Pub. No.  18-HD29D2-4

3

Installer’s Guide

8. Match and connect control wires to proper terminals on the

connector block. (See figures 3, 4 & 5).

9. Push any excess wire back into the wall and 

seal the hole

to prevent air leaks

.

Note: Air leaks in the wall behind the control can cause
improper operation.

R

G

Y

R

G

W1

W1

OT

OT

W2

Y

Y

B

B

24VAC HOT

24VAC 

COMFORT CONTROL 
TERMINAL BLOCK

HEAT PUMP - AIR HANDLER

HEAT PUMP

FAN

SOV

COOLING

HEATING -1st

HEATING -2nd

W2/ 

X2

O

O

O

R

T

AIR HANDLER &
ELECTRIC HEAT

B

C

OD
TEMP

T

X2

NOTE:
IF ODT-1 IS NOT USED, THEN CONNECT A JUMPER WIRE FROM W1 TO W2.

10.Check the operation of the business card drawer. Verify

that it slides in and out without binding.

11. Reinstall the control on its mounting base by aligning the

control at the top of the mounting base. Swing the
control downward and gently press the bottom of control
into position until latch button A engages. See Figure 1.

12. Turn ON power to the heating and cooling equipment.

SETUP

Enter INSTALLER Setup:

(See Table 3, step 1 - 33 for option details)

1.) Set System Mode to OFF

2.) Set Fan to AUTO

3.) Press and hold Mode and Up Arrow at the same

time.

4.) SET-UP will appear on display. See Figure 6.

R

G

Y

R

G

W1

OT

OT

Y

Y

B

W

B

24VAC HOT

24VAC 

COMFORT CONTROL 
TERMINAL BLOCK

SINGLE STAGE OIL FURNACE - SINGLE STAGE COOLING

SINGLE STAGE 
AIR CONDITIONER

FAN

SOV

COOLING

HEATING -1st

HEATING -2nd

W2/ 

X2

O

SINGLE STAGE  
OIL FURNACE

B

C

OD
TEMP

T

R1

R1

Figure 4

Figure 5

Figure 6

When applying this Comfort Control in DUAL FUEL APPLI-
CATIONS using a two-stage gas or oil furnace, select Single
Stage Heat (a setting of 1) for Heater Stages in Step 8 of
Installer Setup and wire according to the external dual fuel
kit instructions. See Table 3.

Enter USER Setup:

(See Table 3, step 40-50 for option details)

Press and hold Mode and Fan at the same time.

Note:  Allow a minimum of 5 seconds after saving selections
(Step 99 - SA) for the control to write selections to memory.
If power is lost or removed prior to the 5 second elapsed
time, the selections may be lost and must be reentered. If
the SERVICE icon is flashing on the control LCD, press any
key and check / re-enter setup choices.

Keypad Navigation:

Use the Mode and Fan buttons to navigate forward and
backward through the configuration and Manual Test Mode
steps.
Press Mode to advance forward to the next step.
Press Fan to return to the previous step.

Use the Up and Down arrow buttons to select or change
setup options.

Lock - Unlock Keypad:

Press and hold Up Arrow and Down Arrow at the same time.

(“Keypad Locked” will display on LCD screen)

Defeat Equipment Time Delay:

(Current Cycle only) Press Mode and Down

Arrow at the same time.

Содержание TCONT401AN21MA Comfort Control

Страница 1: ...e signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING sign...

Страница 2: ...thermostat is being replaced a Remove existing thermostat from wall b Disconnect wires from existing thermostat one at a time Be careful not to allow wires to fall back into the wall c As each wire i...

Страница 3: ...RT CONTROL TERMINAL BLOCK SINGLE STAGE OIL FURNACE SINGLE STAGE COOLING SINGLE STAGE AIR CONDITIONER FAN SOV COOLING HEATING 1st HEATING 2nd W2 X2 O SINGLE STAGE OIL FURNACE B C OD TEMP T R1 R1 Figure...

Страница 4: ...STANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62...

Страница 5: ...ee increments 50 Compressor Cooling Cycle Minimum On Time Minutes 3 2 4 CPH 1 15 Minutes 5 CPH 1 7 Minutes 6 CPH 1 5 Minutes 20 Exit User Setup Press Mode SA CA Cancel SA Save US Default User Settings...

Страница 6: ...enough to prevent overshooting Set Control Response rate to Fast Step 33 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or...

Страница 7: ...n easily be determined by simply pressing the Filter OD keypad button once more Pressing and holding the Filter OD keypad button provides quick access to the filter timer value Keypad Lock Locking the...

Страница 8: ...hich will be added to actual temperature The number can range between 5 and 5 degrees in 1 2 degree increments Factory default is 0 This adjusted value will be used and displayed as actual temperature...

Отзывы: