Electrical
Data

Electrical Service Sizing

To correctly size electrical service
wiring for your unit, find the
appropriate calculations listed below.
Each type of unit has its own set of
calculations for MCA (Minimum Circuit
Ampacity), MOP (Maximum
Overcurrent Protection), and RDE
(Recommended Dual Element fuse
size). Read the load definitions that
follow and then find the appropriate
set of calculations based on your unit
type.

Set 1 is for cooling only and cooling
with gas heat units, and set 2 is for
cooling with electric heat units.

Load Definitions: (To determine load
values, see the Electrical Service Sizing
Data Tables.)

LOAD1 = CURRENT OF THE LARGEST
MOTOR (COMPRESSOR OR FAN
MOTOR)

LOAD2 = SUM OF THE CURRENTS OF
ALL REMAINING MOTORS

LOAD3 = CURRENT OF ELECTRIC
HEATERS

LOAD4 = ANY OTHER LOAD RATED
AT 1 AMP OR MORE

Set 1. Cooling Only Rooftop Units and
Cooling with Gas Heat Rooftop Units

MCA = (1.25 x LOAD1) + LOAD2 +
LOAD4

MOP = (2.25 x LOAD1) + LOAD2 +
LOAD4

Select a fuse rating equal to the MOP
value. If the MOP value does not equal
a standard fuse size as listed in NEC
240-6, select the next lower standard
fuse rating. NOTE: If selected MOP is
less than the MCA, then reselect the
lowest standard maximum fuse size
which is equal to or larger than the
MCA, provided the reselected fuse size
does not exceed 800 amps.

RDE = (1.5 x LOAD1) + LOAD2 +
LOAD4

Select a fuse rating equal to the RDE
value. If the RDE value does not equal
a standard fuse size as listed in NEC
240-6, select the next higher standard
fuse rating. NOTE: If the selected RDE
is greater than the selected MOP value,

then reselect the RDE value to equal the
MOP value.

(Keep in mind when determining LOADS
that crankcase heaters are disabled in the
cooling mode).

DSS = 1.15 x (LOAD1 + LOAD2 + LOAD4)

Select a disconnect switch size equal to
or larger than the DSS value calculated.

Set 2. Rooftop units with Electric Heat

To arrive at the correct MCA, MOP, and
RDE values for these units, you must
perform two sets of calculations. First
calculate the MCA, MOP, and RDE values
as if the unit was in cooling mode (use
the equations given in Set 1). Then
calculate the MCA, MOP, and RDE values
as if the unit was in the heating mode as
follows.

(Keep in mind when determining LOADS
that the compressors and condenser fans
don’t run while the unit is in the heating
mode and crankcase heaters are disabled
in the cooling mode.)

For units using heaters less than 50 kw.

MCA = 1.25 x (LOAD1 + LOAD2 +
LOAD4) + (1.25 x LOAD3)

For units using heaters equal to or
greater than 50 kw.

MCA = 1.25 x (LOAD1 + LOAD2 +
LOAD4) + LOAD3

The nameplate MCA value will be the
larger of the cooling mode MCA value or
the heating mode MCA value calculated
above.

MOP = (2.25 x LOAD1) + LOAD2 +
LOAD3 + LOAD4

The selection MOP value will be the larger
of the cooling mode MOP value or the
heating mode MOP value calculated
above.

Select a fuse rating equal to the MOP
value. If the MOP value does not equal a
standard fuse size as listed in NEC 240-6,
select the next lower standard fuse
rating. NOTE: If selected MOP is less
than the MCA, then reselect the lowest
standard maximum fuse size which is
equal to or larger than the MCA,
provided the reselected fuse size does
not exceed 800 amps.

RDE = (1.5 x LOAD1) + LOAD2 + LOAD3
+ LOAD4

The selection RDE value will be the
larger of the cooling mode RDE value or
the heating mode RDE value calculated
above.

Select a fuse rating equal to the RDE
value. If the RDE value does not equal a
standard fuse size as listed in NEC 240-6,
select the next higher standard fuse
rating. NOTE: If the selected RDE is
greater than the selected MOP value,
then reselect the RDE value to equal the
MOP value.

