From the menu screen, select

Configuration

” then press       .

Following screen will appear:

Enter default password:”0000”
(factory-set)

Press 

and cursor will move to

first field of password. Pressing 

or 

will increment the value from

0 to 9999. Keeping pressure on 

or 

will move the numbers fast.

Press 

to confirm password.

Pressing or will 

allow

navigation from screen 1 to 11 as
shown hereafter:

1. Unit definition

To access one of the 4 parameters

displayed, press 

and change

value using 

or 

. Confirm the

value by pressing 

Unit Type:

Unit type

Chiller:

Cooling only 

Heat pump:

Reversible chiller

Refrg:

Refrigerant R407C, R134a,

R410A or R22

Fans/ckt:

Number of fans per circuit:

1, 2, or 3

Note:

Setting number of fans at 0,

will stop all the fans, but will allow
the compressors to run before being
stopped by  HP switch.

Water Pump:

Water pump type

Single:

Single pump control

Dual:

Dual pump control

Note:

Pump operation

The water pumps can be single or
dual. A timer is used to delay the
pump shut down in normal
operating conditions. The timer is
reset at each unit start.

Figure 5 - Single pump operation

Note:

figures 5 to 8, Unit Off means

that the unit is stopped by keyboard
or by an external contact

Figure 6 - Dual pump operation

When twin pumps are used, a pump
switch will occur at each start and
also in case of fault on the pump in
operation.

Figure 7 - Single pump protection

t

Unit configuration menu:
“Configuration”

User password

0000

Unit type:

Chiller

Refrg

R407C

Fans/ckt

3

Water pump

Single

On

On

Pump

Off

t

On

Unit

Off

On

Pump 1

Off

On

Pump 2

Off

Pump
protection-
input

Pump
protection-
output

Unit stopped

(manual reset)

CG-SV01B-E4

17

Содержание TRACER CH532

Страница 1: ...TRACER CH532 Chiller controller User guide CG SVU01B E4...

Страница 2: ...ven as a guide to good practice in the installation start up operation and periodic maintenance by the user of TRACER CH532 chiller controller They do not contain the full service procedures necessary...

Страница 3: ...sentation 4 Hardware architecture 5 Starting stopping the unit 9 Menus 10 Display menu Data display 11 Customer settings menu Settings 12 Clock Setting menu Clock 15 Unit configuration menu Configurat...

Страница 4: ...display 1 4 lines x 20 characters with back lighting 6 buttons 2 to 7 Figure 1 TRACER CH532 user interface 2 Alarm button Used for displaying or manually resetting the alarms The red LED lights up wh...

Страница 5: ...CG SVU01B E4 5 Hardware architecture Figure 2 TRACER CH532 inputs and outputs Prg Esc 9 9 10 11...

Страница 6: ...ower on Red LED Alarm 3 Fuse 2A 5x20 4 Universal Analog inputs NTC 0 1V 0 10V 0 20mA 4 20mA 5 Passive Analog Inputs NTC PT1000 ON OFF 6 Analog Outputs 0 10V 7 Digital Inputs 24Vac Vdc 8 Digital Inputs...

Страница 7: ...ID9 24Vac DI Water pump 2 fault ID10 24Vac ID10 24Vac DI Faults external reset ID6 24Vac ID6 24Vac DI Cooling Heating mode switch ID7 24Vac ID7 24Vac DI Unused ID11 ID12 DO Compressor A circuit 1 outp...

Страница 8: ...aving water temperature setpoint 2 Minimum value 3 Maximum value 4 Reset 20 C 5 Active setpoint Table 3 Customer Inputs and output summary list TRACER CH532 Medium TRACER CH532 Large Single circuit un...

Страница 9: ...ss 4 Press or to change from N to Y 5 Press Following screen will be displayed 2 Stopping the unit 1 Press to exit from any menu and return to default display 2 Press for 3 seconds unit will stop and...

Страница 10: ...ed It allows access to the settings of Day of the week hour date Daily or weekly program Hourly zone program Configuration menu This menu is password protected It allows to adjust or change Unit defin...

Страница 11: ...fter anti short cycle Rec Off Compressor will stop after anti short cycle 5 Compressors running time Hrs indicates the number of full hours compressor has been working since its first start 6 Number o...

Страница 12: ...int 4 Reset delta 5 Active set point Below the reset starting point the water temperature setpoint will be the normal setting Between the starting and ending point the setpoint will vary proportionall...

Страница 13: ...ndications concerning this circuit ALL All alarms manual and automatic reset ALL But LA All alarms but without Low Ambient alarm MR only Manual reset alarms only factory setting Status output NO10 Add...

Страница 14: ...of the parameters displayed press and change value using or Confirm the value by pressing Local Setpoints are entered on the module Orders sent from the BMS are not taken into account Remote Orders s...

Страница 15: ...r 2 ON OFF program type When enabled this program will control the unit operation On Off This program will allow the user to Make a choice between the daily and or the weekly operation Define the oper...

Страница 16: ...d change value using or Confirm the value by pressing Start Start time Stop Stop time 3 Hourly Zone The Daily weekly program will allow you to define the cooling mode and heating mode setpoints It wil...

Страница 17: ...p all the fans but will allow the compressors to run before being stopped by HP switch Water Pump Water pump type Single Single pump control Dual Dual pump control Note Pump operation The water pumps...

Страница 18: ...or meaning of message Message 47 Pump 1 Pump protection input Pump 2 Pump 1 Operation Enable Disable Pump 2 Pump 1 Pump control outputs Pump 2 Fault reset Message 46 Message 46 Unit stopped manual res...

Страница 19: ...etting 5 bar 4 Control dead bands To access one of the parameters displayed press and change value using or Confirm the value by pressing Dead band Cmp Compressors regulation dead band around water te...

Страница 20: ...imer after compressor start 0 to 300 s factory setting 60s HP Cool StP High pressure limit in cooling mode 15 to 40 bar factory setting 28 bar HP Heat StP High pressure limit in heating mode 15 to 40...

Страница 21: ...en defrost cycle 15 to 60min factory setting 25 min Note Dual circuits have two independent refrigerant circuits Defrost cycle will only occur on the circuit that needs it The other circuit will conti...

Страница 22: ...er is set to show a circuit fault Fault with manual reset when the cause of the fault disappears a manual reset is required to restart the unit The messages displayed on the user interface screen disa...

Страница 23: ...Auto Manual CMP A2 Off Manu if CMP A2 failure 35 min or 6 failures within 3 hours 30 min 27 Alarm Comp B2 Fault Auto Manual CMP B2 Off Manu if CMP B2 failure 35 min or 6 failures within 3 hours 30 min...

Страница 24: ...while unit On Water Pump 1 Manual Unit On Fault on water pump 1 Water Pump 2 Manual Unit On Fault on water pump 2 Water Flow Auto Unit Off Defrost Ckt1 Auto Unit On Defrost on circuit 1 Defrost Ckt2 A...

Страница 25: ...the official LonWorks guidelines LonMark layer 1 6 interoperability guidelines version 3 0 These documents and additional information are available on the internet site www lonmark org Figure 9 1 3 2...

Страница 26: ...rdware During the activation of the service pin The node is Applicationless LED blinks 1second then always OFF When receiving a WINK command from the network 1 LED blinks second ON then always OFF Nor...

Страница 27: ...ssor A2 fault compressor B2 fault compressor C2 fault pump 1 fault pump 2 fault nv16 chlr_off 0 chlr_run 2 HVAC_HEAT 1 HVAC_COOL 3 Chiller state 0 No alarm 1 In alarm Run _enable 0 Chiller not allowed...

Страница 28: ...0 MHz 100 15 20 0 MHz 100 15 Attenuation dB 1000 feet at 20 C maximum 772 kHz 4 5 1 0 MHz 5 5 4 0 MHz 11 8 0 MHz 15 10 0 MHz 17 16 0 MHz 22 20 0 MHz 24 Worst pair to pair near end crosstalk dB minimu...

Страница 29: ...CG SV01B E4 29 Notes...

Страница 30: ...30 CG SV01B E4 Notes...

Страница 31: ...CG SV01B E4 31 Notes...

Страница 32: ...maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty Training The e...

Отзывы: