BAS-SVX17B-EN
17
Configuration
14
Default temporary
override timer setting
1, 2, 3, 4, 5 (hours)
3
Sets the default temporary override time in hours.
15
Zone temperature
calibration
Displays current temperature
reading with any offsets:
• 1 = –9.9ºF (–5.5ºC)
• 100 = 0.0ºF (0.0ºC)
• 199 = 9.9ºF (9.9ºC)
100
(0
offset)
Allows for field calibration in 0.1ºF (0.6ºC) increments of
either the internal sensor on the sensor, or the remote
sensor if used.
Important:
Apply power to the sensor for 60 minutes before
calibrating.
16
Default cooling setpoint
45–98ºF (7.2–36.7ºC)
74
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
17
Default heating setpoint 43–96ºF (6.1–35.6ºC)
68
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
18
Default supply air cool
40–80ºF (4.4–26.7ºC)
55
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
19
Default supply air heat
60–100ºF (15.6–37.8ºC)
100
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
20
Default warm-up
50–90ºF (10–32.2º)
68
If no setpoint has been programmed or the program is
lost, the value that is set becomes the operation setpoint.
21
Minimum cooling
setpoint
45–98ºF (7.2–36.7ºC)
45
Sets the minimum programmable cooling temperature
setpoint.
22
Maximum heating
setpoint
43–96ºF (6.1–35.6ºC)
96
Sets the maximum programmable heating temperature
setpoint.
23
Minimum supply air cool 40–80ºF (4.4–26.7ºC)
40
Sets the minimum programmable cooling temperature
setpoint.
24
Maximum supply air
heat
60–160ºF (15.6–71.1ºC)
160
Sets the maximum programmable heating temperature
setpoint.
25
Maximum warm-up
time
50–90ºF (10–32.2º)
90
Sets the maximum programmable heating temperature
setpoint.
26
Minimum setpoint
deadband
0 = 2ºF (1ºC)
1 = 4ºF (2ºC)
2 = 5ºF (3ºC)
3 = 7ºF (4ºC)
4 = 8ºF (5ºC)
5 = 10ºF (6ºC)
0
Sets the minimum difference between the heating and
cooling setpoints.
Table 4.
Configuration options for sensors used with
variable-air-volume (VAV)
units (continued)
Option
number
Function
Option Value
Default Description