Electrical Data

14

Rating based on 85/95

0

F (29.5/35

0

C) EWT/LWT and 80/67

0

F (27/19

0

C) on coil conditions at nominal airflows.

Note: MCA - Minimum circuit capacity

Largest compressor RLA x 1.25 + sum of remaining compressors RLA and fan motor FLA.
(However, if fan motor FLA is largest, use 1.25 x FLA + remaining compressor RLAs)

Supply voltage must be within 6% of equipment rated voltage.

LRA - Lock rotor amp.
RLA - Rated load amp at 80 

o

F / 67 

o

C return air, 85 

o

F EWT, 95 

o

F LWT and rated airflow.  (for compressors)

FLA - Full Load amp. (for Fan Motor)
Rated at 400V, 50 Hz

High Pressure  Switch
Low Pressure Switch
Pressure relief valve

: cut-out / cut-in
: cut-out / cut-in
: pressure setting (SHELL & TUBE CDS ONLY)

310 / 240 psig
27 /46 psig
350 psig

Table 2

 

Table 1 - WCVS-CA, Electrical Data (@ARI)

Model

Power Supply

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

Over-Size Fan Mtr--->

380-415V/3Ph/50Hz

380-415V/3Ph/50Hz

Compr.1

Compr.2

Compr.3

Compr.4

Fan Motor @ 415V

WCVS 270

WCVS 330

WCVS 400

WCVS 470

WCVS 530

WCVS 600

WCVS 660

WCVS 730

WCVS 800

WCVS 900

WCVS 12H

RLA

(ARI)

LRA RLA

(ARI)

LRA RLA

(ARI)

LRA RLA

(ARI)

LRA

kW

FLA LRA Qty

UNIT

MCA

Max Fuse

Size & MCB

14.4

17.8

21.3

17.8

21.3

17.8

17.8

21.3

21.3

35

35

130

135

175

135

175

135

135

175

175

270

270

14.4

17.8

21.3

17.8

21.3

17.8

17.8

21.3

21.3

35

35

130

135

175

135

175

135

135

175

175

270

270

14.4

14.4

14.4

17.8

17.8

21.3

35

35

130

130

130

135

135

175

270

270

14.4

17.8

17.8

21.3

35

130

135

135

175

270

3.7

5.5

3.7

7.5

5.5

11

5.5

11

5.5

11

7.5

15

7.5

15

11

15

11

15

15

18.5

22

7.32

11.1

7.32
13.9

11.1

19.7

11.1

19.7

11.1

19.7
13.9

27

13.9
27.0
19.7
27.0
19.7
27.0
27.0
33.2
40.5

52

75

52

100

75

155

75

155

75

155

101

188

101

188

140

188

140

188

188

207

260

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

40
43
48
54
59
68
65
76
73
83
83
98
90

105
103

112
110
119

141
147
191

55
58
66
72
80
90
83

132

94

104
101
172
107
179
125
186
132
193
176
182
224

Содержание WCVS 12H

Страница 1: ...ion Operation Maintenance Self Contained Water Cooled Air Conditioners WCVS SVX01A EN Aug 2012 Models WCVS 270 WCVS 330 WCVS 400 WCVS 470 WCVS 530 WCVS 600 WCVS 660 WCVS 730 WCVS 800 WCVS 900 WCVS 12H...

Страница 2: ......

Страница 3: ...he shipment Take photos of the damage material if possible Notify the carrier immediately by phone and registered mail Notify the local Trane Sales Office Concealed damage must be reported within 15 d...

Страница 4: ...al Specification General Information Installation Operation Start up Coil Condenser Cleaning Trouble Analysis Guide Electrical Data Electrical Wiring Unit Dimensions Wiring Diagram Schematic Wiring Di...

Страница 5: ...ory Minor Design Sequence C Double Wall PU Panels Standard on all models Introduction of FUJI Starter Factory Installed Options X None Installed Motor kW Refrigerent Type A R22 B R407c Future Use Serv...

