FOAMATE

™ 2.1 ATP Foam System

FOAMATE

Foamate 2.1 General Information

Trident’s FOAMATE™ 2.1 ATP is an around-the-pump foam proportioning system that adds fast and easy to operate 

Class B

 

foam capabilities to any fire apparatus. The system utilizes a brass eductor installed on the discharge side of the fire pump 
to send a small volume of water back to the suction side of the fire pump. The venturi action of the eductor creates a vacuum 
at the foam concentrate inlet allowing foam to be pulled through the metering valve, into the water stream. The foam solution 
is discharged back to the suction side of the fire pump and sent through all the discharge piping – allowing foam solution to 
be available for each discharge outlet. The brass metering valve allows for injection rates of 1%, 3% and 6% at variable flow 
rates and pressures. Units are available in either GPM or LPM flow designations and are configured with either Victaulic™ or 
FNPT connections. 

NOTE

: Throughout this document, Victaulic ends are referred to as VIC.

Contents

Maximum System Flow Rates: ��������������������������������������������������������������������������������������������������������������������������������������������2
Foamate 2�1 General Information ����������������������������������������������������������������������������������������������������������������������������������������2
Performance and Operating Parameters ����������������������������������������������������������������������������������������������������������������������������2
Installation Instructions �������������������������������������������������������������������������������������������������������������������������������������������������������3
Foam System Operating Procedures from On-Board Foam Tank ��������������������������������������������������������������������������������������4
Foam System Operating Procedures from External Auxiliary Foam Concentrate Source ��������������������������������������������������4
General Operating Tips for ATP Foam Systems ������������������������������������������������������������������������������������������������������������������4
Foam System Shutdown Instructions ���������������������������������������������������������������������������������������������������������������������������������4
Foam System Flushing Instructions ������������������������������������������������������������������������������������������������������������������������������������4
Schematic/Instruction Plate Template ���������������������������������������������������������������������������������������������������������������������������������5
Metering Valve/Dial Template ����������������������������������������������������������������������������������������������������������������������������������������������5
Piping Schematic ����������������������������������������������������������������������������������������������������������������������������������������������������������������6
Benefits of an External Pickup Tube - Enhancing Your Foam System ��������������������������������������������������������������������������������7
Model Numbers and Parts Listing ���������������������������������������������������������������������������������������������������������������������������������������8
Metering Valve Details ���������������������������������������������������������������������������������������������������������������������������������������������������������9
Foam System Maintenance �����������������������������������������������������������������������������������������������������������������������������������������������10
Foamate 2�1 Rebuild Kit ����������������������������������������������������������������������������������������������������������������������������������������������������10
Installation Notes ���������������������������������������������������������������������������������������������������������������������������������������������������������������11
Operating Notes ����������������������������������������������������������������������������������������������������������������������������������������������������������������11
Other Foam System Products �������������������������������������������������������������������������������������������������������������������������������������������12

Maximum System Flow Rates:

1% Injection: 2000 GPM 

[8000 LPM]

3% Injection: 2000 GPM 

[8000 LPM]

6% Injection: 1000 GPM 

[4000 LPM]

Performance and Operating Parameters

 

„

Eductor

: All brass construction. 1

1

2

[38 mm]

 water inlet, 2" 

[50 mm]

 foam concentrate inlet, 2" 

[50 mm] 

foam solution 

outlet. All connections are pipe groove Victaulic.

 

„

Eductor Flow

: 85 GPM 

[320 LPM]

 at 125 PSI 

[8.5 Bar].

 

„

System Operating Pressure

: 125 – 250 PSI 

[8.5 – 17 Bar].

 

„

Flow Rates

: Variable flow rates to multiple discharge outlets 

up to the maximum foam system capacity.

 

„

Factory calibrated. Meets NFPA Standards.

 

„

Metering Valve

: All brass construction. 2" 

[50 mm] 

pipe 

groove Victaulic or FNPT foam concentrate inlet and outlet.

 

„

All discharge outlets provide foam solution at the same time.

 

„

No back pressure restriction from hose lengths or elevation.

 

„

Compatible with any type of foam concentrate and foam 
making nozzle.

 

„

Fire pump operations do not change.

 

„

Maximum fire pump inlet pressure: 5 PSI 

[0.35 Bar].

Содержание FOAMATE 2.1

Страница 1: ...Class B ATP Foam System FOAMATE 2 1 Technical Manual ...

Страница 2: ...d Foam Tank 4 Foam System Operating Procedures from External Auxiliary Foam Concentrate Source 4 General Operating Tips for ATP Foam Systems 4 Foam System Shutdown Instructions 4 Foam System Flushing Instructions 4 Schematic Instruction Plate Template 5 Metering Valve Dial Template 5 Piping Schematic 6 Benefits of an External Pickup Tube Enhancing Your Foam System 7 Model Numbers and Parts Listing...

Страница 3: ...ll shut off valve Schematic Instruction Chart A backing plate is supplied for the schematic instruction plate and must be mounted in close proximity to the foam metering valve Refer to Figure 2 on Page 5 for the mounting hole dimensions Plumbing Requirements NOTE The design of the Metering Valve and Eductor are not intended to support the weight of the 2 50 mm plumbing Piping to and from the Educt...

Страница 4: ...2 50 mm system flush valve must be closed 6 Open 2 50 mm external auxiliary foam concentrate inlet valve NOTE The foam system will work properly from draft or the on board water tank If operating from a pressurized water source hydrant or relay pumper maximum fire pump inlet pressure cannot exceed 5 PSI 0 35 BAR for proper foam system operation In the event of high fire pump inlet pressure install...

Страница 5: ...Metering Valve 1 2 11 2 x 2 Eductor 1 3 2 Brass Swing Type Check Valve 1 4 Schematic Instruction Plate 1 5 Backing Plate 1 FOAMATE 2 1 System Components With Ball Valves See Page 8 for Kit Part Numbers and Component Details Item Description Quantity 1 2 Foam Concentrate Metering Valve 1 2 11 2 x 2 Eductor 1 3 2 Brass Swing Type Check Valve 1 4 Schematic Instruction Plate 1 5 Backing Plate 1 6 2 Br...

Страница 6: ... On Board Water Tank Apparatus On Board Foam Tank All Foamate 2 1 Piping to be a Minimum of 2 ID All Piping To Be Supplied By System Installer Water Pump Three 2 Ball Valves Provided with Kits that include valves 2 Ball Valve available for Auxiliary Foam Inlet P N 30 058 0 Piping Schematic FOAMATE 2 1 Piping Schematic Shown below is the typical installation of the FOAMATE 2 1 ATP Foam Proportionin...

Страница 7: ...Concentrate Pickup Tube Assemblies ure 4 FOAMATE 2 1 ATP Auxiliary Foam Pickup Kits Part Description 10 010 1 2 x 10 Pickup Hose and Pickup Tube Without Ball Valve 10 010 2 2 x 10 Pickup Hose and Pickup Tube With Ball Valve Benefits of an External Pickup Tube Enhancing Your Foam System With a pick up tube the system can use either Class A or Class B foam that is a huge advantage in operation capab...

Страница 8: ...VIC Ends 1 02 028 2 Label Foamate 2 1 LPM Flow Rates 1 02 023 1 Label Foamate 2 1 Instruction 1 02 023 2 Backing Plate Label 1 30 064 0 2 FNPT Check Valve 1 31 014 4 Foamate 2 1 ATP System VIC Ends GPM Flow Rates With Ball Valves Part Number Description Qty 30 043 4 2 Metering Valve VIC Ends 1 31 005 0 11 2 x 2 Eductor VIC Ends 1 02 028 1 Label Foamate 2 1 GPM Flow Rates 1 02 023 1 Label Foamate 2...

Страница 9: ...ers Item Qty Part Description Material 1a 1 07 017 1 Body 2 Inch Foam Bypass Valve VIC Brass 1b 1 07 017 2 Body 2 Inch Foam Bypass Valve FNPT Brass 2 1 12 005 0 Cylinder 2 Inch Bypass Valve Brass 3 1 26 119 1 O Ring 119 EPDM 4 1 26 125 1 O Ring 125 EPDM 5 1 17 003 6 Slotted Spring Pin 1 8 x 3 4 Long Stainless 6 2 17 003 5 Slotted Spring Pin 1 8 x 1 2 Long Stainless 7 1 04 046 0 Retaining Ring Inte...

Страница 10: ...t procedures when doing any apparatus service 3 Foam tank shut off valve must be closed 4 Place metering valve in the closed position 5 Refer to exploded view of metering valve on Page 9 prior to metering valve disassembly Make note of all component positions and match mark all components during disassembly to maintain correct orientation during reassembly 6 Remove two 2 screws from metering valve...

Страница 11: ... 0701 sales tridentdirect com 11 Technical Manual Class B Foam System Installation Notes Record details of the installation on your Fire Truck Operating Notes Training notes on operation of the foam system on your Fire Truck ...

Страница 12: ...dentemergency GP Series Foam Pumps Other Foam System Products Model U Universal Mount Model H Hydraulic Mount Model M Bell Housing Mount Contact Us For Details On These And Other Foam System Products FOAMATE 2 1 Installed Trident Emergency Products LLC 2940 Turnpike Drive Suite 9 Hatboro PA 19040 USA 215 293 0700 Phone 215 293 0701 Fax sales tridentdirect com Email TridentDirect com FOAM PUMPS TM ...

Отзывы: