Facility View

You are working at a job that includes 50 VAV boxes on a single BACnet MS/TP link. All VAVs
have been installed correctly and are fully commissioned. The System Controller has not yet
been installed on the single water loop serving all 50 VAV boxes. You need to override all the
water valves to the open position until the central water pump balancing task is complete. Access
the Facility View by clicking the icon (shown at the upper left) to apply the override to all the
VAVs you have selected on the Device Navigation Tree simultaneously in one operation.
Applying overrides to groups saves time over a one-device-at-a-time approach.

You can also use the Facility View to override air dampers, fans, and water valves on multiple
instances of a single equipment type including BCs, FCs, UVs, and WSHPs.

The Facility View operates using all types of communication: wired or wireless via Single Link
Access, System Controller pass-through, and BACnet/IP. While the presence of a System
Controller improves performance, the Facility View grouping feature can also function
independently of a System Controller.

The Override Dialog Box

Use the Override dialog box accessed with the Override button on the Facility View to drive air
valves and water valves over the entire communication link to specific positions. Once you
activate an override for a group of similar devices, you can then check the status of all selected
devices to be sure they are acting in the expected manner. You are then free to turn to other tasks
while the override is in effect for the specified duration (seven days maximum).

Figure 12.

Override dialog box launched from the Facility View

N

No

otte

e:: Trane standard programs are required to perform group operations.

Содержание Tracer TU

Страница 1: ...ervicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person...

Страница 2: ...which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to...

Страница 3: ...ci ia an ns s M MU US ST T p pu ut t o on n a al ll l P PP PE E i in n a ac cc co or rd da an nc ce e w wi it th h O OS SH HA A N NF FP PA A 7 70 0E E o or r o ot th he er r c co ou un nt tr ry y s sp...

Страница 4: ...ly referred to as an Application SC It is now referred to as Tracer SC SC app controller The Tracer SC with Base license was previously referred to as a Base SC It is now referred to as Tracer SC SC b...

Страница 5: ...Air Valve Dialog Box 12 Current Operating Status Box 12 Drive to Maximum Minimum Air Flow 13 The Hot Deck Air Valve Balancing Steps Dialog Box 13 The Override Dialog Boxes 13 The Air Flow Override Dia...

Страница 6: ...d Wireless Through System Controller pass through or a LAN connection You can also perform operations on multiple similar devices through the Facility View USB and Tracer TU Adapter Connections The D...

Страница 7: ...lers The main System Controller is referred to as an Tracer SC SC app controller To create a link to a facility you need to know the IP or DNS address assigned to the System Controller you want to acc...

Страница 8: ...hat using a secure connection slows Tracer TU performance 7 Click S Sa av ve e Each facility you create is saved and can then be selected from the Facility drop down list Figure 3 Selecting a System C...

Страница 9: ...ing Tool window All the devices on the System Controller s links are listed in the Device Navigation Tree See The Device Navigation Tree Pane section in the Tracer TU Balancing Tool Help for additiona...

Страница 10: ...shown in Figure 6 p 11 It may take the Balancing Tool a minute or two to download and populate the screen with the point values You can navigate to any of the other Balancing Tool screens Flow Calibra...

Страница 11: ...Screen For complete information on connection methods including wireless connections see the Connecting to and Disconnecting from a Controller section in the Tracer TU Balancing Tool Help D De ev vi...

Страница 12: ...rt t button on the Flow Calibration screen You can use this dialog box to perform a two point air valve calibration N No ot te e Tracer TU presents the Hot Deck Air Valve Balancing Steps dialog box w...

Страница 13: ...F Fl lo ow w M Mi in ni im mu um m value in the entry box and press E En nt te er r tab out of the entry box or click C Ca al lc cu ul la at te e R Re es su ul lt t The final two point result is disp...

Страница 14: ...fan On or Off for a limited time while you balance the air flow at the diffusers In addition you can adjust the ECM fan speed as a percentage if an ECM fan is installed and configured or select a fan...

Страница 15: ...og boxes The standard default time duration is 4 hours on all of these override dialog boxes If you wish to release the override manually you can select R Re el le ea as se e and click A Ap pp pl ly y...

Страница 16: ...le equipment type including BCs FCs UVs and WSHPs The Facility View operates using all types of communication wired or wireless via Single Link Access System Controller pass through and BACnet IP Whil...

Страница 17: ...evice list Override hot and chilled water valves economizer valves or isolation valves to Full Open or Full Closed N No ot te e These water valve overrides apply only to equipment with reheat coils su...

Страница 18: ...to a priority conflict Calibrate the air valves of all selected VAV boxes using the VAV Balancing view In addition Facility View performs the following operations Releases overrides to automatic contr...

Страница 19: ...BAS SVU24G EN 19 N No ot te es s...

Страница 20: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: