background image

SS-SVF15A-EN

5

Refrigerant Circuit

Figure 1.

   FILTER DRIER

   FILTER DRIER

NOTE A:  ONLY ONE OUTDOOR AND INDOOR

NOTE A:  ONLY ONE OUTDOOR AND INDOOR

                  COIL REFRIGERANT ENTRY AND

                  COIL REFRIGERANT ENTRY AND

                  EXIT CIRCUIT IS SHOWN. ALL

                  EXIT CIRCUIT IS SHOWN. ALL

                  MODELS HAVE MULTIPLE ENTRY

                  MODELS HAVE MULTIPLE ENTRY

                  AND EXIT CIRCUITS.

                  AND EXIT CIRCUITS.

TXV

TXV

S

D

COMPRESSOR

COMPRESSOR

LOW PRESSURE

LOW PRESSURE

SWITCH (LPCO)

SWITCH (LPCO)

FIELD SUPPLIED

FIELD SUPPLIED

INTER-CONNECTING

INTER-CONNECTING

TUBING

TUBING

OUTDOOR COILOUTDOOR COIL

INDOOR COILINDOOR COIL

SERVICE

SERVICE

VALVE

VALVE

SERVICE

SERVICE

VALVE

VALVE

EXPANSION

EXPANSION

VALVE BULB

VALVE BULB

EQUALIZER

EQUALIZER

TUBE

TUBE

NOTE A

NOTE A

NOTE A

NOTE A

NOTE A

NOTE A

NOTE A

NOTE A

HIGH PRESSURE

HIGH PRESSURE

SWITCH (HPCO)

SWITCH (HPCO)

GAUGE

GAUGE

CONNECTION

CONNECTION

DISCHARGE

DISCHARGE

TEMPERATURE

TEMPERATURE

LIMIT (DTL)

LIMIT (DTL)

NOTE B: DUAL CIRCUIT MODELS HAVE 2

NOTE B: DUAL CIRCUIT MODELS HAVE 2

                  REFRIGERATION CIRCUITS.

                  REFRIGERATION CIRCUITS.

AIR

AIR

AIR

AIR

SUB-COOLING CIRCUIT

SUB-COOLING CIRCUIT

GAUGE

GAUGE

CONNECTION

CONNECTION

INDICATES DIRECTION OF

INDICATES DIRECTION OF

REFRIGERANT FLOW

REFRIGERANT FLOW

COOLING ONLY CIRCUIT DIAGRAM

COOLING ONLY CIRCUIT DIAGRAM

V

V

Содержание TTA120D300AA

Страница 1: ...0TAA TTA120DK0TAA TTA120D3HTAA TTA120DKHTAA TTA120D30UAA TTA120DK0UAA TTA120D3HUAA TTA120DKHUAA TTA120D30WAA TTA120DK0WAA TTA120D3HWAA TTA120DKHWAA TTA120D400AA TTA120DW00AA TTA120D4H0AA TTA120DWH0AA...

Страница 2: ...y All technicians who handle refrigerants must be certified The Federal Clean Air Act Section 608 sets forth the requirements for handling reclaiming recovering and recycling of certain refrigerants a...

Страница 3: ...ken ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE When working with or around hazardous chemicals ALWAYS refer to appropriate MSDS and OSHA guidelines for information on allowabl...

Страница 4: ...A TTA120D Rubber Isolator Kit BAYISLT023A TTA120D Steel Spring Isolator Kit Low Ambient BAYLOAMU02A TTA120D On Off Fan Control Mounted in Unit Control Box large cabinets BAYLOAM333A TTA120D3 Modulatin...

Страница 5: ...DOOR COIL INDOOR COIL INDOOR COIL SERVICE SERVICE VALVE VALVE SERVICE SERVICE VALVE VALVE EXPANSION EXPANSION VALVE BULB VALVE BULB EQUALIZER EQUALIZER TUBE TUBE NOTE A NOTE A NOTE A NOTE A NOTE A NOT...

Страница 6: ...0 Tons Single Compressor TTA120D3 D4 DW DK Cooling Performance Gross Cooling Capacity Matched Air Handler 124 000 Condensing Unit Only 112 000 ARI Net Cooling Capacity 120 000 Efficiency Matched Air H...

Страница 7: ...ming power to verify that there is no reversed phase no phase imbalance and no loss of phase If the phase monitor detects any of these three conditions it will shut off control voltage The transformer...

Страница 8: ...lay coil approximately 1 second after energizing the compressor contactor coil in the cooling mode In the heating mode the RTRM energizes the evaporator fan relay coil approximately 1 second before en...

Страница 9: ...000 1050 1100 1150 13 18 24 29 35 41 46 52 Ambient DB Degree C S uction Pres s ure kPa 20 14 DB WB 23 17 DB WB 27 19 DB WB 30 22 DB WB Discharge Pressure at 400 CFM Ton 200 250 300 350 400 450 500 550...

Страница 10: ...TTA120D TTA120D Charging Curve 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 Liquid Temperature Leaving OD...

Страница 11: ...UNDERCHARGE REFRIGERANT OVERCHARGE EXCESSIVE EVAP LOAD NONCONDENSABLES RESTRICTED O D AIRFLOW O D AIR RECIRCULATION TXV STUCK OPEN SUPERHEAT RESTRICTED I D AIRFLOW REF CIRCUIT RESTRICTIONS REFRIGERAN...

Отзывы: