TRIATEK FMS-2000M Скачать руководство пользователя страница 20

FMS-2000M

LIT-12013578

20

Wiring two remote pressure sensors to the monitor

Note: 

For optimum network communications, connect the reference signal (REF) to the COM terminal on the supervisory device’s FC 

bus terminal block.

-V

in

  V

o

Io

G

N

D

-

+

+V

in

+V

s

IN

-V

in

  V

o

Io

G

N

D

-

+

+V

in

+V

s

IN

24 VAC

output

Common

White

Black

Blue

To BAS

network

-

+

Ref.

Red

Black

Green

White

RS485

RS485

+

-

+

-

+

-

REF

24V_IN

DSPLY

RS485

BACnet

MS/TP

L

an

d

sc

ap

e

Portrait

Red

Black

White

Green

Supplied pre

-wire

d

 10 � cable

22 AWG stranded twisted pair

22 AWG stranded 3-wire

twisted pair, shielded

Supplied power supply

120 VAC input
240 VAC input

120 VAC/240 VAC

60/50Hz input

Figure 14: Wiring two remote pressure sensors to the monitor

Callout

Component

1

FMS-2000M monitor

2

Supplied remote pressure sensors 1 and 2, in order from left to right

3

Optional door switch

Note: 

Configure the door switch setting on the monitor. It can be normally closed or normally open.

4

Io terminal

Note: 

A 4mA to 20mA signal is present at each of the sensors' Io terminals which represents the monitored room pressure. You can use 

it to remotely monitor room pressure when you connect the terminal to a third party controller on the BMS network.

5

Supplied power supply

6

AC power input options

7

BACnet MS/TP

Table 10: 

Wiring two remote pressure sensors to the monitor

Содержание FMS-2000M

Страница 1: ...1 FMS 2000M Critical Environment Monitor LIT 12013578 September 2020 Installation Guide ...

Страница 2: ...voltage wiring and equipment Failure to isolate network wiring and network devices from high voltage wiring and equipment can result in damage to network devices or poor network performance Risk of Property Damage Label all wires prior to disconnecting the equipment Failure to label the wires may cause improper equipment operation after reconnecting the equipment Risk of Property Damage Do not con...

Страница 3: ...he FMS 2000M Critical Environment Monitor IMPORTANT Maintain proper polarity and voltage or current ratings Improper polarity or exceeding the voltage or current ratings will void the warranty IMPORTANT Do not install the FMS 2000M Critical Environment Monitor where the maximum temperature exceeds 125 F 52 C Installing the device where maximum temperatures exceed 125 F 52 C may cause damage to the...

Страница 4: ...ériels Ne passez pas les câbles de communication réseau dans les mêmes gaines chemins de câbles ou panneaux que les câbles à haute tension supérieure à 30 Vca Isolez tous les câbles et appareils réseau des câbles et appareils à haute tension Un défaut d isolement des câbles et appareils à haute tension peut provoquer des dommages aux appareils réseau et réduire les performances du réseau Risque de...

Страница 5: ...rant Une mauvaise polarité ou le dépassement de la tension ou du courant annulera la garantie IMPORTANT N installez pas le contrôleur d environnement critique FMS 2000M où la température maximum dépasse 52 C 125 F Installer l appareil dans un environnement où la température maximum dépasse 52 C 125 F peut endommager FMS 2000M Critical Environment Monitor et peut annuler la garantie IMPORTANT N uti...

Страница 6: ... BACnet MS TP communications 17 Wiring one remote pressure sensor to the monitor 18 Wiring two remote pressure sensors to the monitor 20 Wiring three remote pressure sensors to the monitor 22 Wiring four remote pressure sensors to the monitor 24 Upgrading an FMS 1655M monitor to an FMS 2000M monitor 26 Configuring the display module settings 27 BMS integration 27 Technical specifications 29 Produc...

Страница 7: ... room status awareness with the color coded visual alarms that display on screen and the 360 Safety Halo illuminated edge which allows staff to easily monitor spaces down long corridors You can mute the audible alarm with one tap to the screen to reduce audible alarm fatigue The FMS 2000M features two password protected access levels one for administrators and one for restricted level users such a...

Страница 8: ... Use a 2 Phillips head screwdriver to secure both the box and the bracket Note Do not overtighten the screws because the mounting bracket could warp 9 Connect the wires to the back of the monitor Refer to Figure 11 for more information 10 Align the two slots on the back of the monitor with the tabs on the bracket then swing the monitor towards the wall so that the single tab on the bracket slots i...

Страница 9: ...578 9 6 06 in 4 485 in 3 338 in 0 548 in 0 5 in 4 311 in 2 519 in 2 878 in 63 983 mm 73 101 mm 109 499 mm 12 07 mm 13 919 mm 84 785 mm 113 919 mm 153 924 mm Figure 3 Retrofit ring Figure 2 Retrofit application dimensions ...

Страница 10: ... Critical Environment Monitor 2 Monitor bracket 3 Wall 4 Retrofit ring 5 Mounting screw 6 Set screw Figure 4 Side view of a retrofit application of the FMS 2000M monitor Table 2 FMS 2000M Critical Environment Monitor components for a retrofit application ...

Страница 11: ...e mounting tabs of the rough in box Use a 2 Phillips head screwdriver to secure the bracket with the screws provided Make sure the bracket is level Note Do not overtighten the screws because the mounting bracket could warp 7 Connect the wires to the back of the monitor Refer to Figure 11 for more information 8 Align the two slots on the back of the monitor with the tabs on the bracket and swing th...

Страница 12: ...M Critical Environment Monitor 2 Mounting bracket 3 Wall 4 Stud 5 Rough in box 6 Mounting screw 7 Set screw Table 3 FMS 2000M Critical Environment Monitor components for a new application Figure 7 Side view of a new application of the FMS 2000M monitor ...

Страница 13: ...hould not exceed 1 000 ft 2 Remove each sensor s louvered cover plate and stainless steel backplate from the orange wall bracket 3 Cut an opening in the wall of the monitored space for the orange low voltage mounting bracket and for the remote pressure sensor electronics Nominal hole dimensions are 3 65 in 9 271 cm H x 2 15 in 5 461 cm W 4 Use the rotating clamps to secure the bracket to the wall ...

Страница 14: ...le 4 Remote pressure sensor installation components Number Description 1 Gasket 2 Stainless steel flow tube mounting plate 3 Wall section in cut away view 4 Flow tube 5 Stainless steel mounting plate 6 Gasket 7 Louvered cover plate 8 Remote pressure sensor 9 Mounting bracket 10 Terminal block 11 Thin silicone caulking ...

Страница 15: ...former To check if your FMS 2000M includes an isolated power supply see Product code matrix IMPORTANT Install the FMS 2000M Critical Environment Monitor with a Class 2 Limited Energy or LPS isolated power supply and connect it to an electrical circuit protected by a minimum 20 A circuit breaker Mount the circuit breaker in an approved electrical enclosure located separately but in close proximity ...

Страница 16: ...ble 6 24 VAC to 24 VAC isloation transformer Item Description 1 Black 24 VAC input 50 60 Hz 2 Ground 3 Isolation transformer 24 VAC to 24 VAC 30 VA 4 Red 24 VAC output 50 60 Hz 5 1 A slow blow fuse 6 Class 2 Limited Energy or LPS isolated power supply wiring in this compartment ...

Страница 17: ...3 Power supply Note The figure shows a 120 VAC to 24 VAC step down isolation transformer as an example For information about correct power supply termination see the following wiring information Wiring one remote pressure sensor to the monitor Wiring two remote pressure sensors to the monitor Wiring three remote pressure sensors to the monitor Wiring four remote pressure sensors to the monitor 4 S...

Страница 18: ...24V_IN DSPLY RS485 BACnet MS TP Landscape Portrait 120 VAC 240 VAC 60 50Hz input Figure 12 Wiring one remote pressure sensor to the monitor Callout Component 1 FMS 2000M monitor 2 Remote pressure sensor DIP switch SW1 3 Supplied remote pressure sensor 4 Io terminal Note A 4mA to 20mA signal is present at the sensor s Io terminal which represents the monitored room pressure You can use it to remote...

Страница 19: ...r Off for inverted After you change the sensor mode with switch 5 cycle power to the sensor for the mode change to take effect On or off 6 Reserved n a 7 Reserved n a 8 Sensor communications termination Off Figure 13 Remote pressure sensor DIP switch configuration for one sensor models Table 9 Remote pressure sensor DIP switch positions for one sensor models ...

Страница 20: ...upplied power supply 120 VAC input 240 VAC input 120 VAC 240 VAC 60 50Hz input Figure 14 Wiring two remote pressure sensors to the monitor Callout Component 1 FMS 2000M monitor 2 Supplied remote pressure sensors 1 and 2 in order from left to right 3 Optional door switch Note Configure the door switch setting on the monitor It can be normally closed or normally open 4 Io terminal Note A 4mA to 20mA...