DSS = 1.15 x (LOAD1 + LOAD2 + LOAD3
+ LOAD4)

NOTE: Keep in mind when determining
LOADS that the compressors and
condenser fans don’t run while the unit
is in the heating mode.

The selection DSS value will be the
larger of the cooling mode DSS or the
heating mode DSS calculated above.

Select a disconnect switch size equal to
or larger than the DSS value calculated.

Table ED-1 — Electrical Service Sizing Data — Electric Heat Module  (Electric Heat  Only)

Models: TED/TEH 330 thru 600

Electric Heat FLA

Nominal

Nominal

Unit Size

Unit

KW Heater

(Tons)

Voltage

36

54

72

90

108

FLA

FLA

FLA

FLA

FLA

27½

208

74.9

112.4

30.0

230

86.6

129.9

35.0

460

43.3

65.0

86.6

108.3

575

52.0

69.3

86.6

40.0

208

112.4

50.0

230

129.9

460

65.0

86.6

108.3

129.9

575

52.0

69.3

86.6

103.9

Notes:
1. All FLA in this table are based on heater operating at 208, 240, 480, and 600 volts.

Содержание Voyager 23 to 42 Ton

Страница 1: ...Packaged Rooftop Air Conditioners 27 to 50T on 60 Hz 23 to 42T on 81 148 kW 50 Hz Voyager Commercial with ReliaT el Controls RT PRC007 EN November 2006...

Страница 2: ...flexibility TheVoyager Commercial line offers 27 to 50 ton 60 Hz and 23 to 42 ton 50 Hz models Both 50 and 60 Hz models come in a choice of five sizes to meet the changing demands of the commercial r...

Страница 3: ...d Benefits Application Considerations Selection Procedure Model Number Description General Data Performance Data Performance Adjustment Factors Controls Electric Power Dimension andWeights Mechanical...

Страница 4: ...ef High Efficiency 2 Throwaway Filters High Efficiency 4 Throwaway Filters High Efficiency supply fan motors High Efficiency condenser coil Manual fresh air damper Economizer with dry bulb control Eco...

Страница 5: ...3 D Scroll compressor is that slugging will not cause failure In a reciprocating compressor however the liquid or dirt can cause serious damage Low Torque Variation The 3 D Scroll compressor has a ver...

Страница 6: ...nections to the unit and the zone sensors is as easy as 1 1 2 2 and 3 3 This simplified system makes it easier for the installer to wire ReliaTel MakesTesting Easy ReliaTel requires no special tools t...

Страница 7: ...ion on LonMark visit www lonmark org or Echelon www echelon com Variable Frequency Drives VFD Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation VF...

Страница 8: ...exceed all California seasonal efficiency requirements They also perform better than required to meet the California NOx emission requirements High Efficiency Condenser Coil Increased capacity and ene...

Страница 9: ...d for high static motor conversion is minimized and saves the time normally spent changing to high static oversized motors Single Point Power A single electrical connection powers the unit Trane facto...

Страница 10: ...f may be used to provide relief for single story buildings with no return ductwork and exhaust requirements less than 25 percent Altitude Corrections The rooftop performance tables and curves of this...

Страница 11: ...itude Corrections The rooftop performance tables and curves of this catalog are based on standard air 075 lb ft 034 kg cm If the rooftop airflow requirements are at other than standard conditions sea...

Страница 12: ...cities The satisfactory distribution of air throughout the system requires that there be an unrestricted and uniform airflow from the rooftop discharge duct This discharge section should be straight f...

Страница 13: ...12 000 total peak supply cfm is 30 0 tons Thus a nominal 30 ton unit is selected Step 2 Having selected a nominal 30 ton unit the supply fan and exhaust fan motor bhp must be determined Supply Air Fan...

Страница 14: ...x 12 000 cfm 1 6 F Mixed air temperature entering heat module 64 8 1 6 66 4 F Total winter heating load peak heating ventilation load total fan motor heat 225 87 2 20 6 291 6 MBh Electric Heating Syst...

Страница 15: ...Pa Economizer Table PD 27 07 inches 17 Pa Unit total static pressure 1 50 inches 374 Pa Using total cfm of 10 000 4720 L s and total static pressure of 1 50 inches 38 mm enterTable PD 25 Table PD 25 s...

