Zone Sensor Options
UNT-SVX07J-EN
93
•
Usable range: 200 ft
•
Typical range: 75 ft
Height Requirements
It is recommended that you mount the back plate a
maximum distance of 54 inches above the floor. If a
parallel approach by a person in a wheelchair is required,
reduce the maximum height to 48 inches.
Note:
Consult section 4.27.3 of the 2002 ADA (Americans
with Disability Act) guideline, and local building
codes, for further details regarding wheelchair
requirements.
Mounting Surfaces
Using the hardware provided, mount the back plate of the
sensor to a flat surface such as sheetrock or plaster, or an
electrical junction box. The sensor must be mounted
plumb for accurate temperature control and to ensure
proper air movement through the sensor.
•
If mounting onto sheetrock or plaster, use the plastic
threaded anchors (pre-drilling holes is not usually
necessary) and the two M3.5 x 20 mm mounting
screws.
•
For mounting onto an electrical junction box, use the
two 6-32 x 3/4 in. screws.
Zone Sensor Dimensions
Refer the wall-mounted zone sensor dimensions in the
figure below. Position the sensor on an inside wall three to
five feet above the floor and at least 18 inches from the
nearest outside wall. Installing the sensor at a lower height
may give the advantage of monitoring the temperature
closer to the zone, but it also exposes the sensor to airflow
obstructions. Ensure that air flows freely over the sensor.
Wired Zone Sensor
Refer to the unit wiring schematic for specific wiring
details and point connections.
1.
Note the position of the setpoint adjustment knob and
gently pry the adjustment knob from the cover using
the blade of a small screwdriver.
2. Insert the screwdriver blade behind the cover at the top
of the module and carefully pry the cover away from
the base.
3. To mount the sensor back plate: (see the figure below).
a. Hold the back plate against the mounting surface
and mark the screw locations.
b. Secure the back plate against the mounting surface
using included hardware.
Figure 80.
Wall-mounted wired and wireless zone
sensor dimensions
1.45 in.
0.63 in.
2.48 in.
4.68 in. 3.39 in.
0.12 in.
1.08 in.
2.90 in.
TYP 0.24 in.
TYP R.07 in.
(R1.9)
0.31 in.
2.62 in.