Facility View Operations
More specifically, you can use the Facility View to perform the following tasks:
•
Select the devices to be included in the override operation on the Device Navigation Tree and
transfer them to the Facility View. (See “Specifying a Device Group on the Navigation Tree”
and “Overriding Multiple Air Valves, Water Valves” and Fans” in the
Tracer TU Balancing
Tool Help
.)
Figure 13.
Group selection and transfer to the Facility View
•
Use the check boxes on Facility View to deselect or reselect items from the transferred device
list.
•
Override hot and chilled water valves, economizer valves, or isolation valves to Full Open or
Full Closed.
N
No
otte
e:: These water valve overrides apply only to equipment with reheat coils, such as VAVs,
fan coils, and blower coils. It excludes air handling units.
•
Override air valves to any of the following positions: Full Open, Full Closed, Maximum Flow,
Minimum Flow, or a user-defined position.
Example: Enter a percentage open value that the air valve will drive to, such as 50% open.
N
No
otte
e:: This air valve override applies only to VAV equipment types.
•
Override the ventilation damper on BC, FC, and UV units configured with modulating outside
air dampers. The damper can be opened to an adjustable percent.