Chimney Termination Requirements
Must have an approved cap (to prevent water from entering)
Must not be located where it will become plugged by snow or other material
Must terminate at least 3' (914mm) above the roof
and
at least 2' (610mm) above any portion of the
roof within 10' (3.048M) (see Figure 5)
Figure 5
Outside Air Requirements
Required for mobile homes and in certain localities (check with local building official)
Must not be drawn from an enclosed space (garage, unventilated crawl space)
Requires a 3” duct that attaches to the bottom of the stove (see “a” and “b” below).
Outside air duct must have a rodent screen and rain hood (“c”).
The Travis Industries Outside Air Kit (sku 99200139) includes all the above components.
Figure 6
Slanted Roofs
Flat Roofs
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney