Sequence of Operation

ReliaTel™ Control Cooling Mode

For Zone Sensor Control

When the system switch is set to the 

COOL

 position and the zone temperature rises above the 

cooling setpoint, the RTRM energizes the compressor contactor, provided the high and low 
pressure and the discharge temperature limit controls are closed. When the compressor contacts 
close, the compressor and the outdoor fan motor start to maintain the zone temperature to within 
± 2°F of the sensor setpoint at the sensed location. On units with dual circuits, the second stage of 
cooling is initiated as a result of the Proportional/Integral control algorithms calling for additional 
cooling.

For Thermostat Control:

When the room thermostat system switch is positioned at 

COOL 

and the fan switch is at 

AUTO

the RTRM energizes the compressor contactor, provided the high and low pressure and the 
discharge temperature limit controls are closed. When the contacts of the compressor contactor 
close, operation of the compressor and condenser fan begins. The evaporator fan contactor also 
energizes on a call for cooling and initiates evaporator fan operation. On units with dual circuits, 
the second stage of cooling is initiated as a result of the 2-stage thermostat calling for additional 
cooling.

Note:

Irregular unit operation may occur when the unit is controlled with a triac-switching 
thermostat. Please review the approved thermostat vendor list for all recommended relay-
switching thermostats.

ReliaTel™ Control Evaporator Fan Operation

When the fan selection switch is set to the 

AUTO

 position, the RTRM energizes the evaporator fan 

relay coil approximately 1 second after energizing the compressor contactor coil in the cooling 
mode. In the heating mode, the RTRM energizes the evaporator fan

 

relay coil approximately 1 

second before energizing the electric heat contactors. The RTRM de-energizes the evaporator fan 
relay coil approximately 60 seconds on dual compressor units and 80 seconds on single 
compressor units after the cooling requirement has been satisfied to enhance unit efficiency. When 
the heating cycle is terminated, the evaporator fan relay coil is de-energized at the same time as 
the heater contactors. When the fan selection switch is set to the 

ON

 position, the RTRM keeps the 

evaporator fan relay coil energized for continuous fan motor operation.

ReliaTel™ Control Heating Operation

Electric heat is factory disabled on all split system units with ReliaTel control (jumper placed 
between J2-1 and J2-2 RTRM inputs). To configure the unit for electric heat, cut or remove the 
jumper wire between J2-1 and J2-2 on the RTRM. All split system units with ReliaTel control are 
also configured from the factory for only 1-stage of electric heat (jumper placed between J1-3 and 
J1-6 RTRM inputs). To configure the unit for 2-stages of electric heat, cut or remove the jumper 
placed between J1-3 and J1-6 RTRM inputs.

When the system switch is set to the 

HEAT

 position and heating is required, the RTRM energizes 

the Heat 1 relay coil on the RTRM. When the Heat 1 relay contacts close, the first stage electric heat 
contactor is energized. If the first stage of electric heat cannot satisfy the heating requirement, the 
RTRM energizes the Heat 2

 

relay coil on the RTRM. When the Heat 2

 

relay contacts close, the second 

stage electric heat contactor is energized. The first and second stages of heat are cycled 

“On”

 and 

“Off”

 as required to maintain the zone.

Содержание TTA120D300AA

Страница 1: ...0TAA TTA120DK0TAA TTA120D3HTAA TTA120DKHTAA TTA120D30UAA TTA120DK0UAA TTA120D3HUAA TTA120DKHUAA TTA120D30WAA TTA120DK0WAA TTA120D3HWAA TTA120DKHWAA TTA120D400AA TTA120DW00AA TTA120D4H0AA TTA120DWH0AA...

Страница 2: ...y All technicians who handle refrigerants must be certified The Federal Clean Air Act Section 608 sets forth the requirements for handling reclaiming recovering and recycling of certain refrigerants a...

Страница 3: ...ken ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE When working with or around hazardous chemicals ALWAYS refer to appropriate MSDS and OSHA guidelines for information on allowabl...

Страница 4: ...A TTA120D Rubber Isolator Kit BAYISLT023A TTA120D Steel Spring Isolator Kit Low Ambient BAYLOAMU02A TTA120D On Off Fan Control Mounted in Unit Control Box large cabinets BAYLOAM333A TTA120D3 Modulatin...

Страница 5: ...DOOR COIL INDOOR COIL INDOOR COIL SERVICE SERVICE VALVE VALVE SERVICE SERVICE VALVE VALVE EXPANSION EXPANSION VALVE BULB VALVE BULB EQUALIZER EQUALIZER TUBE TUBE NOTE A NOTE A NOTE A NOTE A NOTE A NOT...

Страница 6: ...0 Tons Single Compressor TTA120D3 D4 DW DK Cooling Performance Gross Cooling Capacity Matched Air Handler 124 000 Condensing Unit Only 112 000 ARI Net Cooling Capacity 120 000 Efficiency Matched Air H...

Страница 7: ...ming power to verify that there is no reversed phase no phase imbalance and no loss of phase If the phase monitor detects any of these three conditions it will shut off control voltage The transformer...

Страница 8: ...lay coil approximately 1 second after energizing the compressor contactor coil in the cooling mode In the heating mode the RTRM energizes the evaporator fan relay coil approximately 1 second before en...

Страница 9: ...000 1050 1100 1150 13 18 24 29 35 41 46 52 Ambient DB Degree C S uction Pres s ure kPa 20 14 DB WB 23 17 DB WB 27 19 DB WB 30 22 DB WB Discharge Pressure at 400 CFM Ton 200 250 300 350 400 450 500 550...

Страница 10: ...TTA120D TTA120D Charging Curve 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 Liquid Temperature Leaving OD...

Страница 11: ...UNDERCHARGE REFRIGERANT OVERCHARGE EXCESSIVE EVAP LOAD NONCONDENSABLES RESTRICTED O D AIRFLOW O D AIR RECIRCULATION TXV STUCK OPEN SUPERHEAT RESTRICTED I D AIRFLOW REF CIRCUIT RESTRICTIONS REFRIGERAN...

Отзывы: