Product manual DALI MSensor 5DPI 14 | 06-2017 | 1.1 | en
Commissioning and Adaptions
c
11 / 48
5. Commissioning and settings
The DALI MSensor either controls all the devices on the DALI circuit or a DALI group. To enlarge the presence
detection area, it is possible to assign the same destination to several DALI MSensors . To achieve this, simply
assign the sensors to the same DALI group.
The DALI MSensor is configured in the masterCONFIGURATOR software (V2.12 or later). The DALI MSensor can
be assigned to a specific effective range. In addition, the parameters of the individual functions can be individually
adjusted.
5.1. Group assignment by using masterCONFIGURATOR
The effective range of the DALI MSensor can be set in the masterCONFIGURATOR software (V2.12 or later).
5.2. Replacing a faulty DALI MSensor V2.0
It is possible to replace a faulty DALI MSensor V2.0
5.3. Replacing a faulty DALI MSensor (V1.7 or earlier)
It is only possible to replace a faulty DALI MSensor (V1.7 or earlier) by a DALI MSensor if specific preconditions are
met:
Further adaptation is required in the case other applications:
I
NOTICE
Luminaires must not belong to more than one DALI group! Otherwise the sensors will not interpret commands
sent to the luminaire correctly.
Unlike other DALI controllers, a DALI address is assigned to the DALI MSensor during addressing. This reduces
the total number of available DALI addresses. This must be taken into account when designing the DALI circuit!
Extending an existing DALI circuit
The DALI MSensor can be used in an existing DALI circuit together with MSensor 02, when a system is extended.
It is not possible to operate a DALI MSensor and a DALI MSensor (V1.7 or earlier) in the same DALI group.
Because of the modified grouping concept, there is no synchronisation of constant light control and presence
detection between the two equipment generations.
Make sure that the MSensor 5DPI_14 controls the same group like the MSensor 2.0
_
Make sure that there is no other DALI MSensor (V1.7 or earlier) in the DALI group in question!
_
Make sure that the faulty DALI MSensor (V1.7 or earlier) is not influenced by other DALI controllers (e.g. by
the fact that a DALI GC activates daylight-based control via the sensor group).
_
If you have any queries, please contact Tridonic Technical Support.