Product Specifications

NOTICE

Refrigerant in Crankcase!

Do not disconnect power except for safety or service. Follow these procedures prior to startup if 
unit has been charged or power has been disconnected for more than 12 hours. If system has 
just been charged through liquid line service valve port, an 8 hour compressor oil warming time 
is not required. 
Set room thermostat to “OFF” position and ensure compressor is not running. 
Apply power for at least 8 hours prior to startup by closing disconnect switch. This will energize 
compressor oil heater which will evaporate any liquid refrigerant in crankcase. After 8 hours the 
thermostat may be set to cooling. 
Failure to follow the above could result in equipment damage.

Table 2.

General Data — TTA120D

10 Tons

Single Compressor 

TTA120D3, D4, DW

, DK

Cooling Performance
Gross Cooling Capacity

Matched Air Handler

124,000

Condensing Unit Only

112,000

ARI Net Cooling Capacity

120,000

Efficiency

Matched Air Handler (EER)

11.2

Condensing Unit Only (EER)

12.2

System Integrated Part Load Value (IPLV)

N/A

System (IEER)

12.2

Condensing Unit Only (IPLV)

N/A

System kW/Condensing Unit kW

10.72/9.18

Compressor

Type

Scroll

No./Tons

1/8.6

System Data

No. Refrigerant Circuits

1

Suction Line (in.) OD

1 3/8

Liquid Line (in.) OD

1/2

Outdoor Coil - Type

Lanced

Tube Size (in.) OD

0.375

Face Area (sq ft)

24.0

Rows/FPI

2/18

Outdoor Fan - Type

Propeller

No. Used/Diameter (in.)

1/28

Drive Type/No. Speeds

Direct/1

CFM

9600

No. Motor/HP

1/1

Motor RPM

1100

Refrigerant Charge (Field Supplied) 

(lbs of R410A)

22.5

Table 3.

Estimated charge levels at ARI rated line lengths (25 feet)

Matched Set

Refrigerant Charge

Per Circuit

Circuit 1

Circuit 2

Liquid Line

Diameter

Vapor Line

Diameter

TTA120D w/TWE120D

22.5

NA

0.5

1.375

Содержание TTA120D300AA

Страница 1: ...0TAA TTA120DK0TAA TTA120D3HTAA TTA120DKHTAA TTA120D30UAA TTA120DK0UAA TTA120D3HUAA TTA120DKHUAA TTA120D30WAA TTA120DK0WAA TTA120D3HWAA TTA120DKHWAA TTA120D400AA TTA120DW00AA TTA120D4H0AA TTA120DWH0AA...

Страница 2: ...y All technicians who handle refrigerants must be certified The Federal Clean Air Act Section 608 sets forth the requirements for handling reclaiming recovering and recycling of certain refrigerants a...

Страница 3: ...ken ALWAYS refer to appropriate MSDS and OSHA guidelines for proper PPE When working with or around hazardous chemicals ALWAYS refer to appropriate MSDS and OSHA guidelines for information on allowabl...

Страница 4: ...A TTA120D Rubber Isolator Kit BAYISLT023A TTA120D Steel Spring Isolator Kit Low Ambient BAYLOAMU02A TTA120D On Off Fan Control Mounted in Unit Control Box large cabinets BAYLOAM333A TTA120D3 Modulatin...

Страница 5: ...DOOR COIL INDOOR COIL INDOOR COIL SERVICE SERVICE VALVE VALVE SERVICE SERVICE VALVE VALVE EXPANSION EXPANSION VALVE BULB VALVE BULB EQUALIZER EQUALIZER TUBE TUBE NOTE A NOTE A NOTE A NOTE A NOTE A NOT...

Страница 6: ...0 Tons Single Compressor TTA120D3 D4 DW DK Cooling Performance Gross Cooling Capacity Matched Air Handler 124 000 Condensing Unit Only 112 000 ARI Net Cooling Capacity 120 000 Efficiency Matched Air H...

Страница 7: ...ming power to verify that there is no reversed phase no phase imbalance and no loss of phase If the phase monitor detects any of these three conditions it will shut off control voltage The transformer...

Страница 8: ...lay coil approximately 1 second after energizing the compressor contactor coil in the cooling mode In the heating mode the RTRM energizes the evaporator fan relay coil approximately 1 second before en...

Страница 9: ...000 1050 1100 1150 13 18 24 29 35 41 46 52 Ambient DB Degree C S uction Pres s ure kPa 20 14 DB WB 23 17 DB WB 27 19 DB WB 30 22 DB WB Discharge Pressure at 400 CFM Ton 200 250 300 350 400 450 500 550...

Страница 10: ...TTA120D TTA120D Charging Curve 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 Liquid Temperature Leaving OD...

Страница 11: ...UNDERCHARGE REFRIGERANT OVERCHARGE EXCESSIVE EVAP LOAD NONCONDENSABLES RESTRICTED O D AIRFLOW O D AIR RECIRCULATION TXV STUCK OPEN SUPERHEAT RESTRICTED I D AIRFLOW REF CIRCUIT RESTRICTIONS REFRIGERAN...

Отзывы: