Travis Industries GreenSmart 564 GS Скачать руководство пользователя страница 31

 

Installation

  

(for qualified installers only)

 

31 

© Travis Industries 

4090709 

100-01222_000 

 Termination Requirements 

Venting terminals shall not be recessed into a wall or siding. 

Minimum 9" (229mm) clearance from any door or window 

Minimum 12" (305mm) above any grade, veranda, porch, deck or balcony 

Minimum 1" (25mm) from outside corner walls  

NOTE

: Clearance in accordance with local installation codes and the requirements 

of the gas supplier. 

Minimum 1" (25mm) from inside corner walls  

NOTE

: Clearance in accordance with local installation codes and the requirements 

of the gas supplier. 

11" Min.

(279mm)

6" Min.
(152mm)

Roof 

Surface

Roof 

Eaves

Minimum 11" (279mm) clearance below unventilated soffits or roof surfaces 
Minimum 18" (457mm) clearance below ventilated soffits 
Minimum 6" (152mm) clearance below roof eaves 

NOTE

: Vinyl surfaces require 24" (610mm) 

NOTE

: Clearance in accordance with local installation codes and the requirements of the gas supplier. 

Minimum 12" (305mm) clearance below a veranda, porch, deck or balcony   

NOTE

:  Permitted only if veranda, porch, deck, or balcony is fully open on a minumum of two sides beneath the floor. 

NOTE

: Clearance in accordance with local installation codes and the requirements of the gas supplier. 

Minimum 48" (1219mm) clearance from any adjacent building 

Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or driveways 
NOTE: may not be used over a walkway or driveway shared by an adjacent building 

Minimum 9" (229mm) clearance to any nonmechanical air supply inlet to the building or the combustion air inlet 
to any other appliance. 

Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10’ (3M) horizontally 

Minimum 36" (914mm) from the area above the meter/regulator  (vent outlet)  - this extends 15’ (4.5M) above the regulator 

NOTE

: Clearance in accordance with local installation codes and the requirements of the gas supplier. 

Minimum 36" (914mm) from the meter/regulator (vent outlet)  

NOTE

: Clearance in accordance with local installation codes and the requirements of the gas supplier. 

M  Minimum 12” (305mm) above the roof line (for vertical terminations) 

Minimum 24” (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations 

C

B

H

E

G

A

D

F

L

K

J

I

NOTE: Measure clearances to the nearest edge of the exhaust hood. 

A

E

E

M

N

 

• 

Use the vinyl siding standoff when installing on an exterior with vinyl siding. 

• 

Vent termination must not be located where it will become plugged by snow or other material 

Содержание GreenSmart 564 GS

Страница 1: ...call gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualifie...

Страница 2: ...ation requirements for the 564 GS fireplace For operating and maintenance instructions refer to the 564 GS Owner s Manual part 100 01223 Listing Details This appliance was listed by SAI Global to AS 4...

Страница 3: ...e Considerations 21 Approved Vent 22 Vent Installation 22 Approved Vent Configurations 23 Restrictor Position 23 Exhaust Restrictor Adjustment 23 Intake Restrictor Adjustment 24 Diffuser Plate Adjustm...

Страница 4: ...gas NG or propane LP Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard Direct questions about the type of fuel used to your dealer Check the l...

Страница 5: ...he fiber logs become damaged replace with Travis Industries log set Do not throw this manual away This manual has important operating and maintenance instructions that you will need at a later time Al...

Страница 6: ...Input Per Hour 20 500 20 500 Maximum Megajoules MJ Input Per Hour 21 6 21 6 Heating capacity will vary with floor plan insulation and outside temperature Efficiency rating is a product thermal effici...

Страница 7: ...imum Framing Dimensions Drywall Top Vent Configuration Rear Vent Configuration See the section Gas Line Installation Side Wall See Optional Non Combustible Facing Drywall See Optional Non Combustible...

Страница 8: ...secure the standoff Bend the standoff in the numbered sequence shown above Remove the screw below the standoff b 1 2 3 c The standoffs are shipped in the flat position Make sure to follow the instruc...

Страница 9: ...e diffuser when changing the vent configuration Converting the Fireplace to Top Vent Configuration Remove the 4 screws securing the outer flue assembly Place the screws and assembly aside NOTE Use a m...

Страница 10: ...he rear facing exhaust port with the same screws Verify the gasket on the intake cover plate is in place then attach it to the rear of the fireplace using the screws removed earlier Verify the gasket...

Страница 11: ...r non combustible surface not on linoleum or carpet This heater may be placed in a bedroom Please be aware of the large amount of heat this appliance produces when determining a location Clearances Wh...

Страница 12: ...1 25mm to the sides 1 25mm below and 4 102mm above the vent to combustibles Included Firestop required Part 250 00747 Center of Rear Vent HINT place the fireplace so the center line is at least 5 127m...

