6. Sensors and transducers
To access one of the parameters
displayed, press
and change
value using
or
. Confirm the
value by pressing
Temp probe:
Sensor type:
NTC
(factory setting)
PT100
Press probe:
Pressure transducer:
0..10V
0..1V
0..20mA
4..20mA
(factory setting)
Min Press:
Pressure at 0V, 0mA or
4 mA (-1.0 to 0.0 bar - factory
setting: 0.0 bar)
Max Press:
Pressure at 10V, 1V or
20 mA (16 to 50 bar - factory
setting: 30bar)
7. Operation limits
To access one of the parameters
displayed, press
and change
value using
or
. Confirm the
value by pressing
LP (Sat Temp):
Low evaporating
pressure limit (-25 to 0°C - factory
setting: -4°C)
Timer LP:
Low pressure fault timer
after compressor start (0 to 300 s -
factory setting: 60s)
HP Cool StP:
High pressure limit in
cooling mode (15 to 40 bar - factory
setting: 28 bar)
HP Heat StP:
High pressure limit in
heating mode (15 to 40 bar - factory
setting: 28 bar)
8. Analog Output (for speed inverter)
Note:
This screen is displayed only if
“Invert” has been selected in the HP
control menu (refer to §3)
To access one of the parameters
displayed, press
and change
value using
or
. Confirm the
value by pressing
Low 0V:
Minimum fan speed (0
to 10 bar - factory setting: 8 bar)
High 10V:
Maximum fan speed
(11 to 40 bar - factory setting: 16 bar)
Temp probe
NTC
Press probe
4..20mA
Min Press
0.0bar
Max Press
30.0bar
LP (Sat Temp)
-4°C
Timer LP
60 s
HP Cool Stp
28.0 bar
HP Heat Stp
28.0 bar
Analog output
Low
OV
08.0 bar
High
10V
16.0 bar
Unit configuration menu:
“Configuration”
20
CG-SV01B-E4