Страница 16: ...7 3 F for 10 000 cfm through heating module Unit supply temperature design heating conditions mixed air temperature air temperature rise 66 7 37 3 104 0 F Air Delivery Procedure Supply air fan bhp and...

Страница 17: ...d Low Leak Fresh Air Damper G D Option and Low Leak Fresh Air Damper H E Option and Low Leak Fresh Air Damper 5 The service digit for each model number contains 31 digits all 31 digits must be referen...

Страница 18: ...rowaway Filters Digit 13 Supply Fan Motor HP 1 7 5 Hp Std Eff 5 6 kW 2 10 Hp Std Eff 7 5 kW 3 15 Hp Std Eff 11 2 kW 4 20 Hp Std Eff 14 9 kW Digit 14 SupplyAir Fan Drive Selections See Note 3 A 458 H 4...

Страница 19: ...FC No Used 1 1 Diameter Width in 22 38 22 00 22 38 22 00 DriveType No Speeds Belt 1 Belt 1 No Motors HP 1 7 50 10 00 1 7 50 10 00 Motor RPM 1760 1760 Motor Frame Size 213 215T 213 215T Exhaust FanType...

Страница 20: ...FC No Used 1 1 Diameter Width in 22 38 22 00 25 00 25 00 DriveType No Speeds Belt 1 Belt 1 No Motors HP 1 7 50 10 00 15 00 1 10 00 15 00 Motor RPM 1760 1760 Motor Frame Size 213 215 254T 215 254T Exha...

Страница 21: ...ct 2 2 Motor HP RPM 1 0 1075 Motor Frame Size 48 Filters Type Furnished Throwaway No Recommended Size in 6 17 16 x 20 x 2 Refrigerant Charge Std Hi Eff Cond Coil Lbs of R 22 4 Std 30 7 54 3 per circui...

Страница 22: ...ce Area sq ft sq m 31 7 2 9 31 7 2 9 Rows Fins Per Foot 2 180 2 180 Refrigerant Control TXV TXV PVC Drain Connect No Size in mm 1 1 25 1 32 1 1 25 1 32 Outdoor FanT ype Propeller Propeller No Used 3 3...

Страница 23: ...ws Fins Per Foot 2 180 3 180 Refrigerant Control TXV TXV PVC Drain Connect No Size in mm 1 1 25 1 32 1 1 25 1 32 Outdoor FanT ype Propeller Propeller No Used 3 4 Diameter in mm 28 0 711 28 0 711 Drive...

Страница 24: ...200 12 400 No Motors rpm 4 940 Motor hp kW 0 75 0 56 Indoor FanT ype No Used FC 1 Diameter in mm 25 0 635 Width in mm 25 0 635 DriveType Belt No Speeds No Motors 1 1 Motor hp 10 0 7 5 kW Motor rpm Fra...

Страница 25: ...4500 4501To 5500 5501To 6500 6501To 7500 Sea LevelTo 609 6 609 9To 762 0 762 3To 1066 8 1067 1To 1674 4 1371 9To 1675 4 1676 7To 1981 2 1981 5To 2286 0 Capacity Multiplier 1 00 92 88 84 80 76 72 Note...

Страница 26: ...s 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity AmbientTemperature Deg...

Страница 27: ...3 464 390 425 425 425 425 442 381 406 406 406 406 419 371 Notes 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gros...

Страница 28: ...633 386 696 252 548 491 602 371 663 239 520 476 570 356 629 224 491 460 538 340 18000 80 591 591 636 482 698 355 566 566 606 467 666 342 541 541 575 451 632 327 514 514 543 436 85 626 626 644 583 699...

Страница 29: ...ot considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity Table PD 5A 30 Ton Gross Cooling Capacities Mbh High Efficiency 3 R...

Страница 30: ...414 429 377 Notes 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity Table...

Страница 31: ...2 612 61 1 61 1 651 518 75 589 516 648 394 714 259 561 501 617 380 681 245 533 485 585 365 646 230 504 470 553 350 18000 80 604 604 651 491 716 364 579 579 621 476 683 350 553 553 590 461 649 335 527...

Страница 32: ...600 volts HeatInputMBH HeatingOutputMBH T ons Unit Model No See Note 1 See Note 1 AirTemp Rise F YCD YCH330 L 27 35 YCD YCH360 L 350 000 250 000 283 500 202 500 10 40 YCD YCH420 L YCD YCH330 H 27 35 Y...

Страница 33: ...13500 445 4 39 479 4 92 526 5 73 569 6 53 604 7 26 638 7 98 673 8 82 705 9 68 733 10 38 14000 459 4 85 490 5 39 535 6 19 579 7 04 614 7 81 647 8 56 680 9 35 713 10 26 742 11 09 14500 473 5 35 503 5 90...

Страница 34: ...726 16 78 751 17 77 774 18 81 19000 690 16 29 71 1 17 27 734 18 29 758 19 34 782 20 41 20000 701 17 83 724 18 91 745 19 94 765 20 99 788 22 12 Static Pressure in wg 1 Table PD 13 Supply Fan Performan...

Страница 35: ...450 RPM 400 RPM 350 RPM 300 RPM Volumetric Airflow Rate CFM Supply Fan Performance 40 and 50 Ton Static Presure InWC 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 0 0 0 5...

Страница 36: ...0 12 0 07 13000 0 21 0 16 0 14 0 15 0 2 0 25 0 15 0 26 0 23 0 14 0 09 10500 0 14 0 11 0 09 0 1 0 22 0 27 0 11 0 18 0 16 0 09 0 06 11500 0 17 0 13 0 11 0 12 0 25 0 31 0 13 0 21 0 19 0 11 0 07 35 12500...

Страница 37: ...RPM No 550 A 600 B 27 T 650 C 700 700 D 750 750 E 550 A 600 B 30T 650 C 700 700 D 750 750 E 600 B 650 650 C 35T 700 700 D 790 790 F 800 800 G 500 500 H 525 525 J 575 575 K 40T 625 625 L 675 675 M 725...

Страница 38: ...5 0 255 0 120 9500 0 320 0 210 0 070 10000 0 255 0 165 0 020 10500 0 190 0 125 11000 0 125 0 060 11500 0 065 0 000 12000 0 005 Notes 1 Performance in table is with both motors operating 2 High speed b...

Страница 39: ...ringWet BulbTemperature C DB 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 72 4...

Страница 40: ...Wet BulbTemperature C DB 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 79 1 62...

Страница 41: ...TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 93 2 76 2 103 2 59 8 114 0 41 3 89 1 73 9 98 5 57 7 108 7 39 0 84 4 71 5 93 5 55 4 103 2 36 6 79 7 68 9 88...

Страница 42: ...SHC TGC SHC TGC SHC 23 9 114 0 90 0 126 9 70 9 140 7 50 1 108 4 86 7 120 7 67 7 133 9 46 9 102 6 83 2 114 3 64 5 126 9 43 7 96 1 79 7 107 3 61 0 119 3 40 4 4720 26 7 115 5 106 1 127 2 86 5 141 0 66 5...

Страница 43: ...oss and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 TGC Total gross capacity 3 SHC Sensible heat capacity Table PD 21a 148 kW 42 Ton Gross Cooling Capacities S...

Страница 44: ...19 4 22 8 16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 72 7 57 2 80 6 46 3 89 7 32 2 69 5 55 4 77 1 44 8 85...

Страница 45: ...16 1 19 4 22 8 16 1 19 4 22 8 L s C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 82 1 64 2 91 1 52 2 101 1 36 6 78 3 62 1 87 0 50 4 96 7 34 6 74...

Страница 46: ...C TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 23 9 94 7 77 4 104 9 60 7 116 1 41 9 90 3 75 0 99 9 58 6 110 8 39 9 85 9 72 4 95 0 56 3 105 2 37 5 80 9 69 8 89 7 53 9 99 4 35 2 4130 26 7 95 8 91 7 1...

Страница 47: ...1 6 111 4 88 8 124 3 69 5 138 0 48 4 105 5 85 3 117 5 66 2 131 0 45 1 99 1 81 8 110 8 62 7 123 4 41 9 4720 26 7 118 4 108 7 130 7 88 8 145 1 68 3 112 8 105 5 124 6 85 3 138 3 65 1 107 3 102 0 118 1 82...

