2472 DI HEATER OPERATION / MAINTENANCE MANUAL
PAGE 21
5.4 HEATER MODULE POWER
Press HEATER ON button and adjust the setpoint to the desired
temperature. T
o do this, press the “
” button on the face of the
Controller unit. Scroll to the desired setpoint temperature. Temperature
controller setpoint will remain at last setting during a restart. (See Figure
5-1.)
NOTE: Maximum setpoint is 90
C.
5.5 POWER DISTRIBUTION INDICATORS
Each 18 kW Heater Module contains three (3) 6 kW resistive heating
elements that are electrically fused at either end. The LED indicators on
the control panel will indicate the functioning of each element (see Figure
3-1: Facility Installation Layout). An indicator that does not illuminate in
conjunction with others indicates a blown fuse on one side of the element
or possibly a failed heater (see Section 8, Troubleshooting).