182
Analog Output Module Indicators
Trident Planning and Installation Guide
AO Field Alarm Indicator
The AO field fault indicator is lit when a field power problem has occurred.
Field
Alarm
Description
Action
Yellow
steady
Field power from one or more
of the redundant sources is
missing or a field error is
detected. A field error may be
an open load or an out-of-
compliance error.
To isolate the missing power source, use
the TriStation Diagnostic Panel.
To determine the actual state, use a
voltmeter, then correct the problem in the
external circuit.
If these steps do not solve the problem,
replace the module.
Содержание Trident
Страница 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Страница 10: ...x Contents Trident Planning and Installation Guide ...
Страница 16: ...xvi Training Trident Planning and Installation Guide ...
Страница 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Страница 63: ...Communication Module 47 Chapter 3 System Description Model 2201 Communication Module Baseplate ...
Страница 106: ...90 Input Output Modules Trident Planning and Installation Guide Model 2401 Digital Output Baseplate ...
Страница 128: ...112 Input Output Modules Trident Planning and Installation Guide Model 2451 Solid State Relay Output Baseplate ...
Страница 140: ...124 Covers Trident Planning and Installation Guide ...
Страница 145: ...Guidelines 129 Chapter 4 Installation and Maintenance Depth Dimensions for Baseplate and Module ...
Страница 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Страница 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Страница 240: ...224 Trident Planning and Installation Guide ...
Страница 248: ...232 Trident Planning and Installation Guide ...
Страница 264: ...248 Glossary Trident Planning and Installation Guide ...
Страница 274: ...258 Index Trident Planning and Installation Guide ...