128
RT-SVX34R-EN
Table 72.
Supply fan VFD programming parameters (continued)
Menu
ID
Name
FC
Unit
Analog In/Out
6-14
Terminal 53 Low Ref./Feedb.
Value
35
6-15
Terminal 53 High Ref./Feedb.
Value
60
Special Function
14-01
Switching Frequency
8.0 kHz (drive dependant, set to
5kHz if 8kHz not available)
14-11 (TR200 only)
Mains Voltage at Mains Fault
391V for 460V 60Hz unit, leave
at default otherwise
14-12
Function at Mains Imbalance
Derate
14-20
Reset Mode
Automatic reset x 5
14–27
Action at Inverter Fault
Warning
14-50
RFI Filter
Off
14-60 (TR200 only)
Function at Over
Temperature
Derate
14-61 (TR200 only)
Function at Inverter Overload
Derate
Note:
For 50Hz units parameters 0-06 Grid Type (TR150s only) and 1-23 Motor Freq will need to be set accordingly.