FMS-2000M
LIT-12013578
15
Wiring the isolated power supply
Item
Description
1
Red, 24 VAC connected to the FMS-2000M monitor
2
Red, 24 VAC connected to the FMS-2000M monitor
3
Transformer 50 Hz/60 Hz
4
1 A slow blow fuse
5
Black, 120 VAC, 50 Hz/60 Hz
6
White, VAC common for 120 VAC and 240 VAC, 50 Hz/60 Hz
7
Blue, 240 VAC, 50 Hz/60 Hz
8
Ground
9
Class 2, Limited Energy, or LPS isolated power supply wiring in this compartment
Table 5:
Universal 120 VAC/ 240 VAC to 24 VAC stepdown isloation transformer
Figure 9: Universal 120 VAC/ 240 VAC to 24 VAC stepdown isloation transformer
To check if your FMS-2000M includes an isolated power supply, see
Product code matrix
.
IMPORTANT:
Install
the FMS-2000M Critical Environment Monitor with a Class 2, Limited Energy, or LPS isolated power supply
and connect it to an electrical circuit protected by a minimum 20 A circuit breaker. Mount the circuit breaker in an approved electrical
enclosure located separately, but in close proximity, to
the FMS-2000M monitor.
IMPORTANT :
Installez
le FMS-2000M Critical Environment Monitor en utilisant un bloc d’alimentation de classe 2, à limitation
d’alimentation ou LPS et raccordez-le à un circuit électrique protégé par un disjoncteur d’un minimum de 20 A. Placez le disjoncteur
du
FMS-2000M
dans un panneau électrique approuvé et situé à l’écart, mais à proximité.