UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
CG-SVU007D-GB
Alarms
N°
Message
Reset
Type
Unit Status
Description
73
Alarms pCOe 5 IO
mismatch
Auto
Unit On
pCOextension5 is in default on Analog input #4
74
Alarm Drive Fault
Manual
Unit Off
Variable Primary Flow Drive fault
75
Alarm Low Differential
Pressure ckt1
Auto
Circuit 1 Off
Low Differential Pressure on circuit 1 (High
Pressure - Low Pressure)
76
Alarm Low Differential
Pressure ckt2
Auto
Circuit 2 Off
Low Differential Pressure on circuit 2 (High
Pressure - Low Pressure)
77
Warning Cutout Supp
Heating
Auto
Unit On
Information that Supplemental Heating is in cut
out
78
Warning LRTC limit ckt1
Auto
Circuit 1 Limit
Low Refrigerant Temperature cut-out on circuit 1
79
Warning LRTC limit ckt2
Auto
Circuit 2 Limit
Low Refrigerant Temperature cut-out on circuit 2
80
EVD EVO EXV synchro
Please wait
Auto
Unit Off
Expansion Valve is currently initiating