Fireplace Insert Installation
(for qualified installers only)
© Travis Industries
100-01261
4110328
Hearth Requirements
•
Non-combustible hearth must extend 12" (300mm) in front of the insert and 4.625" (118mm) from
both sides of the insert
•
When installed over a timber floor:
Hearth must be a minimum of 75mm of non-
combustible masonry with 16mm of FC sheet
along with offcuts to provide air flow (see
illustration to the right).
NOTE
: if using the “Lopi Flush Wood Zero
Clearance Box” (
www.lopi.com.au
) see the
instructions included with the zero clearance
box for hearth requirements.
•
When installed over a cement floor:
Hearth must be non-combustible.
Face Dimensions
33”
23-1/4”
33-1/2”
23-1/4”
33-3/8”
51-1/2”
Radius
23-7/8”
2-7/8”
Avalon Victorian Lace
Fireplace Xtrordinair Arched
Lopi Wilmington
Figure 4
Drafting Performance
This appliance relies upon natural draft to operate. External forces, such as wind, barometric pressure,
topography, or factors of the home (negative pressure from exhaust fans, chimneys, air infiltration, etc.),
may adversely affect draft. Travis Industries can not be responsible for external forces leading to less
than optimal performance.