BAS-SVX17B-EN
7
Pre-Installation
Wire Length
Maximum recommended wire lengths for the sensor are given in
Table 1
:
Table 1.
Recommended wire lengths
Wire size
Maximum recommended wire length from unit
controller to sensor
AWG
mm
2
Meters
Feet
22
0.33
0–46
0–150
20
0.50
47–73
151–240
18
0.75
74–117
241–385
16
1.30
118–185
386–610
14
2.00
186–296
611–970
Note:
The total resistance of these low voltage wires must not exceed 2.5
Ω
/conductor. Any resistance greater than 2.5
Ω
may cause the control to malfunction due to an excessive voltage drop.