From the menu screen, select
“
Configuration
” then press .
Following screen will appear:
Enter default password:”0000”
(factory-set)
Press
and cursor will move to
first field of password. Pressing
or
will increment the value from
0 to 9999. Keeping pressure on
or
will move the numbers fast.
Press
to confirm password.
Pressing or will
allow
navigation from screen 1 to 11 as
shown hereafter:
1. Unit definition
To access one of the 4 parameters
displayed, press
and change
value using
or
. Confirm the
value by pressing
Unit Type:
Unit type
Chiller:
Cooling only
Heat pump:
Reversible chiller
Refrg:
Refrigerant R407C, R134a,
R410A or R22
Fans/ckt:
Number of fans per circuit:
1, 2, or 3
Note:
Setting number of fans at 0,
will stop all the fans, but will allow
the compressors to run before being
stopped by HP switch.
Water Pump:
Water pump type
Single:
Single pump control
Dual:
Dual pump control
Note:
Pump operation
The water pumps can be single or
dual. A timer is used to delay the
pump shut down in normal
operating conditions. The timer is
reset at each unit start.
Figure 5 - Single pump operation
Note:
figures 5 to 8, Unit Off means
that the unit is stopped by keyboard
or by an external contact
Figure 6 - Dual pump operation
When twin pumps are used, a pump
switch will occur at each start and
also in case of fault on the pump in
operation.
Figure 7 - Single pump protection
t
Unit configuration menu:
“Configuration”
User password
0000
Unit type:
Chiller
Refrg
R407C
Fans/ckt
3
Water pump
Single
On
On
Pump
Off
t
On
Unit
Off
On
Pump 1
Off
On
Pump 2
Off
Pump
protection-
input
Pump
protection-
output
Unit stopped
(manual reset)
CG-SV01B-E4
17