Страница 48: ...6 163 8 58 0 126 3 107 0 140 1 81 5 155 3 54 2 118 7 102 9 131 9 77 7 146 2 50 4 5900 26 7 142 4 136 9 155 9 110 2 172 6 83 5 136 0 133 1 148 6 106 4 164 4 79 7 128 4 128 4 140 7 102 3 155 9 75 9 121...

Страница 49: ...4 2 53 8 13 6 11 9 10 5 9 5 8 6 7 9 7 3 6 8 6 3 5 9 5 6 67 3 17 0 14 8 13 2 11 9 10 8 9 9 9 1 8 5 7 9 7 4 7 0 80 7 14 2 13 0 11 9 11 0 10 2 9 5 8 9 8 4 Notes 1 Air temperature rise in this table are...

Страница 50: ...9 31 812 10 21 11235 742 8 74 778 9 63 812 10 55 11650 745 9 11 778 9 96 812 10 89 12065 747 9 47 779 10 34 81 1 11 24 Table PD 25a Supply Fan Performance 82 105 kW SI Static Pressure Pascals 62 9 124...

Страница 51: ...600 RPM 500 RPM 400 RPM Volumetric Airflow Rate CFM Static Presure InWC Table PD 25a Supply Fan Performance 23 29 Ton kW SI Continued Static Pressure Pascals 620 9 683 0 745 1 L s rpm kW rpm kW rpm kW...

Страница 52: ...1 584 5 90 614 6 49 642 7 10 6683 344 2 57 387 3 09 424 3 62 459 4 14 495 4 70 527 5 28 557 5 84 589 6 43 619 7 05 648 7 69 7076 358 2 97 401 3 56 437 4 09 470 4 65 503 5 21 538 5 84 565 6 42 594 7 02...

Страница 53: ...00 s 0 94 1 89 2 83 3 78 4 72 5 66 6 61 7 55 8 5 9 44 10 38 11 33 12 27 13 22 90 WOCFM 80 WOCFM 70 W O CFM 60 W O CFM 5 0 W O C F M 4 0 W O C F M 2 0 H P 1 5 H P 1 0 H P 7 5 H P 800 RPM 750 RPM 700 RP...

Страница 54: ...9 0 1 0 18 0 23 0 1 0 17 0 16 0 11 0 065 11200 0 19 0 15 0 13 0 14 0 24 0 3 0 12 0 21 0 19 0 13 0 077 12100 0 22 0 17 0 15 0 16 0 27 0 33 0 13 0 22 0 21 0 15 0 091 10000 0 01 0 03 0 07 0 11 0 15 0 19...

Страница 55: ...0 17 19 22 29 19 31 29 17 0 08 88 25 4320 31 24 21 23 29 34 22 36 34 25 0 12 5120 44 34 29 32 31 41 26 43 41 29 0 14 4130 29 22 19 21 38 48 22 36 31 19 0 09 4520 34 27 23 25 43 55 24 41 38 23 0 11 103...

Страница 56: ...static pressure drop than the maximum shown in the table for each motor speed tap Table PD 29a Power Exhaust Fan Performance SI External Static Pressure Pa Exhaust High Med Low Airflow Speed Speed Spe...

Страница 57: ...red to provide full nominal airflow in the event of drive failure 2 Supply Air Temperature Controls Cooling Economizer During occupied cooling mode of operation the economizer if available and primary...

Страница 58: ...Sequence of Operation 1 Occupied Zone Temperature Control Cooling Economizer During occupied cooling mode the economizer if provided and primary cooling are used to control zone temperature If the ent...

Страница 59: ...tain Unoccupied zone temperature setpoints For Unoccupied periods heating or primary cooling operation can be selectively locked out at the remote panels or TRACER ConventionalThermostat Interface Con...

Страница 60: ...itches from night setback to occupied mode all heating cooling functions begin normal operation When using the night setback options with aVAV heating cooling rooftop airflow must be maintained throug...

Страница 61: ...DE values as if the unit was in the heating mode as follows Keep in mind when determining LOADS that the compressors and condenser fans don t run while the unit is in the heating mode and crankcase he...