Страница 6: ...TRANE General Specification WCVS 270 12H 2...

Страница 7: ...TRANE 3...

Страница 8: ...e unit weights may be unevenly distributed Unit weights are provided in the general specification WARNING To prevent injury or death and unit damage observe handling cautions and procedures given in F...

Страница 9: ...all a condenser main and standby water pump cooling tower pressure gauges strainers and all components for waterside piping All field installed piping must conform to applicable local codes Recommende...

Страница 10: ...M Water Pressure Drop Ft H20 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 Water Pressure Drop Psi 96 96 96 Condenser 35 T Pressure Drop Vs GPM 2 31 3 31 4 31 5 31 6 31 7 31 8 31 9 31 10 31 11 31 12 31 13 3...

Страница 11: ...60 70 80 90 100 110 120 130 140 150 160 170 180 GPM Water Pressure Drop Ft H20 0 1 0 6 1 1 1 6 2 1 2 6 3 1 3 6 4 1 4 6 5 1 5 6 Water Pressure Drop PSIG 96 96 96 96 Condenser Pressure Drop Vs GPM WCVS...

Страница 12: ...n the Zone Sensor Thumbwheel to desired temperature setting Operation Unit start stop controls are provided on the facia of the unit mounted control box Unit is operated by pressing the START botton w...

Страница 13: ...hould be checked and adjusted at least twice during the first few days of new belt operation Weekly maintenance Six month interval Required Unit Service Envelope The following summarizes the envelope...

Страница 14: ...ype NFPA 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA 90B or as perapplicable local codes Make duct connections to the unit with a flexible material such as heavy canvas I...

Страница 15: ...TRANE Operation Start Up 11 Figure 4 Fan Duct Layout Comment Figure 5 A A A A R 6o minimum A A...

Страница 16: ...d be provided or approved by the chemical supply house Caution Do not clean the refrigerant coil with hot water or steam The use of hot water or steam as a refrigerant coil cleaning agent will cause h...

Страница 17: ...enser If condenser in changed Air in system Moisture in system Bad compressor Service valve closed if any Recover Re evacuate Re charge Recover Re evacuate Re charge or add refring Remove restriction...

Страница 18: ...380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz Over Size Fan Mtr 380 415V 3Ph 50Hz 380 415V 3Ph 50Hz Compr 1 Compr 2 Com...

Страница 19: ...WIRING TO THE COMPRESSOR TERMINALS ARE CONNECTED IN THE CORRECT PHASE SEQUENCES PLEASE REFER DIAGRAM ON FIGURE 6 Figure 6 Scroll Compressors Terminal Wiring LINE 1 2 TO BE CONNECTED IN SERIES WITH CON...

Страница 20: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 270 330 16...

Страница 21: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 400 470 17...

Страница 22: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 530 600 660 18...

Страница 23: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 730 800 19...

Страница 24: ...TRANE Unit Dimensions Water Cooled Vertical System WCVS 900 12H 20...

Страница 25: ...TRANE Wiring Diagram With Starter WCVS 270 330 21...

Страница 26: ...TRANE Schematic Wiring Diagram With Starter WCVS 400 22...

Страница 27: ...TRANE Schematic Wiring Diagram With Starter WCVS 470 530 23...

Страница 28: ...TRANE Schematic Wiring Diagram With Starter WCVS 600 660 730 800 24...

Страница 29: ...TRANE Schematic Wiring Diagram With Starter WCVS 900 25...

Страница 30: ...TRANE Schematic Wiring Diagram With Starter WCVS 12H 26...

Страница 31: ......

Страница 32: ...t office WCVS SVX01A EN August 2012 WCVS SVX01A EN February 2009 MALAYSIA R Trane has a policy of continuous product and product data improvement and reserves the right to change design and specificat...

Отзывы: