30
RT-SVX34R-EN
Table 11.
Electrical service sizing data — 275–350 units – 50Hz
Model
Elec.
Specs
Comp. Std Eff
Comp. High Eff,
eStage
Fan Motors
Supply
Condenser
Exhaust
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
HP
(kW)
FLA
No
HP
(kW)
FLA
(Ea.)
50% 100%
HP
(kW)
FLA
(Ea.)
No.
TC/TE/
YC*275
380/415/
50/3
1/10,
1/11
21.0/
23.0
147/
158
1/6, 2/
9
14.1,
16.8
98, 142
7.5
(5.6),
10
(6.8)
12.1/
11.5,
15.2/
14.6
3
0.75
(0.56)
4.4
1
2
0.75
(0.56)
1.7
TC/TE/
YC*305
380-415/
50/3
0.1818
23
158
1/6, 2/
10
14.1,
18.6
98, 142
7.5
(5.6),
10
(6.8)
12.1/
11.5,
15.2/
14.6
3
0.75
(0.56)
4.4
1
2
0.75
(0.56)
1.7
TC/TE/
YC*350
380-415/
50/3
1/11,
1/12
23.0/
27.5
158/
197
1/6, 2/
11
14.1,
19.2
98, 147
7.5
(5.6),
10
(6.8),
15
(10.5)
12.1/
11.5,
15.2/
14.6,
22.0/
23.0
3
0.75
(0.56)
4.4
1
2
0.75
(0.56)
1.7
Notes:
1
.
All customer wiring and devices must be installed in accordance with local and national electrical codes.
2
.
Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
3
.
100% Power Exhaust is with or without Statitrac™.
4
.
All condenser fan motors are single phase.
Table 12.
Electrical service sizing data — 400–500 – 50Hz
Model
Elec.
Specs
Comp. Std Eff VAV
Only
Comp. Std Eff CV &
High Eff eStage
Fan Motors
Supply
Condenser
Exhaust
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
No/
Ton
RLA
(Ea.)
LRA
(Ea.)
HP
(kW)
FLA
No
HP
(kW)
FLA
(Ea.)
50% 100%
HP
(kW)
FLA
(Ea.)
No.
TC/TE/
YC*400
380-415/
50/3
1/11,
1/17
23.0/
34.0
158/
215
1/8, 2/
13
14.1,
23.0
98, 158
10
(6.8),
15
(10.5)
15.2/
14.6,
22.0/
23.0
4
0.75
(0.56)
4.4
1
2
1.0
(0.75)
2.5
TC/TE/
YC*500
380-415/
50/3
2/11,
1/12
23.0/
27.5
158/
197
1/10,
2/15
18.6,
27.5
142,
155
10
(6.8),
15
(10.5),
20
(12.8)
15.2/
14.6,
22.0/
23.0,
28.0/
28.0
4
0.75
(0.56)
4.4
1
2
1.0
(0.75)
2.5
Notes:
1
.
All customer wiring and devices must be installed in accordance with local and national electrical codes.
2
.
Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
3
.
100% Power Exhaust is with or without Statitrac™.
4
.
All condenser fan motors are single phase.