Trane X1379088401 Скачать руководство пользователя страница 21

BAS-SVX17B-EN

21

Operation

 

Scheduling for VAV Occupied Periods 

Cooling setpoint 

selected

12. Press 

 to select the cooling setpoint. The top arrow of the 

setpoint symbol and the cooling symbol flash. The current 
cooling setpoint appears (or dashes if nothing has been set).

13. Press 

 or 

 to change the cooling setpoint for the period 

you are scheduling.

Fan Auto

Fan On

14. Press 

 to select the fan setting. The fan setting appears and 

the currently selected fan setting flashes.

Note:

CV/HP only, and only if the programmable fan option is enabled.

15. Press   or 

 to select the fan setting for the period you are 

scheduling.

16.

To confirm your schedule settings, press 

 and hold for 2 

seconds, or wait 30 seconds. The home screen will appear.

Occupancy setting 

selected

1.

Follow steps 1—8 of the procedure described in 

“Scheduling,” 

p. 20

.

2. Press   or 

 to select the occupied setting.

Warm-up setpoint 

selected

3. Press 

 to select the warm-up setpoint. The bottom current 

period will flash. 

Note:

Only if the heat installed option is enabled.

4. Press 

 or 

 to change the setpoint.

Supply air heating 

setpoint selected

5. Press 

 to select the supply air heating setpoint. The bottom 

arrow of the setpoint symbol, the heating symbol, and the fan 
and arrow outlines all flash.

Note:

Only if the modulated heat option is enabled.

6. Press 

 or 

 to change the setpoint.

Supply air cooling 

setpoint selected

7. Press 

 to select the supply air cooling setpoint.The top 

arrow of the setpoint symbol, the cooling symbol, and the fan 
and arrow outlines all flash.

8. Press 

 or 

 to change the setpoint.

9.

To confirm your schedule settings, press 

 and hold for 2 

seconds, or wait 30 seconds. The home screen will appear.

Содержание X1379088401

Страница 1: ...g up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualif...

Страница 2: ...f Trane in the United States and other countries All trademarks referenced in this document are the trademarks of their respective owners Warnings Cautions and Notices Warnings cautions and notices ar...

Страница 3: ...Procedures 18 Changing the System Setting 18 Changing the Fan Setting CV HP Configuration only 19 Setting the Time Clock and the Day 19 Scheduling 20 Scheduling for VAV Occupied Periods 21 Temporary...

Страница 4: ...ate with constant volume CV units heat pump HP units and variable air volume VAV units System modes CV Heat Cool Auto Off HP Emergency Heat Heat Cool Auto Off VAV Auto Off A cooling setpoint range occ...

Страница 5: ...ustration provides specific dimension details The dimensions are the same for all models 2 9 in 73 5 cm 1 08 in 27 5 mm 4 68 in 118 9 mm 1 34 in 34 14 mm 0 58 in 14 76 mm 0 31 in 8 mm 0 12 in 3 mm TYP...

Страница 6: ...Requirements It is recommended that you mount the back plate a maximum distance of 54 inches above the floor If a parallel approach by a person in a wheelchair is required reduce the maximum height to...

Страница 7: ...ommended wire length from unit controller to sensor AWG mm2 Meters Feet 22 0 33 0 46 0 150 20 0 50 47 73 151 240 18 0 75 74 117 241 385 16 1 30 118 185 386 610 14 2 00 186 296 611 970 Note The total r...

Страница 8: ...kout tagout procedures to ensure the power cannot be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury NOTICE Equipment damage Applying exces...

Страница 9: ...e wires are connected to the appropriate terminals at the unit controller 2 Connect the wires to the terminal block included in the hardware package with the sensor See Table 2 p 10 to determine where...

Страница 10: ...1TB8 11 SERVICE STATUS UCM INPUT 10 10 10 10 10 10 10 11 10 10 1TB8 10 SYSTEM STATUS ON OFF INPUT 9 9 9 9 9 9 9 10 9 9 1TB8 9 COOL STATUS UCM INPUT 8 8 8 8 8 8 8 9 8 8 1TB8 8 HEAT STATUS UCM INPUT 7 7...

Страница 11: ...Cover To replace the cover 1 Hook the cover over the top of the back plate Apply light pressure to the bottom of the cover until it snaps in place 2 Secure the cover by installing the security screw...