Страница 13: ...e to a position to the left rear of the fireplace 36 1 2 927mm 33 1 2 851mm 16 1 2 419mm WARNING A cut out for the gas line may be required on the framing See the dimensions under Gas Line Connection...

Страница 14: ...r tab out 90 use a screwdriver if necessary Fireplace Drywall Framing Nailing Bracket TOP VIEW 1 2 13mm Drywall 5 8 0 625mm Drywall There are four nailing brackets on the front of the fireplace Follow...

Страница 15: ...lation uses the framing dimensions shown in the illustration below NOTE all clearances still apply 7 178mm Approximate varies due to vent installation 44 1 2 Min 1130mm Minimum 1 2 13mm Clearance NOTE...

Страница 16: ...Industries 4090709 100 01222_000 Corner Installations Top Vent Configuration A typical 45 installation uses the framing dimensions shown in the illustration below NOTE all clearances still apply 14 1...

Страница 17: ...ther for natural gas or for propane but not for both Check the sticker on the top of the gas control valve to make sure the correct fuel is used Gas Line Connection Installation must be performed by a...

Страница 18: ...er plate has a 7 8 0875mm diameter hole covered with a push plug in line with the gas inlet on the gas control valve By rotating the plate 180 the hole may be re located You may also secure the plate...

Страница 19: ...hut off prior to working on any electrical lines The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical...

Страница 20: ...to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Note When using a GreenSmart remote use the receiver for on off operation do not use a wall switch or...

Страница 21: ...s use the high wind termination if available from the vent manufacturer Vent Clearances The vent must maintain the required clearance to combustible materials to prevent a fire Do not fill air spaces...

Страница 22: ...for details Always use the high wind cap or high wind sconce cap part 58DVA HSCH or 46DVA HSCH Installation instructions for Simpson Dura Vent may be found at www duravent com 6 5 8 168mm Diameter Ven...

Страница 23: ...ptable vent configurations detail the correct vent restrictor positions Exhaust Restrictor Adjustment If the diffuser is required to be in position 2 you may wish to adjust the diffuser while the exha...

Страница 24: ...Travis Industries 4090709 100 01222_000 Intake Restrictor Adjustment Loosen the two screws holding the intake restrictor in place 1 4 Socket Slide the restrictor down to the lower position and tighten...

Страница 25: ...on 2 is flattened See the directions below to change the diffuser to position 2 Back Wall of Firebox Firebox Roof Remove the exhaust restrictor 1 4 Nutdriver Remove the diffuser 1 4 Nutdriver Secure t...

Страница 26: ...5 Elbow Termination See the charts below to determine maximum vent 3 feet 915mm 0 feet mm 0 feet mm 4 max 610mm Exhaust Restrictor 0 stock Intake Restrictor 1 stock Diffuser Position 1 stock Vent with...

Страница 27: ...et 1 5 m 10 feet 3 m 5 feet 1 5 m 10 feet 3 m 0 feet 15 feet 4 5 m 20 max 6 m 10 feet 3 m 15 feet 4 5 m 15 feet 4 5 m 20 max 6 m 10 feet 3 m 15 feet 4 5 m 22 max 6 7 m 22 max 6 7 m Exhaust Restrictor...

Страница 28: ...t 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 40 max 12m Exhaust Restrictor 6 Intake Restrictor 2 Diffuser Position 2 25 feet 7 5m 30 feet 9...

Страница 29: ...et 20 feet 6m 20 feet 6m 5 feet 1 5m 10 feet 3m 5 feet 1 5m 10 feet 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 21 max 6 4m 21 max 6 4m Exha...

Страница 30: ...m 10 feet 3m 5 feet 1 5m 10 feet 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 40 max 12m Exhaust Restrictor 6 Intake Restrictor 2 Diffuser Po...

Страница 31: ...with local installation codes and the requirements of the gas supplier G Minimum 48 1219mm clearance from any adjacent building H Minimum 84 2134mm clearance above any grade when adjacent to public wa...

Страница 32: ...ring the fireplace must be raised so the base of the unit is above the carpet surface or flooring material Floor Mounted Fireplaces Raised Fireplaces A hearth is not required when the fireplace is rai...

Страница 33: ...ce Tile or other non combustible facing may be placed on the front of the fireplace see Facing Overview on page 34 for further details Drywall Installation Drywall Installation Drywall may be installe...

Страница 34: ...up to this location 1 25mm above the base of the fireplace The fireplace may be raised to accommodate thicker hearth materials Masonry Line Hearth Line Tile Line Tile Line Masonry Line Tile Line Mason...

Страница 35: ...air Raised Fireplaces Facing is installed 1 maximum 25mm above the base of the fireplace Facing is installed to this edge of the fireplace FRONT VIEW Tile Line Tile Line Hearth Line Tile Line 27 3 4...

Страница 36: ...ce Note how the facing extends 1 25mm above the base of the fireplace 1 25mm Fireplace Support Floor Drywall Tile or other facing under 1 25mm thick Face Floor Max 1 25mm Hearth note how it extends un...

Страница 37: ...Drywall Fireplace Drywall Framing Nailing Bracket Masonry TOP VIEW Protruding Masonry Fireplace Drywall or cement board etc Framing NOTE The nailing brackets are not used for this type of installatio...

Страница 38: ...500674 The template helps locate and support the masonry as it being installed Masonry Line Hearth Line Drywall Floor Mounted Fireplaces or Raised Hearths Build the hearth 1 max 25mm above the base of...

Страница 39: ...The masonry extends 1 25mm above the base of the fireplace 1 25mm Fireplace Support Floor Floor Mounted Fireplace with Hearth SIDE OF FIREPLACE Drywall Masonry or other non combustible over 1 25mm thi...

Страница 40: ...3 4 0 75mm or less they may be placed directly to the side but not in front of the fireplace Non combustible mantel columns do not have a minimum clearance 38 1 2 978mm 12 305mm Maximum Non Combustibl...

Страница 41: ...2mm EXTERIOR WALLS When installed with a 2x4 51mm X 102mm exterior wall the termination may not fit flush against the exterior wall You may wish to place framing around the termination to fill the gap...

Страница 42: ...Section Firestop NOTE FOR 2 x 4 51mm X 102mm EXTERIOR WALLS When installed with a 2x4 51mm X 102mm exterior wall the termination may not fit flush against the exterior wall You may wish to place frami...

Страница 43: ...se a cloth or paper towel 4 Install the four AA batteries included in the owner s pack into battery holder see the illustration below The AA batteries act as a power backup in case the household AC po...

Страница 44: ...to use pliers to adjust the front air shutter Typically the front air shutter is fully closed left on NG fully open right on LP 10 Turn the flame adjust knob to its highest position the flames should...

Страница 45: ...s Open the four latches holding the glass frame in place start with the bottom follow the directions shown to the right a Lift the glass frame up and pull it forward to remove b Re Attaching the Glass...

Страница 46: ...ed 1 4 turn when it is disengaged Follow the directions below to re install the latch if it becomes loose Top of Firebox Hold the latch at an angle and insert it into the slot on the glass frame ancho...

Страница 47: ...llation for qualified installers only 47 Travis Industries 4090709 100 01222_000 Log Set Installation Log Set Overview When installed the logs should appear as shown below Rear Log Left Log Right Twig...

Страница 48: ...only Travis Industries 4090709 100 01222_000 Rear Log Installation Place the rear log on the grate and slide it all the way back until the log contacts the end brackets on the grate The rear log has...

Страница 49: ...ualified installers only 49 Travis Industries 4090709 100 01222_000 Right Log Installation Note how the right side of the log rests on the burner but does not cover any burner holes The right log has...

Страница 50: ...or qualified installers only Travis Industries 4090709 100 01222_000 Left Log Installation The left log has a groove that fits over the grate Note how the right side of the log rests on the burner but...

Страница 51: ...ion for qualified installers only 51 Travis Industries 4090709 100 01222_000 Left Twig Installation This hole fits over the pin on the rear log The left twig should be positioned so the front edge con...

Страница 52: ...lation for qualified installers only Travis Industries 4090709 100 01222_000 Right Twig Installation The right twig has two holes for the pins on the rear and right log When in place the right twig wi...

Страница 53: ...rs only 53 Travis Industries 4090709 100 01222_000 Ember Installation A bag of embers is provided to further enhance the firebox Place the embers on the firebox floor and on the burner Do not place em...

Страница 54: ...uctions Install the conversion kit prior to installing the gas line to ensure proper gas use 1 Remove the glass see page 43 Remove the logs and embers if installed page 47 2 Remove the burner see illu...

Страница 55: ...ce in so the orifice protrudes 15 16 24mm indicating full insertion d Look here for the orifice identification Apply thread sealant to the LP orifices prior to installation Use the chart below to iden...

Страница 56: ...rd the screws see a below holding the stock regulator in place see b below Remove the stock regulator and gasket see c below Place the LP regulator in place making sure the pre fitted gasket see c bel...

Страница 57: ...the fireplace to the correct configuration Remove the grate replace after fireback installation 1 4 Nutdriver Remove and discard the hearth plate Loosen this screw and slide the bracket up Place the...

Страница 58: ...need to press on the grill to get the tab over the bushing this prevents the grill from accidentally falling off Bend the tab outward on both sides This is the end stop for the lower grill it allows...

Страница 59: ...Optional Equipment for qualified installers only 59 Travis Industries 4090709 100 01222_000...

Страница 60: ...ontalTermination 42 Installation Options 6 Installation Overview 7 Intake Restrictor Adjustment 24 Listing Details 2 Log Set Installation 47 LP Conversion Instructions 54 Mantel Requirements 40 Minimu...

Отзывы: