background image

® U.S. Registered Trademark
Copyright © American Standard Inc. 1999

INSTALLER'S GUIDE

XT300C Deluxe Programmable

Heat-Cool Thermostat

18-HD25D1-3

APPLICATION

The XT300C Deluxe Programmable Heat-Cool Thermostat provides electronic control of 24 Vac single-stage heating and
cooling systems. Refer to Table 1 for a general description of the thermostat. This thermostat is powered by the heating system
only. Refer to Wiring for information on wiring for cooling-only applications.

Table 1. Description of XT300C

RECYCLING NOTICE

If this thermostat is replacing a thermostat that contains
mercury in a sealed tube, do not place your old
thermostat in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Thermostat...

1. Read these instructions carefully. Failure to follow the

instructions can damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

Location

Install the thermostat about 5 ft (1.5m) above the floor in an
area with good air circulation at average temperature. See
Fig. 1. Avoid installing the thermostat where it can be affected
by the following:

Drafts, or dead spots behind doors and in corners.

Hot or cold air from ducts.

Radiant heat from sun or appliances.

Concealed pipes and chimneys.

Unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wallplate Installation

Position wallplate horizontally on the wall or on a 2 in. x 4 in.
wiring box.

1. Position and level the wallplate for appearance only (the

thermostat will function properly even when
not level).

Fig. 1. Typical location of thermostat.

5 FEET

[1.5 METERS]

YES

NO

NO

NO

M17106

69-1212-1

Model

System

Changeover

System  
Selection

Fan
Selection

Comments

XT300C Heat-Cool

Automatic

Heat-Off-Cool -

Auto

On-Auto

System and fan selections are done by
keyboard.

Содержание XT300C

Страница 1: ...heck the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Страница 2: ...inal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat WIRES THROUGH WALL WALL MOUNTING HOLES M15044 MOUNTING SCR...

Страница 3: ...E BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM...

Страница 4: ...crease To scroll the Installer Setup numbers backwards press Time To exit the Installer Setup press Run Program CAUTION Equipment Damage Hazard Can cause permanent equipment damage Electric heat syste...

Страница 5: ...eat mode Heating cycle rate 4 5 5 5 cph recommended 3 6 or 9 cph not recommended 3 6 or 9 3 3 cph 6 6 cph 9 9 cph Cooling cycle rate 9 3 3 3 cph recommended 2 or 5 cph not recommended 2 or 5 2 2 cph 5...

Страница 6: ...5 the compressor will be on during call for heat Minimum On Time Cool 33 10 10 minute minimum on time for compressor 0 thru 15 Minimum number of minutes 0 thru 15 the compressor will be on during call...

Страница 7: ...ogram System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy M12954 Daylight Time AM DST Tue Set Day Time M12955 Run Program Aut...

Страница 8: ...Refer to Table 5 for the directions and results of the specific tests Fig 13 Display of all the segments of the LCD NOTE Press Time to advance to the next test and Time to go back to the previous tes...

Страница 9: ...splays Copy 60 12 Copy test number displays System select models 60 3 System test number displays Fan select models 60 10 Fan test number displays Set Current Day Time 60 1 Set Current Day Time test n...

Страница 10: ...ot come on Thermostat is not being powered Check for 24 Vac between R and W terminals Check if the circuit breaker is tripped reset the circuit breaker Check if the system fuse is blown replace the fu...

Страница 11: ...utes for the system to respond Enter Installer Setup number 39 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool Cool setpoint is above room tem...

Страница 12: ...AMMABLE HEAT COOL THERMOSTAT 69 1212 1 Pub No 18 HD25D1 3 69 1212 1 T C Rev 3 99 American Standard Inc Troup Highway Tyler TX 75711 9010 Printed in U S A on recycled paper containing at least 10 post...