2472 DI HEATER OPERATION / MAINTENANCE MANUAL
PAGE 23
7
MAINTENANCE
7.1 REPAIR INSTRUCTIONS
7.1.a Heater Element Check
Follow Lockout/Tagout procedures as referenced in the Safety
section of this manual.
The resistance of each 6 kW heater element winding is 36 ohms.
Remove the 20 Amp fuses and check across the right hand element
terminals at the fuse block. Refer to schematic.
Another reference (with 20 Amp fuses removed) is from the right
hand element terminal to ground, in which case a value of at least
one mega-ohm resistance should be measured.
Resistance through the element or to ground at values less than
indicated probably indicates a faulty element, in which case a heater
module replacement is necessary.
7.1.b Fuse Replacement
A power distribution indicator (LED) that does not illuminate along
with the others on the control panel indicates a blown 20 Amp fuse of
a failed heater. Each heater module contains three (3) 6 kW
elements with a 20 Amp fuse at either end of the element wiring. The
labeling of the power distribution LED’s should correspond with the
fuse block labeling. The LED indicates which element is inoperative
but not which fuse.
!
CAUTION:
Fuses must be replaced with the same type of fuses and
rating. Failure to do so could result in a safety hazard and cause
injury to personnel and equipment. Consult factory for further
information.
Follow Lockout/Tagout procedures as referenced in the Safety
section of this manual.