Страница 62: ...7 5 19 6 18 8 7 0 6 7 10 0 26 4 25 2 15 0 38 6 36 0 460 60 3 414 506 27 3 142 7 5 9 8 9 4 3 5 2 9 10 0 13 2 12 6 15 0 19 3 18 0 575 60 3 517 633 21 8 114 7 5 7 8 7 5 2 8 2 3 10 0 10 3 10 1 15 0 15 4 1...

Страница 63: ...Ea No HP Ea MCA Fuse Size TC TE YC 275 380 415 50 3 1 10 1 15 18 1 27 3 110 174 5 13 1 3 75 4 4 2 75 2 9 79 100 TC TE YC 305 380 415 50 3 2 15 27 3 174 5 13 1 3 75 4 4 2 75 2 9 93 110 TC TE YC 350 380...

Страница 64: ...the three Horizontal Fresh Air Hoods are located side by side The Fresh Air Hoods not shown extend only 23 15 16 from the end of the unit SIDE VIEW SHOWING FRESH AIR AND POWER EXHAUST HOODS FORDOWNFLO...

Страница 65: ...65 RT PRC007 EN Dimensional Data 60 50 Hz Figure DD 2 60 Hz 27 35 50 Hz 23 29 Tons TC TE YC Low Heat Note Dimensions in are mm 1 25 4 mm...

Страница 66: ...RT PRC007 EN 66 Dimensional Data 60 50 Hz Figure DD 3 60 Hz 27 35 50 Hz 23 29 Tons YC High Heat Note Dimensions in are mm 1 25 4 mm...

Страница 67: ...67 RT PRC007 EN Dimensional Data 60 50 Hz Figure DD 4 60 Hz 40 50 50 Hz 33 42Tons TC TE YC Low High Heat Note Dimensions in are mm 1 25 4 mm...

Страница 68: ...lable for use with all zone sensors to provide remote sensing capabilities SINGLE SETPOINT SENSOR WITH SYSTEM FUNCTION LIGHTS BAYSENS021 PROGRAMMABLE NIGHT SETBACK SENSOR BAYSENS020 Dimensional Data F...

Страница 69: ...CHANGEOVER SENSOR WITH SYSTEM FUNCTION LIGHTS BAYSENS010 WITHOUT LED STATUS INDICATORS BAYSENS008 SINGLE SETPOINT WITHOUT LED STATUS INDICATORS BAYSENS006 Note 1 Remote sensors are available for use...

Страница 70: ...ensing capabilities REMOTE MINIMUM POSITION POTENTIOMETER CONTROL BAYSTAT023 TEMPERATURE SENSOR BAYSENS016 ZONE TEMPERATURE SENSOR W TIMED OVERRIDE BUTTON AND LOCAL SETPOINT ADJUSTMENT BAYSENS014 1 ZO...

Страница 71: ...addition to the standard 2 row coil weight included in the basic unit weight see component weights TableW 3 Model A B C D E F D330 275 899 408 693 314 717 325 723 328 571 259 471 214 H330 275 920 417...

Страница 72: ...Man Guide W O With Serv base Discon Discon Cond Curb Model Relief Exhaust FanMotor2 Damper Econ Vanes Bypass Valves Elec Switch Switch Coil3 Lo Hi D330 275 110 50 165 74 20 9 50 23 260 117 55 25 85 39...

Страница 73: ...s Evaporator and Condenser Coils Condenser coils shall have 3 8 copper tubes mechanically bonded to lanced aluminum plate fins Evaporator coils shall be 1 2 internally finned copper tubes mechanically...

Страница 74: ...munication link The following alarm and diagnostic information shall be available RTRM Originated Data Unit operating mode Unit failure status Cooling failure Heating failure Emergency service stop in...

Страница 75: ...l have 3 8 copper tubes mechanically bonded to lanced aluminum plate fins DischargeAir Sensing Provides true discharge air sensing in heating and cooling models This sensor is a status indicator reada...

Страница 76: ...temperature adjustment control and timed override buttons used withTracer Integrated Comfort system May also be used for MorningWarm up setpoint and sensor BAYSENS016 Temperature Sensor is a bullet or...

Страница 77: ...77 RT PRC007 EN...

Страница 78: ......

Страница 79: ......

Страница 80: ...l us at comfort trane com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number RT PRC...

Отзывы: