Installation - Electrical
64
UNT-SVX07J-EN
Table 35. Force-Flo two-stage electric heat
Unit
Size
Voltage
# Wires 1
st
Stage kW Total kW Total amps/
ph
02
208/60/1 2
0.8
2.3
10.9
240/60/1
2
1.0
3.0
12.5
277/60/1
2
1.0
3.0
10.9
208/60/3
3
0.8
2.3
6.3
240/60/3 3
1.0
3.0
7.3
480/60/3
4
1.0
3.0
3.7
220-240/50/1
2
1.0
3.0
12.5
220-240/50/3
3
1.0
3.0
7.3
380-415/50/3
4
1.0
3.0
4.2
03
208/60/1
2
1.5
4.5
21.7
240/60/1
2
2.0
6.0
25.0
277/60/1
2
2.0
6.0
21.7
208/60/3 3
1.5
4.5
12.6
240/60/3
3
2.0
6.0
14.5
480/60/3 4
2.0
6.0
7.3
220-240/50/1
2
2.0
6.0
25.0
220-240/50/3
3
2.0
6.0
14.5
380-415/50/3
4
2.0
6.0
8.4
04
208/60/1 2
1.9
5.7
27.5
240/60/1
2
2.5
7.5
31.3
277/60/1 2
2.5
7.5
27.1
208/60/3
3
1.9
5.7
15.9
240/60/3
3
2.5
7.5
18.1
480/60/3
4
2.5
7.5
9.1
220-240/50/1
2
2.5
7.5
31.3
220-240/50/3
3
2.5
7.5
18.1
380-415/50/3
4
2.5
7.5
10.5
06
208/60/1
2
2.2
7.9
38.0
240/60/1 2
3.0
10.5
43.8
277/60/1
2
3.0
10.5
38.0
208/60/3 3
3.4
7.9
21.9
240/60/3
3
4.5
10.5
25.3
480/60/3 4
4.5
10.5
12.7
220-240/50/1
2
3.0
10.5
43.8
220-240/50/3
3
4.5
10.5
25.3
380-415/50/3
4
4.5
10.5
14.7
Unit
Size
Voltage
# Wires 1
st
Stage kW Total kW
Total amps/
ph
08
208/60/3 3
4.5
10.1
28.2
240/60/3
3
6.0
13.5
32.5
480/60/3 4
6.0
13.5
16.3
220-240/50/3
3
6.0
13.5
32.5
380-415/50/3
4
6.0
13.5
18.8
10
480/60/3
4
8.0
18.0
21.7
380-415/50/3
4
8.0
18.0
25.1
12
480/60/3
4
9.0
20.0
24.1
380-415/50/3
4
9.0
20.0
27.9
Note:
When both stages are on, the electric heat will operate only when fan
is in high speed. All data based on individual units.
Table 35. Force-Flo two-stage electric heat
Содержание UniTrane
Страница 163: ......