63
RT-PRC007-EN
Electrical
Data
Table ED-5 – Electrical Service Sizing Data – Electric Heat Module
(Electric Heat Units Only)
Models: TED/TEH 275 thru 500
Electric Heat FLA
Nominal
Nominal
Unit Size
Unit
KW Heater (380/415V)
(Tons)
Voltage
23/27
34/40
45/54
56/67
68/81
23-29
380
34.5
51.1
68.9
85.5
–
415
37.6
55.6
–
–
–
33, 42
380
–
51.1
68.9
85.5
103.4
415
–
55.6
75.1
93.2
112.7
Notes:
1. All FLA in this table are based on heater operating at 380 or 415 volts as shown above.
Table ED-4 – Electrical Service Sizing Data
Fan Motors
Compressor
Supply
Condenser
Exhaust
Electrical
2
RLA
LRA
FLA
FLA
Max.
Model
Characteristics
No/Ton
(Ea.)
(Ea.)
HP
FLA
No.
HP
(Ea.)
No.
HP
(Ea.)
MCA*
Fuse Size
TC/TE/YC*275
380-415/50/3
1/10, 1/15 18.1/27.3
110/174
5
13.1
3
.75
4.4
2 .75
2.9
79
100
TC/TE/YC*305
380-415/50/3
2/15
27.3
174
5
13.1
3
.75
4.4
2
.75
2.9
93
110
TC/TE/YC*350
380-415/50/3
2/15
27.3
174
5
13.1
3
.75
4.4
2
.75
2.9
93
110
TC/TE/YC*400
380-415/50/3
2/15,
27.3
174
7.5
16.6
4
.75
4.4
2
.75
2.9
119
125
1/10
18.1
110
TC/TE/YC*500
380-415/50/3
3/15
27.3
174
7.5
16.6
4
.75
4.4
2
.75
2.9
128
150
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
* Minimum Circuit Ampacity.
50 Hz
Nominal
FLA Add
Unit Size
Unit Voltage
(Tons)
380
415
23 - 29
1
1
33 - 42
2
2
Table ED-6— Electrical Service Sizing Data — Crankcase Heaters —
Heating Mode Only)