Страница 12: ...the sensor is new the configuration screen appears see Figure 3B If no buttons are pressed for 90 seconds the display returns to the home screen in constant volume CV configuration The light dims Fig...

Страница 13: ...guration button for 2 seconds Figure 4 The configuration screen appears see Figure 3 p 12 2 Use the keypad on the sensor cover to select the system and functional options See Table 3 p 14 for sensors...

Страница 14: ...an setting 7 Computed recovery 0 Disabled 1 Enabled 0 If enabled this option offsets the setpoint temperature and starts the system before the scheduled occupied period to efficiently reach the occupi...

Страница 15: ...d 1 Set to 0 for 3 25 ton Voyager units built before January 1 1996 that have the original UCP 18 Default cooling setpoint 45 98 F 7 2 36 7 C 74 If no setpoint has been programmed or the program is lo...

Страница 16: ...Disabled 1 Enabled 0 If enabled this setting allows the system to automatically switch between supply air cooling and constant volume heating operation during an occupied period 8 Programmable days p...

Страница 17: ...int 19 Default supply air heat 60 100 F 15 6 37 8 C 100 If no setpoint has been programmed or the program is lost the value that is set becomes the operation setpoint 20 Default warm up 50 90 F 10 32...

Страница 18: ...e sensor showing an example of the home screen on the display System in cooling mode 1 From the home screen select the system setting by pressing twice 2 Press or to select the desired system setting...

Страница 19: ...to temporary override set up Follow the procedure in Temporary Override Set up CV HP only p 22 to override the fan setting 3 To confirm your setting press or wait 10 seconds The home screen will appe...

Страница 20: ...o times Days of week selected 2 Press or to select the days of the week All days of the week appear and Monday flashes 3 Press or to select the day you want to schedule Morning Day Evening Night Perio...

Страница 21: ...cupancy setting selected 1 Follow steps 1 8 of the procedure described in Scheduling p 20 2 Press or to select the occupied setting Warm up setpoint selected 3 Press to select the warm up setpoint The...

Страница 22: ...ess or to increase or decrease the heating or cooling setpoint The fan setting flashes when selected 5 To override the fan setting press if starting from the heating setpoint press twice Press or to c...

Страница 23: ...VAV units Occupied Warm up setpoint 68 F 20 C Supply air heating setpoint 100 F 37 8 C Supply air cooling setpoint 55 F 12 8 C Locked symbol 1 Begin at the home screen 2 Press and simultaneously for 4...

Страница 24: ...setup for each period of the day in order before you move on to the next day For instance refer to Figure 7 below once the schedule is opened you will start with Monday and the Morning period 1 Set th...

Страница 25: ...ng Auto On Day Auto On Evening Auto On Night Auto On Wednesday Morning Auto On Day Auto On Evening Auto On Night Auto On Thursday Morning Auto On Day Auto On Evening Auto On Night Auto On Friday Morni...

Страница 26: ...y Period Start time Occupancy Warm up or unoccupied heating setpoint Supply air or unoccupied cooling setpoint Supply air heat setpoint modulating heat only Monday Morning Day Evening Night Tuesday Mo...

Страница 27: ...service appears for 2 seconds The home screen appears and the light dims Check Filter Timer Check filter interval is a configuration option that allows you to set a timer that is adjustable in 1 day...

Страница 28: ...en selected for option 13 CV HP configurations Verify that option value 1 has been selected for option 12 VAV configurations Keypad does not respond Check to see if the lock symbol is on To unlock the...

Страница 29: ...C 4 0 F 2 2 C when outside this range Resolution 0 225 F 0 2 C over a range of 50 to 90 F 10 to 32 C 0 40 F 0 125 C when outside this range Setpoint functional range 43 to 98 F 6 1 to 36 6 C Input vo...

Страница 30: ...t Flicker EN61000 3 3 EN61000 3 3 1995 A1 2001 A2 2006 Electromagnetic Immunity for Industrial EN61326 1 2006 by Council Directive 89 336 EEC EN61000 4 2 2006 4 0 kV by contact EN61000 4 2 2006 8 0 kV...

Страница 31: ...BAS SVX17B EN 31 Declaration of CE Conformity Notes...

Страница 32: ...Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and pro...

Отзывы: