Pub. No.  18-HD29D2-4

7

Installer’s Guide

Features

Cycle Rate

The selected number of system cycles per hour. If the cycle
rate were set to 3, each cycle would be 20 minutes long. The
total ON and/or OFF  times depends on actual indoor space
load. A shorter cycle rate (more cycles per hour) may be
desired for Heating in order to maintain a tighter control on
indoor setpoint. A longer cycle rate may be desirable for
Cooling so the system has the opportunity to remove
moisture from the air and improve indoor comfort.

Auto Changeover

 When the system mode is set to AUTO, the control automati-

cally switches between heating and cooling modes to
maintain the desired comfort level.

Setpoint Deadband

 The number of degrees separating Heating and Cooling

setpoints. The amount of separation between mode
setpoints is user defined between 2 and 10 degrees. When
the control is set to AUTO, and the cooling setpoint is
changed to a cooler setting, the heating setpoint also
changes to maintain the selected degrees separation. The
same action occurs when the heating setpoint is changed to
a warmer temperature.

Backlit Display & Keys

The liquid crystal display and the keypad will illuminate
whenever a keypad button is pressed to improve control
visibility.  The back light stays on for 10 seconds after the
last key press.

Cooling Droop

Cooling Droop is an automatic function that cycles the
compressor on to improve indoor comfort by removing
moisture from the air. The Droop cycle is activated when
temperature is at or below the cooling  temperature
setpoint. When this function is active, the control will
control temperature at 1 or 2 degrees below cooling
setpoint. The Droop cycle is deactivated when the tempera-
ture rises above the cooling setpoint.

Energy Savings

The Energy Savings mode provides energy savings by
offsetting the indoor setpoint to a cooler temperature
setting for heating and a warmer temperature setting for
cooling.

The Energy Savings mode is activated by pressing the
Energy Savings key “$” on the control’s keypad. Pressing
the Energy Savings key “$” again deactivates the Energy
Savings mode. Pressing and holding the Energy Savings
key “$” provides quick access to the setpoint offset for both
heating and cooling.

Filter Reminder

FILTER”

 will automatically flash to remind the home-

owner that it is time to change the filter once the preset
time has expired. Pressing the “Filter/OD” keypad button
resets the internal clock timer. Once the timer has been
reset,  the number of days remaining  until the next filter
change can easily be determined by simply pressing the
“Filter/OD” keypad button once more. Pressing and holding
the “Filter/OD” keypad button provides quick access to the
filter timer value.

Keypad Lock

Locking the control’s keypad can help prevent unwanted
tampering  or changing the thermostat settings by pressing
the controls UP and DOWN arrow keypad buttons at the
same time and holding for 2 seconds.  “Keypad Locked”  will
be displayed on the LCD. Repeating this combination
unlocks the keypad and the “Keypad Locked” will disap-
pear.

Business Card Drawer

The drawer attached to the mounting base of the control is
designed to provide a convenient location for the home
owner to locate their local servicer. A standard business
card can be folded and inserted into the slot on the drawer
to remind the User whom to call when service is required.

LitePort

LitePort is a patented feature that allows the servicer
access to extended real-time and history data events stored
in the Comfort Controls memory.

Manual Test Mode

The built in Manual Test Mode allows the servicer to
quickly and easily test the control’s individual control
outputs and makes diagnostic procedures a snap.
Set the Mode to OFF, set the Fan to AUTO, and press the
MODE and DOWN arrow keypad buttons at the same time
and hold for 2 seconds. See Table 1, steps 70-78 for details.

Default Factory Settings

The thermostat is shipped with a set of factory default
settings. The factory default settings can be restored at any
time using the control configuration menu. (See Table 3,
step 99).

Service Indicator

The

 “SERVICE”

  indicator automatically flashes when an

internal fault or error has been detected by the Comfort
Control.

Minimum Off Time Delay Override

Minimum Off time delays can be overridden for the current
cycle by pressing the Mode and Down arrow keys at the
same time for approximately 2 seconds. It may be neces-
sary to lower the indoor setpoint for cooling or increase the
setpoint for heating to activate the system. Minimum off
time delays will be enforced on the next cycle.

Wait Indicator

“Waiting”  will illuminate when the indoor setpoint is
moved in the direction of calling for additional system
capacity.  “Waiting” indicates system time delays are being
enforced and that the control is adjusting to the new
settings.

Calibrate Indoor Temperature

This option allows calibration of the room temperature
sensor. The selected number is number of degrees, plus or
minus, which will be added to actual temperature. The
number can range b 5 and - 5 degrees in 1/2 degree
increments. Factory default is 0. This adjusted value will be
used as actual temperature for both display and control
action. For example, if 2 is selected, 72 degrees actual will
read 74 degrees.

Содержание TCONT401AN21MA Comfort Control

Страница 1: ...e signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING sign...

Страница 2: ...thermostat is being replaced a Remove existing thermostat from wall b Disconnect wires from existing thermostat one at a time Be careful not to allow wires to fall back into the wall c As each wire i...

Страница 3: ...RT CONTROL TERMINAL BLOCK SINGLE STAGE OIL FURNACE SINGLE STAGE COOLING SINGLE STAGE AIR CONDITIONER FAN SOV COOLING HEATING 1st HEATING 2nd W2 X2 O SINGLE STAGE OIL FURNACE B C OD TEMP T R1 R1 Figure...

Страница 4: ...STANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62...

Страница 5: ...ee increments 50 Compressor Cooling Cycle Minimum On Time Minutes 3 2 4 CPH 1 15 Minutes 5 CPH 1 7 Minutes 6 CPH 1 5 Minutes 20 Exit User Setup Press Mode SA CA Cancel SA Save US Default User Settings...

Страница 6: ...enough to prevent overshooting Set Control Response rate to Fast Step 33 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or...

Страница 7: ...n easily be determined by simply pressing the Filter OD keypad button once more Pressing and holding the Filter OD keypad button provides quick access to the filter timer value Keypad Lock Locking the...

Страница 8: ...hich will be added to actual temperature The number can range between 5 and 5 degrees in 1 2 degree increments Factory default is 0 This adjusted value will be used and displayed as actual temperature...

Отзывы: