
FMS-2000M
LIT-12013578
24
Wiring four remote pressure sensors to the monitor
Figure 18: Wiring four remote pressure sensors to the monitor
Note:
For optimum network communications, connect the reference signal (REF) to the COM terminal on the supervisory device’s FC
bus terminal block.
-V
in
V
o
Io
G
N
D
-
+
+V
in
+V
s
IN
-V
in
V
o
Io
G
N
D
-
+
+V
in
+V
s
IN
-V
in
V
o
Io
G
N
D
-
+
+V
in
+V
s
IN
-V
in
V
o
Io
G
N
D
-
+
+V
in
+V
s
IN
To BAS
network
-
+
Ref.
RS485
RS485
RS485
RS485
+
-
+
-
+
-
REF
24V_IN
DSPLY
RS485
BACnet
MS/TP
L
an
d
sc
ap
e
Portrait
24 VAC
output
Common
White
Black
Blue
120 VAC input
240 VAC input
120 VAC/240 VAC
60/50Hz input
22 AWG stranded 3-wire
twisted pair, shielded
Supplied pre
-wire
d
10 � cable
Red
Black
Green
White
22 AWG stranded twisted pair
22 AWG stranded twisted pair
22 AWG stranded twisted pair
Red
Black
White
Green
Callout
Component
1
FMS-2000M monitor
2
Supplied remote pressure sensors 1, 2, 3, and 4, in order from left to right
3
Optional door switch
Note:
Configure the door switch setting on the monitor. It can be normally closed or normally open.
4
Io terminal
Note:
A 4mA to 20mA signal is present at each of the sensors' Io terminals which represents the monitored room pressure. You can use
it to remotely monitor room pressure when you connect the terminal to a third party controller on the BMS network.
5
Supplied power supply
6
AC power input options
7
BACnet MS/TP
Table 14:
Wiring four remote pressure sensors to the monitor