General Data
27½ Ton
30 Ton
Cooling Performance
1
Nominal Gross Capacity
329,000
363,000
Natural Gas Heat
2
Low
High
Low
High
Heating Input (BTUH)
350,000
600,000
350,000
600,000
First Stage
250,000
425,000
250,000
425,000
Heating Output (BTUH)
283,500
486,000
283,500
486,000
First Stage
202,500
344,500
202,500
344,500
Steady State Efficiency (%)
3
81.00
81.00
81.00
81.00
No. Burners
1
2
1
2
No. Stages
2
2
2
2
Gas Supply Pressure (in. w.c.)
Natural or LP (minimum/maximum)
2.5/14.0
2.5/14.0
2.5/14.0
2.5/14.0
Gas Connection Pipe Size (in.)
3
/
4
1
3
/
4
1
Electric Heat
KW Range
5
27-90
5
27-90
5
Capacity Steps:
2
2
Compressor
Number/Type
2/Scroll
2/Scroll
Size (Nominal)
10/15
15
Unit Capacity Steps (%)
100/40
100/50
Motor RPM
3450
3450
Outdoor Coil
Standard Efficiency
High Efficiency
Standard Efficiency
High Efficiency
Type
Lanced
Lanced
Lanced
Lanced
Tube Size (in.) OD
3
/
8
3
/
8
3
/
8
3
/
8
Face Area (sq. ft.)
51.33
51.33
51.33
51.33
Rows/Fins Per Inch
2/16
3/16
2/16
3/16
Indoor Coil — Type
Hi-Performance
Hi-Performance
Tube Size (in.) OD
1
/
2
1
/
2
Face Area (sq. ft.)
31.67
31.67
Rows/Fins Per Foot
2/180
2/180
Refrigerant Control
TXV
TXV
No. of Circuits
1
1
Drain Connection No./Size (in)
1/1.25
1/1.25
Type
PVC
PVC
Outdoor Fan Type
Propeller
Propeller
No. Used/Diameter
3/28.00
3/28.00
Drive Type/No. Speeds
Direct/1
Direct/1
CFM
24,800
24,800
No. Motors/HP/RPM
3/1.10/1125
3/1.10/1125
Indoor Fan Type
FC
FC
No. Used
1
1
Diameter/Width (in)
22.38/22.00
22.38/22.00
Drive Type/No. Speeds
Belt/1
Belt/1
No. Motors/HP
1/7.50/10.00
1/7.50/10.00
Motor RPM
1760
1760
Motor Frame Size
213/215T
213/215T
Exhaust Fan Type
Propeller
Propeller
No. Used/Diameter (in)
2/26.00
2/26.00
Drive Type/No. Speeds/Motors
Direct/2/2
Direct/2/2
Motor HP/RPM
1.0/1075
1.0/1075
Motor Frame Size
48
48
Filters
— Type Furnished
Throwaway
Throwaway
No./ Recommended Size (in)
6
16/16 x 20 x 2
16/16 x 20 x 2
Refrigerant Charge
(Std./Hi Eff Cond Coil)
(Lbs of R-22)
4
(Std) 46.0/(High) 58.0
(Std.) 46.6/(High) 58.0
Minimum Outside Air Temperature
For Mechanical Cooling
0 F
0 F
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in
accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93.
2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric heat KW range per specific voltage, see table PD-10.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
Table GD-1 — General Data — 27½ - 30 Tons
60 Hz