest Sales Office Consideration however should be given to stocking the following components Description Quantity Complete Power Supply 1ea Power Supply Indicating Light 1ea Ionizing Collect Cell Insulator 6ea TRION Detergent 55gal Part numbers are not listed as they are subject to change Always state Unit Model and Serial Number...

Страница 16: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2017 All Rights Reserved Form No 147207 001 Rev 09 17 ...

Отзывы: