Display menu: “Data display”

From the menu screen, select “

Data

Display

” then press 

Pressing or will 

allow

navigation from screen 1 to 8 as
shown hereafter:

The menu is looped making it
possible to scroll from the first item
in the menu to the last item.

1. Water and air temperatures
Lvg Wat Temp  =

Leaving water

temperature

Ret Wat Temp  =

Entering water

temperature

Amb Temp  =

Ambient air

temperature

Active StP =

Active water setpoint

2. Refrigerant pressures
HP ckt1 =

Condensing Pressure

circuit 1

HP ckt2 =

Condensing Pressure

circuit 2 (dual circuit units only)

LP ckt1 =

Evaporating Pressure

circuit 1

LP ckt2 =

Evaporating Pressure

circuit 2 (dual circuit units only)

3. Refrigerant saturated temperatures

Sat Temp CDS1 =

Condensing

temperature circuit 1

Sat Temp CDS2 =

Condensing

temperature circuit 2 (dual circuit
units only)

Sat Temp EVP1 =

Evaporating

temperature circuit 1

Sat Temp EVP2 =

Evaporating

temperature circuit 2 (dual circuit
units only)

Legend for screens 4,5 and 6:
Cmp A1 =

Compressor A/circuit 1

Cmp B1/C1 =

Compressor B and

C/circuit 1

Cmp A2 =

Compressor A/circuit 2

(dual circuit units only)

Cmp B2/C2 =

Compressor B and

C/circuit 2 (dual circuit units only)

4. Compressors status

Possible Status:

Off = 

Compressor stopped

On =

Compressor running

Rec.On =

Compressor will start after

anti-short cycle

Rec.Off =

Compressor will stop after

anti-short cycle

5. Compressors running time
Hrs

indicates the number of full

hours compressor has been working
since its first start.

6. Number of compressors starts

Starts

indicates the number of

compressor starts since first start-up.

7. Operating mode

Mode =

Running mode

-

Cooling =

Cold water production

-

Heating =

Hot water production 

(Reversible chillers only)

Stp         Local       07.0°C

-

Stp =

Current setpoint

-

Local = 

Source of Setpoint

Local =

Cooling or heating 

setpoint defined locally

Extern =

Auxiliary setpoint 

or operating mode by 
external contact

Auto =

setpoint by the 

automatic reset or the 
daily/weekly program

Remote =

Setpoint by 

supervisor

Ckt1/Ckt 2 =

Operational circuits

-

Enable =

Circuit is operational

-

Disable =

Circuit is not 

operational

8. Compressors failures counters

This menu indicates the number of
compressors failure regardless of
the history.

Lvg Wat Temp

08.0°C

Ret Wat Temp

12.0°C

Amb Temp

28.0°C

Active StP

07.0°C

HP ckt1

00.0 bar

HP ckt2

00.0 bar

LP ckt1

00.0 bar

LP ckt2

00.0 bar

Sat Temp  CDS1

00.0°C

Sat Temp  CDS2

00.0°C

Sat Temp  EVP1

00.0°C

Sat Temp  EVP2

00.0°C

Cmp A1

Off

Cmp B1 C1

Off

Cmp A2

Off

Cmp B2 C2

Off

Cmp A1

000000 Hrs

Cmp B1 C1

000000 Hrs

Cmp A2

000000 Hrs

Cmp B2 C2

000000 Hrs

Mode

Cooling

Stp         Local

07.0°C

Ckt1

Enable

Ckt2

Enable

Nb of CMP faults

Cpt

A1:0

Cpt A 2:0

Cpt

B1:0

Cpt B 2:0

Cpt

C1:0

Cpt C 2:0

Cmp A1

000000 Starts

Cmp B1 C1

000000 Starts

Cmp A2

000000 Starts

Cmp B2 C2

000000 Starts

Содержание TRACER CH532

Страница 1: ...TRACER CH532 Chiller controller User guide CG SVU01B E4...

Страница 2: ...ven as a guide to good practice in the installation start up operation and periodic maintenance by the user of TRACER CH532 chiller controller They do not contain the full service procedures necessary...

Страница 3: ...sentation 4 Hardware architecture 5 Starting stopping the unit 9 Menus 10 Display menu Data display 11 Customer settings menu Settings 12 Clock Setting menu Clock 15 Unit configuration menu Configurat...

Страница 4: ...display 1 4 lines x 20 characters with back lighting 6 buttons 2 to 7 Figure 1 TRACER CH532 user interface 2 Alarm button Used for displaying or manually resetting the alarms The red LED lights up wh...

Страница 5: ...CG SVU01B E4 5 Hardware architecture Figure 2 TRACER CH532 inputs and outputs Prg Esc 9 9 10 11...

Страница 6: ...ower on Red LED Alarm 3 Fuse 2A 5x20 4 Universal Analog inputs NTC 0 1V 0 10V 0 20mA 4 20mA 5 Passive Analog Inputs NTC PT1000 ON OFF 6 Analog Outputs 0 10V 7 Digital Inputs 24Vac Vdc 8 Digital Inputs...

Страница 7: ...ID9 24Vac DI Water pump 2 fault ID10 24Vac ID10 24Vac DI Faults external reset ID6 24Vac ID6 24Vac DI Cooling Heating mode switch ID7 24Vac ID7 24Vac DI Unused ID11 ID12 DO Compressor A circuit 1 outp...

Страница 8: ...aving water temperature setpoint 2 Minimum value 3 Maximum value 4 Reset 20 C 5 Active setpoint Table 3 Customer Inputs and output summary list TRACER CH532 Medium TRACER CH532 Large Single circuit un...

Страница 9: ...ss 4 Press or to change from N to Y 5 Press Following screen will be displayed 2 Stopping the unit 1 Press to exit from any menu and return to default display 2 Press for 3 seconds unit will stop and...

Страница 10: ...ed It allows access to the settings of Day of the week hour date Daily or weekly program Hourly zone program Configuration menu This menu is password protected It allows to adjust or change Unit defin...

Страница 11: ...fter anti short cycle Rec Off Compressor will stop after anti short cycle 5 Compressors running time Hrs indicates the number of full hours compressor has been working since its first start 6 Number o...

Страница 12: ...int 4 Reset delta 5 Active set point Below the reset starting point the water temperature setpoint will be the normal setting Between the starting and ending point the setpoint will vary proportionall...

Страница 13: ...ndications concerning this circuit ALL All alarms manual and automatic reset ALL But LA All alarms but without Low Ambient alarm MR only Manual reset alarms only factory setting Status output NO10 Add...

Страница 14: ...of the parameters displayed press and change value using or Confirm the value by pressing Local Setpoints are entered on the module Orders sent from the BMS are not taken into account Remote Orders s...

Страница 15: ...r 2 ON OFF program type When enabled this program will control the unit operation On Off This program will allow the user to Make a choice between the daily and or the weekly operation Define the oper...

Страница 16: ...d change value using or Confirm the value by pressing Start Start time Stop Stop time 3 Hourly Zone The Daily weekly program will allow you to define the cooling mode and heating mode setpoints It wil...

Страница 17: ...p all the fans but will allow the compressors to run before being stopped by HP switch Water Pump Water pump type Single Single pump control Dual Dual pump control Note Pump operation The water pumps...

Страница 18: ...or meaning of message Message 47 Pump 1 Pump protection input Pump 2 Pump 1 Operation Enable Disable Pump 2 Pump 1 Pump control outputs Pump 2 Fault reset Message 46 Message 46 Unit stopped manual res...

Страница 19: ...etting 5 bar 4 Control dead bands To access one of the parameters displayed press and change value using or Confirm the value by pressing Dead band Cmp Compressors regulation dead band around water te...

Страница 20: ...imer after compressor start 0 to 300 s factory setting 60s HP Cool StP High pressure limit in cooling mode 15 to 40 bar factory setting 28 bar HP Heat StP High pressure limit in heating mode 15 to 40...

Страница 21: ...en defrost cycle 15 to 60min factory setting 25 min Note Dual circuits have two independent refrigerant circuits Defrost cycle will only occur on the circuit that needs it The other circuit will conti...

Страница 22: ...er is set to show a circuit fault Fault with manual reset when the cause of the fault disappears a manual reset is required to restart the unit The messages displayed on the user interface screen disa...

Страница 23: ...Auto Manual CMP A2 Off Manu if CMP A2 failure 35 min or 6 failures within 3 hours 30 min 27 Alarm Comp B2 Fault Auto Manual CMP B2 Off Manu if CMP B2 failure 35 min or 6 failures within 3 hours 30 min...

Страница 24: ...while unit On Water Pump 1 Manual Unit On Fault on water pump 1 Water Pump 2 Manual Unit On Fault on water pump 2 Water Flow Auto Unit Off Defrost Ckt1 Auto Unit On Defrost on circuit 1 Defrost Ckt2 A...

Страница 25: ...the official LonWorks guidelines LonMark layer 1 6 interoperability guidelines version 3 0 These documents and additional information are available on the internet site www lonmark org Figure 9 1 3 2...

Страница 26: ...rdware During the activation of the service pin The node is Applicationless LED blinks 1second then always OFF When receiving a WINK command from the network 1 LED blinks second ON then always OFF Nor...

Страница 27: ...ssor A2 fault compressor B2 fault compressor C2 fault pump 1 fault pump 2 fault nv16 chlr_off 0 chlr_run 2 HVAC_HEAT 1 HVAC_COOL 3 Chiller state 0 No alarm 1 In alarm Run _enable 0 Chiller not allowed...

Страница 28: ...0 MHz 100 15 20 0 MHz 100 15 Attenuation dB 1000 feet at 20 C maximum 772 kHz 4 5 1 0 MHz 5 5 4 0 MHz 11 8 0 MHz 15 10 0 MHz 17 16 0 MHz 22 20 0 MHz 24 Worst pair to pair near end crosstalk dB minimu...

Страница 29: ...CG SV01B E4 29 Notes...

Страница 30: ...30 CG SV01B E4 Notes...

Страница 31: ...CG SV01B E4 31 Notes...

Страница 32: ...maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty Training The e...

Отзывы: