FMS-2000M
LIT-12013578
27
BMS integration
Configuring the display module settings
FMS-2000M DIP switch position
Demo mode
Run mode
Position 1
On
On
Position 2
On
On
Position 3
Off
On
Position 4
On
Off
Table 17:
Monitor DIP switch configurations for the operating modes
Objects
Analog inputs
Read/Write
Availability of analog input objects
FMS2M-Bx1x FMS2M-Bx2x FMS2M-Bx3x FMS2M-Bx4x
AI-1
Analog input 1, differential pressure
Read only
Yes
Yes
Yes
Yes
AI-2
Analog input 2, differential pressure
Read only
No
Yes
Yes
Yes
AI-3
Analog input 3, differential pressure
Read only
No
No
Yes
Yes
AI-4
Analog input 4, differential pressure
Read only
No
No
No
Yes
Note:
In the following tables, the abbreviation NV refers to network variable (NV).
Objects
Binary inputs
Read/Write
Availability of binary input objects
FMS2M-Bx1x FMS2M-Bx2x FMS2M-Bx3x FMS2M-Bx4x
BI-1
Digital input 1, door switch 1
Read only
Yes
Yes
Yes
Yes
BI-2
Digital input 2, door switch 2
Read only
No
Yes
Yes
Yes
BI-3
Digital input 3, door switch 3
Read only
No
No
Yes
Yes
BI-4
Digital input 4, door switch 4
Read only
No
No
No
Yes
Objects
Analog values
Read/Write
Availability of analog value objects
FMS2M-Bx1x FMS2M-Bx2x FMS2M-Bx3x FMS2M-Bx4x
AV-1
NV Temperature 1
Read or write
Yes
Yes
Yes
Yes
AV-2
Low alarm setpoint 1
Read or write
Yes
Yes
Yes
Yes
AV-3
Low warning setpoint 1
Read or write
Yes
Yes
Yes
Yes
AV-4
High warning setpoint 1
Read or write
Yes
Yes
Yes
Yes
AV-5
High alarm setpoint 1
Read or write
Yes
Yes
Yes
Yes
AV-6
NV Humidity 1
Read or write
Yes
Yes
Yes
Yes
AV-7
NV Temperature 2
Read or write
No
Yes
Yes
Yes
AV-8
Low alarm setpoint 2
Read or write
No
Yes
Yes
Yes
AV-9
Low warning setpoint 2
Read or write
No
Yes
Yes
Yes
AV-10
High warning setpoint 2
Read or write
No
Yes
Yes
Yes
AV-11
High alarm setpoint 2
Read or write
No
Yes
Yes
Yes
AV-12
NV Humidity 2
Read or write
No
Yes
Yes
Yes
Table 18: Analog inputs for integration in a BMS
Table 19: Binary inputs for integration in a BMS
Table 20: Analog values for integration in a BMS