MCA = 1.25 x (heater amps + all motor FLAs)
MOP = (2.25 x largest motor FLA) + second motor FLA +
heater amps (if applicable)
Select a standard fuse equal to or less than the MOP. The
selected fuse must be larger than the MCA.
Standard fuse sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60
amps
Fan-coil electric heat MBh = (heater kW) (3.413)
Table 33. Force-Flo single-stage, max kW electric heat
Unit
Size
Voltage
# Wires
Heater kW
Heater amps/
ph
02
208/60/1 2
2.25
10.90
240/60/1
2
3.00
12.50
277/60/1 2
3.00
10.90
208/60/3
3
2.25
6.30
240/60/3 3
3.00
7.30
480/60/3
4
3.00
3.70
220-240/50/1
2
3.00
12.50
220-240/50/3
3
3.00
7.30
380-415/50/3
4
3.00
4.20
03
208/60/1
2
4.50
21.70
240/60/1 2
6.00
25.00
277/60/1
2
6.00
21.70
208/60/3 3
4.50
12.60
240/60/3
3
6.00
14.50
480/60/3 4
6.00
7.30
220-240/50/1
2
6.00
25.00
220-240/50/3
3
6.00
14.50
380-415/50/3
4
6.00
8.40
04
208/60/1 2
5.70
27.50
240/60/1
2
7.50
31.30
277/60/1 2
7.50
27.10
208/60/3
3
5.70
15.90
240/60/3 3
7.50
18.10
480/60/3
4
7.50
9.10
220-240/50/1
2
7.50
31.30
220-240/50/3
3
7.50
18.10
380-415/50/3
4
7.50
10.50
06
208/60/1
2
7.90
38.00
240/60/1 2
10.50
43.80
277/60/1
2
10.50
38.00
208/60/3
3
7.90
21.90
240/60/3
3
10.50
25.30
480/60/3 4
10.50
12.70
220-240/50/1
2
10.50
43.80
220-240/50/3
3
10.50
25.30
380-415/50/3
4
10.50
14.70