Installation
(for qualified installers only)
29
© Travis Industries
4070620
100-01199_000
Termination Requirements
NOTE
: Measure all clearances from the nearest edge of the exhaust hood.
A
Minimum 230mm clearance from any door or window
B
Minimum 305mm above any grade, veranda, porch, deck or balcony
C
Minimum 0mm from outside corner walls
D
Minimum 0mm from inside corner walls
E
Minimum 280mm clearance below unventilated soffits or roof surfaces
Minimum 460mm clearance below ventilated soffits
Minimum 150mm clearance below roof eaves
NOTE
: Vinyl surfaces require 610mm
F
Minimum 460mm clearance below a veranda, porch, deck or balcony (must have two open sides)
G
Minimum 1.2m clearance from any adjacent building
H
Minimum 2.1m clearance above any grade when adjacent to public walkways or driveways
NOTE: may not be used over a walkway or driveway shared by an adjacent building
I
Minimum 1.2m clearance from any mechanical air supply inlet
J
Minimum 915mm clearance above and 48” below and to the sides of non-mechanical air supply
inlet
K
Minimum 915mm from the area above the meter/regulator (vent outlet)
L
Minimum 915mm from the meter/regulator (vent outlet)
M
Minimum 610mm above the roof line (for vertical terminations)
N
Minimum 610mm horizontal clearance to any surface (such as an exterior wall) – for vertical
terminations
•
Use the vinyl siding standoff when installing on an exterior with vinyl siding.
•
Vent termination must not be located where it will become plugged by snow or other material.
•
Venting termination shall not be recessed into a wall or siding.
11” Min.
6” Min.
Roof
Surface
Roof
Eaves
C
B
H
E
G
A
D
F
L
K
J
I
NOTE: Measure clearances to the nearest edge of the exhaust hood.
A
E
E
M
N
280mm Min.
13mm
Min.