Страница 21: ...normal or Off for inverted After you change the sensor mode with switch 5 cycle power to the sensor for the mode change to take effect On or off On or off 6 Reserved n a n a 7 Reserved n a n a 8 Sensor communications termination Off On Table 11 Remote pressure sensor DIP switch configuration for two sensor models Figure 15 Remote pressure sensor DIP switch configuration for two sensor models ...

Страница 22: ...twisted pair Common White Black Blue 120 VAC input 240 VAC input 120 VAC 240 VAC 60 50Hz input Figure 16 Wiring three remote pressure sensors to the monitor Callout Component 1 FMS 2000M monitor 2 Supplied remote pressure sensors 1 2 and 3 in order from left to right 3 Optional door switch Note Configure the door switch setting on the monitor It can be normally closed or normally open 4 Io termina...

Страница 23: ...witch to On for normal or Off for inverted After you change the sensor mode with switch 5 cycle power to the sensor for the mode change to take effect On or off On or off On or off 6 n a n a n a 7 n a n a n a 8 Sensor communications termination Off Off On Figure 17 Remote pressure sensor DIP switch configuration for three sensor models Table 13 Remote pressure sensor DIP switch configuration for t...

Страница 24: ...ted pair shielded Supplied pre wired 10 cable R e d B la c k G re e n White 22 AWG stranded twisted pair 22 AWG stranded twisted pair 22 AWG stranded twisted pair Red Black White Green Callout Component 1 FMS 2000M monitor 2 Supplied remote pressure sensors 1 2 3 and 4 in order from left to right 3 Optional door switch Note Configure the door switch setting on the monitor It can be normally closed...

Страница 25: ... switch to On for normal or Off for inverted After you change the sensor mode with switch 5 cycle power to the sensor for the mode change to take effect On or off On or off On or off On or off 6 Reserved n a n a n a n a 7 Reserved n a n a n a n a 8 Sensor communications termination Off Off Off On Figure 19 Remote pressure sensor DIP switch configuration for four sensor models Table 15 Remote press...

Страница 26: ...f you use a BACnet network connect the networking cable to the 3 pin header See the figure above 8 To complete the installation see Mounting the FMS 2000M monitor for a retrofit application Upgrading an FMS 1655M monitor to an FMS 2000M monitor Callout Description 1 FMS 2000M monitor 2 FMS 1655M remote pressure sensor 3 Red display power wire If the sensor includes a 3 position terminal block with...

Страница 27: ... Yes BI 2 Digital input 2 door switch 2 Read only No Yes Yes Yes BI 3 Digital input 3 door switch 3 Read only No No Yes Yes BI 4 Digital input 4 door switch 4 Read only No No No Yes Objects Analog values Read Write Availability of analog value objects FMS2M Bx1x FMS2M Bx2x FMS2M Bx3x FMS2M Bx4x AV 1 NV Temperature 1 Read or write Yes Yes Yes Yes AV 2 Low alarm setpoint 1 Read or write Yes Yes Yes ...

Страница 28: ... or write No No No Yes AV 21 Low warning setpoint 4 Read or write No No No Yes AV 22 High warning setpoint 4 Read or write No No No Yes AV 23 High alarm setpoint 4 Read or write No No No Yes AV 24 NV Humidity 4 Read or write No No No Yes Objects Multistate objects Read Write Availability of multistate objects FMS2M Bx1x FMS2M Bx2x FMS2M Bx3x FMS2M Bx4x MV 1 Isolation mode 1 positive 2 negative 3 n...

Страница 29: ...to 50 user passwords with 2 access levels administrator and restricted Communications protocol BACnet MS TP to BAS 76 8k 38 4k 19 2k 9600 baud Power requirement 24 VAC nominal 21 6 VAC minimum 26 4 VAC maximum 50 60 Hz 30 VA power supply Class 2 Limited Energy or LPS isolated power supply Power consumption 30 VA maximum Optional input power supply Universal 120 VAC 240 VAC to 24 VAC 30 VA step dow...

Страница 30: ... pressure sensors 4 ISO power supply 0 No power supply included 1 Universal 120 VAC 240 VAC to 24 VAC 2 24 VAC to 24 VAC 1 IMPORTANT Do not apply cleaner directly to the touch panel surface If cleaner spills onto the touch panel soak up the cleaner immediately with an absorbent cloth Do not use cleaner that is either acid or alkali Use neutral pH cleaner Do not use organic chemicals such as paint ...

Страница 31: ...ited States Canada This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used i...

Отзывы: