Digital Output Module Indicators
187
Chapter 5
Fault and Alarm Indicators
DO Status Indicators
The DO status indicators identify the processing state for the DO Module.
A fault light indicates that the module has an internal fault. If you have a field fault
and a module fault, resolve the field fault first.
Normal State
Pass
Fault
Active
Lock
Description
Action
Green
steady
No
light
Green
steady
No
light
Module is operating normally.
No action is required.
Fault States
Pass
Fault
Active
Lock
Description
Action
Green
steady
No
light
No
light
No
light
Possible conditions include:
Application has not been loaded
into the MP.
If the module is the hot spare,
no action is required.
Application has been loaded
into the MP, but has not been
started up.
Module has just been installed
and is currently running start-up
diagnostics.
Other module is active.
If the module is active, replace
module.
No
light
Red
steady
—
1
No
light
Possible conditions include:
Module may be in the process
of power-up self-test.
If the Pass indicator does not
go on within five minutes,
replace the module.
Excessive load current required.
Correct field fault condition.
Module has detected a fault.
Module is operational, but
should be replaced.
—
—
—
Red
steady
Module is unlocked from the
baseplate.
Lock module using a #2 flat-
blade screwdriver.
Green
steady
Red
steady
—
—
Indicators/signal circuitry on
the module are malfunctioning.
Replace the module.
1. This symbol ( — ) means the indicator is not important for this condition.
Содержание Trident
Страница 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Страница 10: ...x Contents Trident Planning and Installation Guide ...
Страница 16: ...xvi Training Trident Planning and Installation Guide ...
Страница 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Страница 63: ...Communication Module 47 Chapter 3 System Description Model 2201 Communication Module Baseplate ...
Страница 106: ...90 Input Output Modules Trident Planning and Installation Guide Model 2401 Digital Output Baseplate ...
Страница 128: ...112 Input Output Modules Trident Planning and Installation Guide Model 2451 Solid State Relay Output Baseplate ...
Страница 140: ...124 Covers Trident Planning and Installation Guide ...
Страница 145: ...Guidelines 129 Chapter 4 Installation and Maintenance Depth Dimensions for Baseplate and Module ...
Страница 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Страница 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Страница 240: ...224 Trident Planning and Installation Guide ...
Страница 248: ...232 Trident Planning and Installation Guide ...
Страница 264: ...248 Glossary Trident Planning and Installation Guide ...
Страница 274: ...258 Index Trident Planning and Installation Guide ...